DKG-329 AUTOMATIC
TRANSFER SWITCH
CONTROLLER
WITH UNINTERRUPTED TRANSFER AND MULTIPLE GENSET SUPPORT
DESCRIPTION FEATURES
The DKG-329 is microprocessor controlled unit True RMS measurements
designed to monitor 3-phase mains voltages, send Synchroscope & check synch
remote start command to generating sets and No break transfer& no break load test
control the changeover of generator and mains Automatic contactor control
contactors.
Multiple genset system support
The unit offers an internal synchroscope for Load shedding, dummy load
uninterrupted transfer in both directions. The Event logging with time stamp and measurements
number of gensets to run before transfer is
Battery backed-up real time clock
selectable, allowing multiple genset support.
Built in daily / weekly / monthly exerciser
If a fault condition occurs, the unit disables the
Weekly operation schedule programs
remote starting automatically and indicates the
Field adjustable parameters
failure with the corresponding led lamp and text.
RS-232 serial port
The unit provides a comprehensive set of digitally
adjustable program parameters. The unauthorized Free MS-Windows Remote monitoring SW
access to program parameters is prevented by a 3 GSM and PSTN modem support
level password system. All programs may be GSM SMS message sending on fault
modified via front panel pushbuttons and do not MODBUS communications
require any external unit. Multiple language support
Last 100 faults are stored in the event log file. The Customer logo display capability
event log includes not only the date-time 16 Amp contactor outputs
information, but also a comprehensive list of
1 Amp DC semiconductor control outputs
measured parameters at the time that the fault has
occurred. Configurable digital inputs: 7
Configurable digital outputs: 3
The WINDOWS based RAINBOW program
allows remote monitoring and control. Total digital outputs: 6
The unit supports MODBUS protocol enabling I/O expansion capability
communication with PLCs and building Plug-in connection system
management systems. The MODBUS protocol is Sealed front panel
also supported through GSM and PSTN
modems.
DKG-329 User Manual V-12 (09.10.2012)
TABLE OF CONTENTS
Section
1. INSTALLATION
1.1. Introduction to the Control Panel
1.2. Mounting the Unit
1.3. Wiring the Unit
2. INPUTS AND OUTPUTS
3. DISPLAYS
3.1. Led Displays
3.2. Language Selection
3.3. Digital Display
4. ALARMS AND WARNINGS
5. MODES OF OPERATION
6. LOAD TRANSFER MODES
6.1. Transfer with Interruption
6.2. No Break Transfer
7.OTHER FEATURES
7.1. Remote start operation
7.2. Mains Simulation (Disable Start)
7.3. Delayed Mains Simulation, Battery Charging
7.4. Service Request Display
7.5. Engine Hours Meter
7.6. Date-Time Display
7.7. Display of Software Version
7.8. Modem connection
7.9. SMS message sending
7.10. Remote Monitoring and Programming
7.11. External Control of the Unit
7.12. Automatic Exerciser
7.13. Resuming to factory set parameters
7.14. Load Shedding / Dummy Load
7.15. Firmware Update
7.16. Pre-Transfer Signal
8. MODBUS COMMUNICATION
9. WEEKLY OPERATION SCHEDULE
10. EVENT LOGGING
11. STATISTICAL COUNTERS
12. MAINTENANCE
13. PROGRAMMING
14. TROUBLESHOOTING
15. DECLARATION OF CONFORMITY
16. TECHNICAL SPECIFICATIONS
17. CONNECTION DIAGRAM
-2-
DKG-329 User Manual V-12 (09.10.2012)
1. INSTALLATION
The unit is a control and protection panel designed to monitor the 3-phase mains voltages, send remote
start command to the generating set and make changeover of both generator and mains contactors. The genset is
supposed to be controlled by a Remote Start type control unit. It shows the measured values on its display. The
unit is designed to provide user friendliness for both the installer and the user. Programming is usually
unnecessary, as the factory settings have been carefully selected to fit most applications. However
programmable parameters allow the complete control over the load transfer. Programmed parameters are
stored in a Non Volatile Memory and thus all information is retained even in the event of complete loss of
power.
The unit is designed for panel mounting. The user should not be able to access parts of the unit
other than the front panel.
Mount the unit on a flat, vertical surface. Before mounting, remove the mounting brackets and
connectors from the unit, then pass the unit through the mounting opening. The unit will be maintained in its
position by the mounting brackets spring.
The output of the current transformers shall be 5 Amperes. The input current rating of the current
transformers may be selected as needed (between 10/5 and 9000/5 amps). Current transformer outputs
shall be connected by separate cable pairs from each transformer, to related inputs. Never use common
terminals or grounding. The power rating of the transformer should be at least 5 VA. It is recommended to
use 1% precision transformers.
Programmable digital inputs are compatible with both ‘normally open’ and ‘normally closed’
contacts, switching either to BAT- or BAT+.
-3-
DKG-329 User Manual V-12 (09.10.2012)
-4-
DKG-329 User Manual V-12 (09.10.2012)
-5-
DKG-329 User Manual V-12 (09.10.2012)
-6-
DKG-329 User Manual V-12 (09.10.2012)
3. DISPLAYS
-7-
DKG-329 User Manual V-12 (09.10.2012)
The unit is able to display information in 3 languages. Language selection is made through program
parameter CONTROLLER CONFIGURATION > LANGUAGE SELECTION. Below selections are available:
0: English language
1: Turkish language
2: Chinese language
3: ask selection at power-up
If language is set to 3, below screen will come at power on:
Left / Up / Down arrow pushbuttons will select the screen language. The language will be asked
everytime power is turned on.
With selections of 0,1,2 this screen will not appear and the selected language is enabled.
-8-
DKG-329 User Manual V-12 (09.10.2012)
-9-
DKG-329 User Manual V-12 (09.10.2012)
Alarms indicate an abnormal situation in the generating set are divided into 3 priority levels:
1- ALARMS: These are the most important fault conditions and cause:
- The ALARM led to be on steadily,
- The genset contactor to be released immediately,
- The engine to be stopped immediately,
- The Horn, Alarm, Alarm+Load_dump and Alarm+Load_dump+Warning digital
outputs to operate, (if selected via programming menu)
If the ALARM MUTE button is pressed, the Horn output will be deactivated; however the
existing alarms will persist and disable the operation of the genset.
Alarms may be of LATCHING type following programming. For latching alarms, even if the alarm
condition is removed, the alarms will stay on and disable the operation of the genset. The existing alarms
may be canceled by pressing one of the operating mode buttons (LOAD TEST / TEST / OFF / AUTO).
Most of the alarms have programmable trip levels. See the programming chapter for adjustable
alarm limits.
- 10 -
DKG-329 User Manual V-12 (09.10.2012)
STOP FAIL (warning): Set if the engine has not stopped before the expiration of the Stop Timer.
OVERLOAD (load_dump): Set if at least one of the genset phase currents goes over the Overcurrent
Limit for Overload Timer. If currents goes below the limit before expiration of the timer then no alarm will
be set.
EXCESS POWER (load_dump): Set if the genset power (kW) supplied to the load goes over the Excess
Power limit for Overload Timer. If the power goes below the limit before expiration of the timer then no
alarm will be set.
GENSET LOW VOLTAGE: Set if any of the generator phase voltages goes outside programmed limits for
Overload Timer. This fault will be monitored with holdoff timer delay after the engine is running.
GENSET HIGH VOLTAGE: Set if any of the generator phase voltages goes outside programmed limits for
Overload Timer. This fault will be monitored with holdoff timer delay after the engine is running.
LOW BATTERY VOLTAGE (warning): Set if the battery voltage goes below the programmed limit.
HIGH BATTERY VOLTAGE: Set if the battery voltage goes above programmed limits. Both warning and
alarm levels for high battery voltage are programmable.
MAINS PHASE ORDER FAIL (warning): Set if the mains phase order checking is enabled, mains phases
are present and mains phase order is reversed. This fault prevents the Mains Contactor to close.
5. MODES OF OPERATION
The modes of operation are selected by pushing the front panel keys. Changing the operation
mode while the genset is running will result to a behavior suitable for the new operating mode. For example,
if the LOAD TEST mode is selected when genset is running at TEST mode, then the load will be transferred
to the genset.
OFF: In this mode, the mains contactor will be energized if mains phase voltages are within the
programmed limits. The engine will be stopped.
AUTO: It is used for genset and mains automatic transfer. If at least one of the mains phase voltages is
outside limits, the mains contactor will be deactivated and the REMOTE START output will be activated at
the end of the start wait period. The engine will run without load during engine heating period. After this, if
alternator phase voltages and frequency are within limits, then the unit will wait for the generator contactor
period and the generator contactor will be energized.
When all the mains phase voltages are within the limits, the engine will continue to run for the mains waiting
period. At the end of this period the generator contactor is deactivated and the mains contactor will be
energized. If a cooling period is given, the REMOTE START output will be active during the cooling period.
At the end of the period, the REMOTE START output will be de-energized and the diesel will stop. The unit
will be ready for the next mains failure. If the operation of the genset is disabled by the weekly schedule,
then the AUTO led will flash, and the operation of the genset will be as in the OFF mode.
TEST: It is used to test the generator when the mains are on, or keep the generator running in the
emergency backup mode. The operation of the generator is similar to the AUTO mode, but the mains
contactor will not be deactivated if the mains are not off. If the mains are off, mains contactor will be
deactivated and the generator contactor will be activated. When the mains are on again, a changeover to
the mains will be made, but the engine will be kept running unless another mode is selected. To stop the
engine, select AUTO or OFF mode.
LOAD TEST: It is used to test the genset under load. Once this mode is selected, the engine will run and
the load will be transferred to the genset. The genset will feed the load indefinitely unless another mode is
selected.
- 11 -
DKG-329 User Manual V-12 (09.10.2012)
The unit has two ways of transferring the load from genset to mains and vice versa.
This is the most conventional way of transferring the load between the genset and mains. There
will be a power interruption period duration during the transfer. Note that the program parameters Mains
Contactor Timer and Genset Contactor Timer define the power interruption period.
In this mode, the transfer will be made without power interruption. This implies that both of
the mains and generator contactors will be active during transfer.
The maximum duration that both contactors will be activated is programmable. However this
process may be quicker with the use of one auxiliary contact at each contactor. Thus the changeover
will be quite instantaneous, preventing any excess or reverse power condition. Any digital input can be
programmed for genset contactor auxiliary contact and mains contactor auxiliary contact.
The unit will allow a No Break Transfer only if all of the below conditions are fulfilled:
-Mains phase voltages within the programmed limits,
-Mains frequency within the programmed limits,
-Genset phase voltages within the programmed limits,
-Genset frequency within the programmed limits,
-Mains phase order correct (or phase order check must be disabled),
-Genset phase order correct (or phase order check must be disabled),
-The difference between mains and genset frequencies not more than programmed limit,
-The voltage difference between mains_L1 and genset_L1 not more than programmed limit,
-The phase angle between mains_L1 and genset_L1 not more than programmed limit,
- 12 -
DKG-329 User Manual V-12 (09.10.2012)
When a No Break Transfer cycle is initiated, the unit checks all the above criteria to be
satisfied as long as the Synchronization Fail Timeout is not expired.
Normally with frequencies matching at +/- 2Hz and voltages matching at +/-10 volts an
uncontrolled No Break Transfer will be successfull.
If synchronization conditions are not met at the expiration of the Synchronization Fail
Timeout, then the unit reverts to a Transfer with Interruption.
If matching is found before the expiration of the Synchronization Fail Timeout, then both
contactors will be activated. If contactor auxiliary contacts are used, the other contactor will release
immediately. If contactor auxiliary contacts are not used, the other contactor will release after contactor
timeout.
The unit has a set of programmable parameters to define the No Break Transfer operation.
These parameters are:
Mains Voltage Low Limit (Electrical Parameters): Each of the mains phase voltages must be over
this limit.
Mains Voltage High Limit (Electrical Parameters): Each of the mains phase voltages must be below
this limit.
Mains Frequency Low Limit (Electrical Parameters): The mains frequency must be over this limit.
Mains Frequency High Limit (Electrical Parameters): The mains frequency must be below this limit.
Genset Voltage Low Limit (Electrical Parameters): Each of the genset phase voltages must be over
this limit.
Genset Voltage High Limit (Electrical Parameters): Each of the genset phase voltages must be
below this limit.
Low Frequency Shutdown (Engine Parameters): The genset frequency must be over this limit.
Low Frequency Warning (Engine Parameters): The genset frequency must be over this limit.
High Frequency Shutdown (Engine Parameters): The genset frequency must be below this limit.
High Frequency Warning (Engine Parameters): The genset frequency must be below this limit.
Genset Phase Order Enable(Electrical Parameters): If set , this parameter will enable the phase
order check for genset. The phase order check should be disabled only in single phase gensets.
Mains Phase Order Enable(Electrical Parameters): If set, this parameter will enable the phase order
check for mains.
No Break Transfer(Controller Config Parameters): This parameter enables/disables the No Break
Transfer feature.
Max Frequency Difference(Controller Config Parameters): This is the maximum difference between
mains and genset frequencies to enable a NO Break Transfer.
Max Voltage Difference(Controller Config Parameters): This is the maximum difference between the
mains_L1 and genset_L1 voltages to enable a NO Break Transfer.
Max Phase Difference(Controller Config Parameters): This is the maximum phase difference
between the mains_L1 and genset_L1 to enable a No Break Transfer.
Synchronization Fail Timeout (Controller Config Parameters): If the phase and voltage
synchronization is not successful before the expiration of this timer, then the unit terminates the No
Break Transfer and makes a Transfer with Interruption.
Contactor Timeout (Controller Config Parameters): This is the maximum time duration in which both
contactors are active in case of No Break Transfer.
Any digital input may be assigned as mains and genset contactor feedback input for faster transfer.
For this, “digital input function select parameter group” is used to select the function and “input
configuration parameter group” is used to configure digital inputs. The action parameter should be
set to 3 and “always active” option should be selected for both contactor feedback inputs. NC type
must be selected for mains contactor feedback input.(Pls refer to programming chapter for more
detailed explanation)
- 13 -
DKG-329 User Manual V-12 (09.10.2012)
7. OTHER FEATURES
The unit offers the possibility of REMOTE START mode of operation. Any digital input may be
assigned as Remote Start Input using Input Function Select program parameters.
The REMOTE START signal may be a NO or NC contact, switching to either battery positive or
battery negative. These selections are made using programming menu.
It is also necessary to set the ACTION program parameter of the related input to 3 in order to
prevent any alarm from this input.
In this mode the mains phases are not monitored. If the REMOTE START signal is present then
the mains will be supposed to fail, inversely if the REMOTE START signal is absent, then mains
voltages will be supposed to be present. The front panels mimic diagram’s mains LEDs will reflect the
status of the REMOTE START input.
The unit offers an optional SIMULATE MAINS signal input. Any digital input may be assigned
as Simulate Mains using Input Function Select program parameters.
It is also necessary to set the ACTION program parameter of the related input to 3 in order to
prevent any alarms generated from this input.
The SIMULATE MAINS signal may be a NO or NC contact, switching to either battery positive or
battery negative. These selections are made using the programming menu.
If the Simulate Mains input is defined and the input signal is active, the mains phases are not
monitored and supposed to be inside limits. This will prevent the genset from starting even in case of a
mains failure. If the genset is running when the signal is applied, then usual Mains Waiting and
Cooldown cycles will be performed before engine stop. When the SIMULATE MAINS signal is present,
the front panels mimic diagram’s mains LEDs will reflect the mains voltages as present.
When the signal is passive, the unit will revert to normal operation and monitor the mains
voltage status.
- 14 -
DKG-329 User Manual V-12 (09.10.2012)
The Delayed Mains Simulation feature is used in battery backed up telecom systems where
batteries are able to supply the load during a certain period. The genset is requested to run only when
battery voltage drops below the critical level. Once the engine runs, the rectifier system starts charging
the batteries and the battery voltage goes up immediately. Thus the engine should continue to run a
programmed period for effective charging. The critical battery voltage level will be detected by an
external unit which provides the digital Simulate Mains signal for the genset control unit.
The unit offers an optional SIMULATE MAINS signal input. Any digital input may be assigned
as Simulate Mains using Input Function Select program parameters.
It is also necessary to set the ACTION program parameter of the related input to 3 in order to
prevent any alarms generated from this input.
The SIMULATE MAINS signal may be a NO or NC contact, switching to either battery positive or
battery negative. These selections are made using the programming menu.
If the Delayed Simulate Mains program parameter is set to 1 and the input signal is active
when the genset is not feeding the load, the mains phases are not monitored and supposed to be inside
limits. This will prevent the genset from starting when the simulate mains signal is present (batteries
charged). The genset will start when mains voltages are out of limits and the simulate mains signal not
present.
If the genset is running when the signal is applied, then MAINS SIMULATION will be prevented
during Flashing Relay Timer program parameter. After this, usual Mains Waiting and Cooldown cycles
will be performed before engine stop. When the SIMULATE MAINS signal is present, the front panels
mimic diagram’s mains LEDs will reflect the mains voltages as present.
When the signal is passive, the unit will revert to normal operation and monitor the mains
voltage status.
- 15 -
DKG-329 User Manual V-12 (09.10.2012)
This led is designed to help the periodic maintenance of the genset to be made consistently.
The periodic maintenance is basically carried out after a given engine hours (for example 200
hours), but even if this amount of engine hours is not fulfilled, it is performed after a given time limit (for
example 12 months).
The unit has both programmable engine hours and maintenance time limit. The engine hours is
programmable with 50-hour steps, the time limit is programmable with 1 month steps. If any of the
programmed values is zero, this means that the parameter will not be used. For example a maintenance
period of 0 months indicates that the unit will request maintenance only based on engine hours, there will
be no time limit. If the engine hours is also selected as 0 hours this will mean that the SERVICE REQUEST
display will be inoperative.
When the engine hours OR the time limit is over, the SERVICE REQUEST led (red) will start to
flash and the service request relay function will be active.
The service request relay function may be assigned to spare relays using Relay Definition
program parameters. Also relays on an extension module may be assigned to this function.
The remaining engine hours and the remaining time limit are kept stored in a non-volatile memory
and are not affected from power supply failures.
The time and engine hours to service are displayed in the STATISTICAL COUNTERS menu.
The unit features a non-erasable incremental engine hour meter. The hour meter information is
kept in a non-volatile memory and is not affected from power supply failures.
- 16 -
DKG-329 User Manual V-12 (09.10.2012)
Some additional features are installed within consecutive software releases. In order to be sure
of the validity of the status of the unit, the software version needs to be known.
The software version of the unit is displayed together with the data – time information.
The software version consists of 2 numbers. The first number represent the operating software
version of the unit.
The unit is capable of making modem calls in case of alarm, as well as answering modem calls
made from a remote location. GSM modems and classic cable network (PSTN) modems are
acceptable.
If the modem is connected to the unit, the Modem Enable program parameter should be set to
1, otherwise faulty operation may occur.
A maximum of 2 telephone numbers can be defined for outgoing modem calls. In case of alarm,
the unit will attempt to reach control centers associated with each number. In case of modem
connection failure, the call will be repeated up to 30 times with 2 minute intervals.
When the modem call is in progress, a telephone icon ( ) will appear at the upper right
corner of the screen.
Advised modems are DATAKOM types which are powered up from the same DC battery
voltage than the unit. Most of other desktop modems with standard AT commands are also usable, but it
is the user’s responsibility to provide an uninterrupted AC supply source to the modem. The necessary
modem cable will be supplied by DATAKOM.
Modem calls are always terminated by the central RAINBOW software. However the unit does
not allow connection durations exceeding 2 minutes, and hangs up the modem when this period
expires.
The PC program used for remote monitoring and programming is the same RAINBOW software
used for RS-232 connection.
Please note that the modem operation is also compatible with the MODBUS communication.
Thus the unit can iniate and receive calls to/from a MODBUS master station. Please review chapter_8
for more details on MODBUS communication.
- 17 -
DKG-329 User Manual V-12 (09.10.2012)
The GSM SMS sending is activated by setting the SMS Enable program parameter to 1.
When a fault condition occurs, the unit will compose an SMS message and will send it to up to 6
phone numbers. If modem is enabled, only 4 telephone numbers are available for SMS sending.
The unit is also able to send SMS messages in below conditions, without creating a visible alarm or
warning:
Mains Fail, Mains Restored (enabled via SMS on Mains Change program parameter)
If both modem and SMS are enabled, the unit will send SMS messages first and attempt modem
connection afterwards.
When SMS sending is in progress, an (SMS) icon will appear at the upper right corner of the
screen.
The maximum number of alarms transmitted in a SMS message is 4. This limitation is due to the
maximum length of an SMS message which is 160 characters.
DKGxxx <SITE-ID>
STOP : EMERGENCY STOP.
END OF ALARM LIST
The first line of the message carries information about the unit type and the site identity string. This
line is intended for the identification of the genset sending the SMS message.
Each following line will give one fault information. The message will always be terminated by the
“END OF ALARM LIST” string.
When the message is sent, the existing alarms will be masked, causing the audible alarm relay to
release and preventing consecutive GSM SMS messages. Any new upcoming alarm will result in a new
GSM SMS message. The new message will indicate all existing alarms, even masked ones.
The necessary GSM modem cable will be supplied by DATAKOM. This is the same cable as
PSTN (land) modems.
- 18 -
DKG-329 User Manual V-12 (09.10.2012)
Thanks to its standard serial RS-232 port, the unit offers the remote monitoring and
programming feature.
The remote monitoring and programming PC software is called RAINBOW and may be
downloaded from www.datakom.com.tr internet site with password login.
The modem, SMS and Modbus modes are not compatible with the local PC connection. Modem
Enable, SMS Enable and MODBUS Address program parameters should be set to 0 before connection.
The RAINBOW software allows the visualization and recording of all measured parameters. The
recorded parameters may then be analyzed graphically and printed. The software also allows the
programming of the unit and the storage of the program parameters to PC or the downloading of stored
parameters from PC to the unit.
For PCs without a serial port, below USB to serial adapters are tested and approved :
DIGITUS USB 2.0 TO RS-232 ADAPTER (PRODUCT CODE: DA70146 REV 1.1)
DIGITUS USB 1.1 TO RS-232 ADAPTER (PRODUCT CODE: DA70145 REV 1.1)
FLEXY USB 1.1 TO SERIAL ADAPTER (PRODUCT CODE BF-810)
CASECOM USB TO SERIAL CONVERTER (MODEL: RS-01)
The unit offers total external control through programmable digital inputs. Each digital input may be
programmed for below external control functions:
- Force OFF mode
- Force AUTO mode
- Force TEST mode
- Force LOAD TEST mode
- Disable Auto Start
- Force to Start
- Fault Reset
- Alarm Mute
- Panel Lock
External mode select signals have priority on mode buttons of the unit. If the mode is selected by
external signal, it is impossible to change this mode with front panel keys. However if the external mode
select signal is removed, the unit will revert to the last selected mode via pushbuttons.
It is also possible to lock the front panel completely for remote command.
- 19 -
DKG-329 User Manual V-12 (09.10.2012)
7.12 Exerciser
The unit offers automatic exerciser operation. The exercise operation may be done on a daily,
weekly or monthly basis.
The start day and time of the exercise is programmable as well as its duration. The exercise
may be done with or without load following programming.
Please refer to the programming section for a more detailed description of the above
parameters.
When the start day and hour of exercise has come, the unit will automatically switch to either
TEST or LOAD TEST mode. The engine will run and if the on_load exercise is selected then the load
will be transferred to the genset.
If a mains failure occurs during the off-load exercise, the load will not be transferred to the
genset unless the Emergency Backup Operation is allowed by setting the related program parameter
to 1. Thus it is highly recommended that the Emergency Backup mode enabled with off-load exerciser.
At the end of the exercise duration, the unit will switch back to the initial mode of operation.
If any of the mode selection keys are pressed during exercise, then the exercise will be
terminated.
Using the daily exercise mode, the unit may feed the load from the genset during predefined
hours of the day. This operation may be used in high tariff periods of the day.
- 20 -
DKG-329 User Manual V-12 (09.10.2012)
The load shedding feature consists on the disconnection of the least crucial loads when the
genset power approaches to its limits. These loads will be supplied again when the genset power falls
below the programmed limit. The internal Load Shedding function is always active. Any of the auxiliary
relays may be used as the load shedding output.
The dummy load function consists on the connection of a dummy load if the total genset load is
below a limit and to disconnection of the dummy load when the total power exceeds another limit. The
dummy load function is the inverse of the load shedding function, thus the same output may be used for
both purposes.
The parameters used in Load Shedding feature are in the Electrical Parameters Group:
Load Shedding Low Limit: If the genset active power output goes below this limit, then the Load
Shedding relay will be deactivated.
Load Shedding High Limit: If the genset active power output goes above this limit, then the Load
Shedding relay will be activated.
The unit offers possibility of updating the firmware in the field. The firmware is updated through
the RS-232 serial port using Rainbow or a special DOS program.
The unit will go to firmware download mode with a special command from the PC program. In
download mode, the display of the unit will show “DL-V1.00”
During firmware update process, the progress is visible through a completion bar on the screen.
After completion of the update a special command will set back the unit to normal operation
mode.
- 21 -
DKG-329 User Manual V-12 (09.10.2012)
8. MODBUS COMMUNICATION
The unit offers the possibility of MODBUS communication via its RS232 serial port.
The connection to the MODBUS master may be done in 3 ways:
1) RS232 connection using directly the RS232 port provided.
2) RS422/485 connection using external RS422/485 converter.
3) Modem connection using external modem.
The MODBUS mode is activated by assigning a controller address to the unit using MODBUS
Address program parameter. The possible address range is 1 to 144. Setting the address to 0 will
disable the MODBUS mode and allow communication under RAINBOW protocol.
The MODBUS properties of the unit are:
-Data transfer mode: RTU
-Serial data: 9600 bps, 8 bit data, no parity, 1 bit stop
-Supported functions:
-Function 3 (Read multiple registers)
-Function 6 (Write single register)
Detailed description about the MODBUS protocol is found in the document “Modicon Modbus
Protocol Reference Guide”. The web address is: www.modbus.org/docs/PI_MBUS_300.pdf
Below is a limited shortlist of readable registers. For the detailed Modbus Application Manual
and a complete list of registers please contact DATAKOM.
- 22 -
DKG-329 User Manual V-12 (09.10.2012)
In most applications, the genset is requested to operate only in working hours. Thanks to the
weekly program feature unwanted operation of the genset may be prohibited.
The unit has one programmable turn-on/turn-off time pairs for each day of week. These
programmable parameters allow the genset to operate automatically only in allowed time limits.
The weekly operation schedule is only active in AUTO mode. In other modes it will not affect
the genset operation.
In AUTO mode, if the operation of the genset is disabled by the weekly schedule, then the
AUTO led will flash (instead of a steady on state).
If the same time is used for turn on and turn off, then it will be considered as a turn-on time.
The unit has a battery backed-up precision real time clock circuit. The real time clock circuit will
continue its operation even in power failures. The real time clock is precisely trimmed using the Real
Time Clock Adjust program parameter. For more details check the programming section.
- 23 -
DKG-329 User Manual V-12 (09.10.2012)
The unit keeps record of the last 100 events in order to supply information for the service personal.
The genset status information and a comprehensive set of measured values are stored within the event
memory. The events are recorded with a time stamp which comes from the internal real time clock
circuit of the unit.
The events are stored in a circular memory. This means that a new coming event will erase the oldest
recorded event. The events are always displayed starting from the most recent one.
Events are kept in a non-volatile memory and are not affected from power failures.
Switching from one menu screen to another is made with the ◄MENU and MENU►buttons.
When the EVENT RECORD screen is displayed, each depression on the ◄MENU button makes the
display switch to the previous event and MENU►button makes the display switch to the next event.
Each event is displayed in 4 pages. Event and page numbers are shown at the top right corner of the
display. Events are numbered starting from 1, number 1 being the latest one. Pages are listed from A to
D. Navigation between different pages of the same event is done with ▼and ▲buttons.
- 24 -
DKG-329 User Manual V-12 (09.10.2012)
The unit provides a set of non resettable incremental counters for statistical purposes.
These counters are kept in a non-volatile memory and are not affected from power failures.
12. MAINTENANCE
Wipe the unit, if necessary with a soft damp cloth. Do not use chemical agents
- 25 -
DKG-329 User Manual V-12 (09.10.2012)
13. PROGRAMMING
The program mode is used to program timers, operational limits and the configuration of the unit.
To enter the program mode, press together ◄MENU and MENU►buttons for 1 second. The
program mode is only allowed if the PROGRAM LOCK input is left open. If this input is tied to
GROUND, the program value modification will be disabled to prevent unauthorized intervention. It is
advised to keep the PROGRAM LOCK input tied to GROUND.
When the program mode is entered, below password entry screen will be displayed.
- 26 -
DKG-329 User Manual V-12 (09.10.2012)
- 27 -
DKG-329 User Manual V-12 (09.10.2012)
- 28 -
DKG-329 User Manual V-12 (09.10.2012)
- 29 -
DKG-329 User Manual V-12 (09.10.2012)
- 30 -
DKG-329 User Manual V-12 (09.10.2012)
- 31 -
DKG-329 User Manual V-12 (09.10.2012)
- 32 -
DKG-329 User Manual V-12 (09.10.2012)
- 33 -
DKG-329 User Manual V-12 (09.10.2012)
- 34 -
DKG-329 User Manual V-12 (09.10.2012)
- 35 -
DKG-329 User Manual V-12 (09.10.2012)
The parameters below define the functions of relay outputs. The unit has 6 relay outputs. The
fixed function relays are Remote Start, Alarm (Horn), Mains Contactor and Generator Contactor.
RELAY-1 and RELAY-2 have programmable functions, selected from a list.
The relays may be extended up to 22 using Relay Extension Modules. Other relays are in the
optional Extension Modules.
- 36 -
DKG-329 User Manual V-12 (09.10.2012)
- 37 -
DKG-329 User Manual V-12 (09.10.2012)
The function of a programmable relay output may be selected from the below list.
00 Remote Start 32 - 80 -
01 Alarm 33 - 81 -
02 - 34 - 82 -
03 - 35 - 83 -
04 Gen. Contactor 36 Emerg.Stop alarm 84 Emerg Stop warn.
05 Mains Contactor 37 Spare-1 Alarm 85 Spare-1 warning
06 - 38 Spare-2 Alarm 86 Spare-2 warning
07 - 39 - 87 -
08 Shutdown alarm 40 - 88 -
09 Shutdown or 41 - 89 -
load_dump alarm 42 Low speed alarm 90 Low speed warning
10 Shutdown or 43 High speed alarm 91 High speed warning
load_dump or warning 44 Low voltage alarm 92 -
11 Automatic ready 45 High voltagealarm 93 -
12 Week. on time 46 - 94 Fail to stop warning
13 Exerciser on 47 - 95 -
14 Load_dump alarm 48 - 96 Service request
15 Pre-Transfer signal 49 - warning
16 Mains Fail 50 - 97 Mains Phase Order
17 - 51 High battery voltage Fail
18 Service Request alarm 98 Low battery warning
19 - 52 - 99 High battery warning
20 Load Shedding Relay 53 - 100 -
21 - 54 - 101 -
22 - 55 - 102 -
23 - 56 - 103 Synchronization Fail
24 Mains Phase Order 57 - 104 -
Fail 58 - 105 Gen Low voltge warn.
25 Genset Phase Order 59 - 106 Gen High voltge warn.
Fail 60 Emerg.Stop load_dump 107 Reverse Power warn.
26 - 61 Spare-1 load_dump 108 -
27 - 62 Spare-2 load_dump 109 -
28 Alternate Volt/Freq 63 - 110 Gen CB Fail To Close
Enabled 64 - 111 Gen CB Fail To Open
29 - 65 - 112 -
30 - 66 - 113 -
31 - 67 - 114 -
68 - 115 -
69 - 116 -
70 - 117 -
71 - 118 -
72 Overcurrent load_dump 119 -
73 Excess power ldd 120 -
74 Reverse power ldd
75 -
76 -
77 Mains CB Fail To Close
78 Mains CB Fail To Open
79 Genset Phase Order
Fail Loaddump
The parameters below define the functions of digital inputs, selected from a list.
Functions from 12 to 23 activate also the related operating sequence.
The related input configuration parameters apply for each input, thus any signal can be
programmed for NO or NC contact, closing to BAT+ or BAT-.
- 38 -
DKG-329 User Manual V-12 (09.10.2012)
- 39 -
DKG-329 User Manual V-12 (09.10.2012)
- 40 -
DKG-329 User Manual V-12 (09.10.2012)
14. TROUBLESHOOTING
The genset operates while AC mains are OK or continues to operate after AC mains are OK:
kW and cosΦ readings are faulty although the Amp readings are correct:
-Current transformers are not connected to the correct inputs or some of the CTs are connected with
reverse polarity. Determine the correct connections of each individual CT in order to obtain correct kW
and cosΦ for the related phase, and then connect all CTs.
AUTO led flashes and the genset does not run when mains fail:
The unit is in Weekly Schedule OFF time. Please check date and time setting of the unit. Please check
also Weekly Schedule program parameters.
Measure the DC-supply voltage between Bat+ and Bat- terrminals at the rear of the unit. If OK, turn all
fuses off, then turn all fuses on, starting from the DC supply fuse. Then test the unit again.
The program lock input disables programming mode entry. Disconnect the program lock input from
battery negative before modification. Do not forget to make this connection again to prevent
unauthorized program modifications.
These parameters are reserved for factory setting and require a higher level password.
- 41 -
DKG-329 User Manual V-12 (09.10.2012)
The CE mark indicates that this product complies with the European requirements for safety,
health environmental and customer protection.
Alternator voltage: 0 to 300 V-AC Phase to Neutral (0 to 520 V-AC Phase to Phase)
Alternator frequency: 0-100 Hz.
Mains voltage: 0 to 300 V-AC Phase to Neutral (0 to 520 V-AC Phase to Phase)
Mains frequency: 0-100 Hz.
DC Supply range: 9.0 VDC to 33.0 VDC
Cranking dropouts: survives 0 V for 100ms.
Typical stand-by current consumption: 100 mADC.
Maximum current consumption: 200 mADC.
Generator/mains contactor outputs: 16 A @ 250 VAC.
DC outputs: 1A @ 28 VDC. Protected semiconductor outputs.
Current inputs: from current transformers, .../5A. Max load 0.7VA per phase.
Digital inputs: input voltage 0 - 30 VDC. Internally connected to battery positive via 4700 ohm resistor.
Measurement category: CAT II
Air category: Pollution degree II
Communication port: RS-232. 9600 bauds, no parity, 1 stop bit.
Operating temperature range: -20°C to +70°C (-4 ºF to +158 ºF)
Storage temperature range: -40°C to +80°C (-40 ºF to +176 ºF)
Maximum humidity: 95%, non-condensing
Dimensions: 171x134x46mm (WxHxD)
Panel Cut-out dimensions: 151 x 111mm minimum.
Weight: 300 g (approx.)
Case material: High temperature, self extinguishing ABS/PC (UL94-V0)
IP protection: IP65 from front panel, IP30 from the rear
- 42 -