You are on page 1of 8

OMICRON PTL ABB RED670 V2.2.

1 Line PTT User Manual

OMICRON PTL

ABB RED670 V2.2.1 Line PTT

User Manual

V1.100

© OMICRON electronics GmbH 1/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

Content
1. General ...................................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................4
5. XRIO Converter ......................................................................................................................................5
5.1 Additional Information Block .................................................................................................................5
5.1.1 Hardware Configuration ..................................................................................................................5
5.1.2 Test Configuration ..........................................................................................................................6
5.1.3 Remote Relay Parameter Section ..................................................................................................6
6. Specific Protection Tests ......................................................................................................................6
6.1 Switch onto Fault ..................................................................................................................................6
6.1.1 Impedance Mode (Quad) Activation BC .........................................................................................7
6.1.2 Impedance Mode (Quad) Activation DLD .......................................................................................7
6.1.3 UILevel Mode Activation BC ...........................................................................................................7
6.1.4 UILevel Mode Activation DLD.........................................................................................................8
6.2 Line Differential end to end tests ..........................................................................................................8

© OMICRON electronics GmbH 2/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

1. General
This user manual describes details of testing ABB RED670 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.

The template has been tested with the following relay:


Manufacturer: ABB
Model: RED670
Firmware Version: 2.2.1

2. Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 3.20 software or
higher versions and the following test modules:

• Control Center
• Quick CMC
• Ramping
• Overcurrent
• State Sequencer
• Advanced Distance
• Diff operating characteristic

Any CMC test set can be used with this Protection Test Template.
Additionally, a synchronized timing source (CMGPS 588) is needed for End-to-End testing.

© OMICRON electronics GmbH 3/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

3. Hardware
There are multiple possibilities of wiring an ABB RED670 relay to a CMC test set. The advised
connections are shown in Figure 1. These connections are the default settings in the
Hardware Configuration of the PTT.

Connection Diagram ABB RED670 V2.2.1 Line

CB Close Cmd
VC-N
VA-N
VB-N

N
N
IC
IA
IB

CB aux. A [52b]

CB aux. C [52b]
CB aux. B [52b]
Trip C
Trip A
Trip B

Start

Figure 1: Connection for RED670

4. Functional Range
Supported functions:

• Line differential protection L4CPDIF


• High speed distance protection ZMFPDIS
• High speed distance protection for series compensated lines ZMFCPDIS
• Automatic switch onto fault logic ZCVPSOF
• Phase overcurrent protection, four steps OC4PTOC (only Non-Directional)
• Instantaneous phase overcurrent protection PHPIOC
• Residual overcurrent protection, four steps EF4PTOC (only Non-Directional)
• Instantaneous residual overcurrent protection EFPIOC

© OMICRON electronics GmbH 4/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

Not supported functions:

• Power swing detection ZMRPSB


• Pole slip protection PSPPPAM
• Out-of-step protection OOSPPAM
• Four step phase overcurrent protection OC4PTOC (Directional settings)
• Four step residual overcurrent protection EF4PTOC (Directional settings)
• Four step directional negative phase sequence overcurrent protection NS4PTOC
• Sensitive directional residual overcurrent and power protection SDEPSDE
• Thermal Overload LCPTTR
• Breaker failure protection CCRBRF
• Stub protection STBPTOC
• Pole discordance protection CCPDSC
• Directional underpower protection GUPPDUP
• Directional overpower protection GOPPDOP
• Broken Conductor Check BRCPTOC
• Voltage restrained overcurrent protection VRPVOC
• Two step undervoltage protection UV2PTUV
• Two step overvoltage protection OV2PTOV
• Two step residual overvoltage protection ROV2PTOV
• Overexcitation protection OEXPVPH
• Voltage differential protection VDCPTOV
• Loss of voltage check LOVPTUV
• Radial feeder protection PAPGAPC
• Underfrequency protection SAPTUF
• Overfrequency protection SAPTOF
• Rate-of-change of frequency protection SAPFRC
• Scheme communication ZCRWPSCH and ZCPSCH

Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes most of the protection parameters of the relay.

5. XRIO Converter
The Test Object contains the ABB RED670 XRIO Converter, which includes setting parameters of the
modelled protection relay. The setting parameters are built as an image of the PCM600 software.

The Standard Filter for XRIO Files can be used for importing settings into the Relay Parameter
Section.

5.1 Additional Information Block


The parameters included in this block must be entered manually by the user since they are not relay
setting parameters. This chapter describes specialties of the Additional Information Block of the ABB
RED670 XRIO Converter.

5.1.1 Hardware Configuration


• Additional Information\Hardware Configuration\Analog modules

In this block, the analog inputs card type of TRM_40 of the relay has to be correctly selected
before importing the relay settings into the XRIO Converter. Furthermore the current and voltage
measurement channels for the input card have to be set.

• Additional Information\Relay Information\Overcurrent Protection\PHPIOC, EFPIOC\Phase


segregated active for EF?

© OMICRON electronics GmbH 5/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

This parameter shown in the figure below is normally active in the default configuration of
RED670 V2.2.1, so please deactivate it if necessary. If the parameter is active an additional delay
time tWaitForPHS (from the SMPPTRC logic block) is active in the relay to secure a 3-pole trip
when the phase selection fails.

Figure 2: Phase segregated logic for EFPIOC

5.1.2 Test Configuration


The Differential test mode has to be set as an option from two possible ways of testing; either “Single
Relay Test Only” or “Single Relay and GPS Test”. The test modules will be activated accordingly to this
setting:

Figure 3: Differential test mode

5.1.3 Remote Relay Parameter Section


The CT settings from the Remote Side have to be entered:

Figure 4: CT settings from the Remote Side

6. Specific Protection Tests

6.1 Switch onto Fault


The automatic switch onto fault logic ZCVPSOF can be activated externally (by the breaker-closed input)
or internally (automatically) with the dead-line detection using the UI level-based logic. When the setting
AutoInitMode is DLD disabled, ZCVPSOF is activated by an external binary input BC.

Note: Please assure that the CB Close Command signal (Binary Output 1) of the CMC is connected to
the CB Close Cmd of the relay if the setting AutoInitMode is DLD disabled.

If ZCVPSOF is activated there are two different operate modes which can lead to a trip signal, the
impedance mode and the UILevel mode. To test the different combinations of activation and operate
modes there are four State Sequencer test modules.

© OMICRON electronics GmbH 6/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

6.1.1 Impedance Mode (Quad) Activation BC


In this test the setting tSOTF and the impedance mode are tested with external activation.

The ZCVPSOF function is activated via binary signal and kept activated for the duration of tSOTF after the
signal drops off. The trip signal is issued with a distance zone. To verify the settings two different fault
scenarios are simulated:

Fault 1:
After the drop off from the CB close command in the second state the ZCVPSOF function is kept activated
for the duration of tSOTF. The fault in the next state is simulated at 95 % of the line length just before
tSOTF has expired. Therefore the fault should be cleared instantaneously.

Fault 2:
Afterwards the same fault is simulated just after the time tSOTF has expired. Now the relay must not trip
instantaneously but with the time of zone Z2.

6.1.2 Impedance Mode (Quad) Activation DLD


In this test the settings of tDLD, tSOTF and the impedance mode are tested with internal activation.

The ZCVPSOF function is activated if a dead line is detected for at least the time tDLD. After the drop off
of this detection the ZCVPSOF function is kept activated for the duration of tSOTF. To verify these times
three different fault scenarios are simulated:

Fault 1:
The dead line state is simulated for a time t<tDLD so that ZCVPSOF should not be activated and the fault
at 95 % of the line length must be cleared within the trip time of zone Z2.

Fault 2:
The dead line state is simulated for a time t>tDLD so that ZCVPSOF should be activated. However as the
following fault at 95 % of the line length is simulated just after tSOTF has expired the ZCVPSOF function
is not active anymore and the fault must be cleared within the trip time of zone Z2.

Fault 3:
The dead line state is simulated for a time t>tDLD so that ZCVPSOF should be activated. As the following
fault at 95 % of the line length is simulated just before tSOTF has expired the ZCVPSOF function is still
active and the fault must be cleared instantaneously.

6.1.3 UILevel Mode Activation BC


In this test the settings of tSOTF, tDURATION and the UILevel mode are tested with external activation.

The ZCVPSOF function is activated via binary signal and kept activated for the duration of tSOTF after the
signal drops off. The trip signal is issued if a fault is present for a time t>tDURATION. To verify the
settings three different fault scenarios are simulated:

Fault 1:
After the drop off from the CB close command in the second state the ZCVPSOF function is kept activated
for the duration of tSOTF. As the fault in the next state is simulated just after tSOTF has expired the relay
must not clear the fault instantaneously.

Fault 2:
After the drop off from the CB close command in the second state the ZCVPSOF function is kept activated
for the duration of tSOTF. The fault in the next state is simulated just before tSOTF has expired. But as
the fault is not present for a time t>tDURATION the UILevel Detector must not issue a trip signal.

Fault 3:
After the drop off from the CB close command in the second state the ZCVPSOF function is kept activated
for the duration of tSOTF. The fault in the next state is simulated just before tSOTF has expired. The fault
is present for a time t>tDURATION and therefore it should be cleared instantaneously.

© OMICRON electronics GmbH 7/8


OMICRON PTL ABB RED670 V2.2.1 Line PTT User Manual

6.1.4 UILevel Mode Activation DLD


In this test the settings of tDLD, tSOTF, tDURATION and the UILevel mode are tested with internal
activation.

The ZCVPSOF function is activated if a dead line is detected for at least the time tDLD. After the drop off
of this detection the ZCVPSOF function is kept activated for the duration of tSOTF. The trip signal is
issued if a fault is present for a time t>tDURATION. To verify these times four different fault scenarios are
simulated:

Fault 1:
The dead line state is simulated for a time t<tDLD so that ZCVPSOF should not be activated and the fault
must not be cleared instantaneously.

Fault 2:
The dead line state is simulated for a time t>tDLD so that ZCVPSOF should be activated. However as the
following fault is simulated just after tSOTF has expired the ZCVPSOF function is not active anymore and
the fault must not be cleared instantaneously.

Fault 3:
The dead line state is simulated for a time t>tDLD so that ZCVPSOF should be activated. The fault in the
next state is simulated just before tSOTF has expired. But as the fault is not present for a time
t>tDURATION the UILevel Detector must not issue a trip signal.

Fault 4:
The dead line state is simulated for a time t>tDLD so that ZCVPSOF should be activated. The fault in the
next state is simulated just before tSOTF has expired. The fault is present for a time t>tDURATION and
therefore it should be cleared instantaneously.

6.2 Line Differential end to end tests


For the Line Differential end to end tests each relay has to be connected to a CMC using a CMGPS 588.
Furthermore, the parameters of each relay must be entered in the corresponding PTT in the Relay
Parameter Section.

To run the end to end tests corresponding test modules need to be open and then run simultaneously on
both CMCs. E.g. run the module “Line Differential external fault A-N (Relay 1)” on the CMC connected to
Relay 1 and “Line Differential external fault A-N (Relay 2)” on the other.

For the test of the differential characteristic it has to be assured that exactly the same test points are set in
the corresponding test modules for both relays.

© OMICRON electronics GmbH 8/8