TEST PLAN OF PC0800688 TYPE TEST

FLUODER S.A, Paraguay, South America


2848.8 kVA, 23KV/69.2-115.1 V, Rectifier Transformer
TEST CRITERIA / REFERENCE STANDARD

Day 1
Measurement of Voltage Ratio & Check of Phase Displacement

Check of ratio and polarity of built in current transformer

Magnetic Balance and Magnetising Current measurement

Check of Vector group


IEC 60076-1
Measurement of Winding Resisance

Measurement of DC Insulation Resistance

Measurement of DC insulation resistance between core & frame

Determination of Capacitance and Dissipation factor


Applied Voltage test (AV)
IEC 60076-3
Induced voltage test (IVW)
Measurement of No load loss and Current

IEC 60076-1
Measurement of Short-Circuit Impedance and Load Loss

Temperature Rise Test


Start of temperature rise test ( T) IEC 60076-2

Oil sampling shall be done before temp.rise test and DGA analysis (T)
Day 2
Complete temperature rise test

Oil Sampling for DGA analysis after heatrun test (T)

Frequency Response Analysis (FRA) IEC 60076-18

oil leakage test on Transformer tank. IEC 60076-1


Test Reports
Day 3

AS PER APPROVED DRAWING


Dimensions measurement.

AS PER T&R/ customer spec.


Functional Test .