Pms Comment Sheet Rev.8-160219: Alarm Indication
Pms Comment Sheet Rev.8-160219: Alarm Indication
8- 160219
Note 1) Please refer to Flow Charts as next pages for each condition of stand-by DG start.
2) Please only prepare stand by-start generator with synchronizing and CB close function, when
Voltage high/low, Frequency High/low.
It will be determined at site commissioning stage.
3) Voltage High/Low & Frequency High/Low alarm with two (2) of D/G stand-by start function
are to be added only for D/G starting
4) Temperature High-High/Low-Low alarm with one (1) of stand-by D/G start and connect BUS
BAR (i.e. D/G incoming CB close) function is to be added with auto-synchronizing.
After synchronizing, the faulty D/G is slowly stopped with load shifting.
Flow Chart
- BUS BAR Voltage & Frequency High - High & Low – Low
POWER SUPPLY
- D/G “REMOTE” MODE
- SYNP “AUTO” MODE
BUS FREQ.
BUS VOLTAGE
CHECK
VOLTAGE NO
ESTABLISH
ABNORMAL DG INCOMING CB
OPEN COMMAND
ABNORMAL DG INCOMING
CB OPENED
ST’BY D/G NO
INCOMING CB
CLOSED
CB NOT CLOSE
YES ALARM
POWER SUPPLY
POWER SUPPLY
- D/G “REMOTE” MODE
- SYNP “AUTO” MODE
BUS FREQ.
BUS VOLTAGE
CHECK
ABNORMAL DG INCOMING
CB(s) OPEN COMMAND
ABNORMAL DG INCOMING
CB(s) OPENED
POWER SUPPLY
- D/G “REMOTE” MODE
- SYNP “AUTO” MODE
VOLTAGE NO
ESTABLISH
ST’BY DG INCOMING CB
CLOSE COMMAND
WITH AUTO SYNCHRONIZING
AUTO SYNCHRONIZING
COMPLETED
STBY D/G NO
INCOMING CB
CLOSED
CB NOT CLOSE
ALARM
YES
ABNORMAL DG INCOMING CB
OPEN COMMAND
ABNORMAL DG INCOMING CB
OPENED
ABNORMAL D/G SHOULD BE
STOPPED AFTER COOLING
DOWN TIME.
(ABOUT 5 MINUTES)
POWER SUPPLY
WITH LOAD SHARING
Flow Chart
- Incoming CB Abnormal Trip
Case 1 : One (1) Generator on 6.3KV HV SWBD
POWER SUPPLY
- D/G “REMOTE” MODE
- SYNP “AUTO” MODE
DG INCOMING
CB ABNORMAL
YES
ABNORMAL DG INCOMING CB
OPENED
D/G SHOULD BE STOPPED
AFTER COOLING DOWN
TIME.
(ABOUT 5 MINUTES)
BLACK OUT
(REFER TO BLACK OUT
POWER RECOVERY FLOW)
DG INCOMING
CB ABNORMAL
YES
NOTE
1. DG LOAD SHEDDING IS AVAILABLE
ABNORMAL DG INCOMING CB IN ACCORDANCE WITH DG STATUS.
OPENED
VOLTAGE NO
ESTABLISH
ST’BY DG INCOMING CB
CLOSE COMMAND
WITH AUTO SYNCHRONIZING
AUTO SYNCHRONIZING
COMPLETED
STBY D/G NO
INCOMING CB
CLOSED
CB NOT CLOSE
ALARM
YES
POWER SUPPLY
1.1.3. Load Dependent Auto – Start/Stop Control
- Manual Start/stop
(1) When the D/G is started/stopped by manual, Automatic load sharing can be done
No Description Tag. No
※ PT List
PT
No Description Tag. No
Type
1 PT1 Package Air Condition Unit 3409-660-GE-001~7
3409-660-JC-001-A,B
2 PT1 No.1 & 2 Water Cooler Condensing Unit
3409-660-JB-001
3 PT1 Incinerator Control Panel 3409-435-EC-001
BLACK OUT
EM’CY DG INCOMING CB
NO.1 AND NO.3 MAIN CLOSE
NO ON 380V EMCY ESBD
D/Gs INCOMING
VCB CLOSED
(WITHIN abt.30s) NO.1 OR NO.3 MAIN D/G
START
EM’CY AC380V
YES BUS TIE CB CLOSE
NO.1 OR NO.3 MAIN D/G ON 380V EMCY SWBD
INCOMING VCB CLOSE
BUS-TIE BREAKER
ON 6.3KV HV SWBD
CLOSE
ON 6.3KV HV SWBD NO.1,2 EM’CY AC220V
INCOMING CB CLOSE
BUS-TIE BREAKER
ON 220V EMCY SWBD
CLOSE
NO.1,2 MAIN 6.3KV ON 6.3KV HV SWBD
TRANSFORMER VCB
CLOSE ON 6.3KV HV SWBD EMCY POWER RESTORED
NO.1,2 MAIN 6.3KV WITHIN 45SEC.
TRANSFORMER VCB
NO.1,2 MAIN 380V CLOSE ON 6.3KV HV SWBD
INCOMING CB CLOSE
ON 380V MAIN SWBD MAIN POWER &
EMCY POWER
NO.1,2 MAIN 380V
RESTORED SEPARATELY
INCOMING CB CLOSE
NO.1,2 MAIN AC220V ON 380V MAIN SWBD
INCOMING CB CLOSE
ON 220V MAIN SWBD
END
NO.1,2 MAIN AC220V
INCOMING CB CLOSE
MAIN POWER & ON 220V MAIN SWBD
EMCY POWER
RESTORED SEPARATELY
MAIN POWER &
EMCY POWER
RESTORED SEPARATELY
SEQUENCE START
ESS CONSUMERS
SEQUENCE START
ESS CONSUMERS
END
END
2) Modified Flow chart
(In case that the Main power restored failed on No.1 &3 Main D/G, No.2 Main D/G & No.4 Main D/G
Flow are same as No.1 Main D/G & No.3 Main D/G Flow)
BLACK OUT
YES
NO.1 OR NO.3 MAIN D/G
NO.1 MAIN D/G INCOMING VCB CLOSE EM’CY AC380V
INCOMING VCB CLOSE ON 6.3KV HV SWBD BUS TIE CB CLOSE
ON 380V EMCY SWBD
END END
3) CB re-connection tables
- Circuit breakers of transformers, main DG incoming and HVSB bus tie breaker are
equipped with under voltage relays. The PMS will reconnect the breakers after Main DG
has started. This requires that none of the breakers are blocked for any reason.
Reconnect
No. Description I/O Sequence Remark
time delay
No.1 910-YI-141 From 6.3KV
Black Out
1 And - - HVSB
(HVSB No.1 AND No.2 BUS Dead)
No.2 910-YI-142 To PMS
Reconnect
No. Description I/O Sequence Remark
time delay
No.1 910-YI-141
Black Out From 6.3KV
1 And - -
(HVSB No.1 AND No.2 BUS Dead) HVSB
No.2 910-YI-142
2) Condition
- All DG is selected in “ Remote” mode on DG local panel, synchronizing panel is selected in
“Auto” mode
- DG incoming VCBs are selected in “Remote” mode on HVSB
- VSCs(Vacuum Switch Contactor) for each heavy consumer are selected in “Remote” mode
on HVSB
- Click “HEAVY CONSUMER START ON” command on PMS mimic.
3) Power Required
Description Rated power Required power
No.1 Ballast Pump 1,100KW
370KW
3409-501-PA-001-A 1,600KW
No.2 Ballast Pump 1,100KW
370KW
3409-501-PA-001-B 1,600KW
No.3 Ballast Pump 1,100KW
370KW
3409-501-PA-001-C 1,600KW
No.1 Fire Pump 2,000KW
550KW
3409-730-PA-001-A 2,800KW
No.2 Fire Pump 2,000KW
550KW
3409-730-PA-001-B 2,800KW
1) Scope
- Maximum load/Capacity (KW) of each GTG and actual/using load (KW) on DP4 is transferred to
FSO’s PMS. And then, FSO’s PMS calculating remain load with actual/using load (KW) & Maxi
mum load /Capacity (KW).
- The FSO’s stand-by generator is automatically started by PMS in order to parallel running with
DP4 power when remain load is reached at 85% of total remain load on DP4 power.
- In this regard remain load parameter (%) can be adjusted by parameter input on PMS.
- For easy understanding, please refer to below graph.
DP4
ACTUAL
LOAD
(KW)
1.1.8. Isochronous mode.
1) Scope
- DGs can parallel running when Isochronous mode.
- When Isochronous mode selected, each D/G start/stop command can available from PMS.
- There is no feedback signal for Isochronous mode from DG.
1.1.9. PMS shall have Symmetric and Asymmetric load sharing mode. And load sharing can be
carried out by PMS as per selection of Symmetric or Asymmetric mode
1.1.10. Reactive (KVAR) Unbalance alarm set point will be informed after discussing with Generator
engine Maker.
Reactive (KVAR) load sharing function is to be added. In this regard, please refer to below
I/O concerning the reactive power signal of each D/G.
1.1.11. When all DG running and voltage/frequency High-High/Low-Low condition, the logic and
sequence are to be verified and installed by KM.