Professional Documents
Culture Documents
Table of Contents
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
1. General
1.1 Safety instructions and warnings for user
This handbook contains all necessary information for the correct operation of the R 2000 family of
systems.
It has been written for technically qualified personnel.
Unauthorized tampering with the unit, especially ignoring the warnings in this handbook, can cause
malfunction and damage to the unit. Only authorized personnel should be allowed to make changes to
the unit and perform cable connections especially the power supply.
Should it be necessary, e.g. in case of service or repair, to make measurements within the unit, then all
customary accidents prevention procedures should be observed. Only professional electrical tools
should be used.
Roland Electronic GmbH declare that the product listed above complies with the requirements of the
EMC directives listed below.
Applied Directives:
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
2. System Configuration
( ) automatically / manual
( ) extended manual
( ) 1 = max/min filter
( ) 2 = max/min difference
( ) 3 = absolute valueg
( ) 4 = flanke extreme
( ) 5 = positive amplitude
( ) 6 = negative amplitude
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
3. Introduction
The processing of tubes requires the fully automatic location of weld seams and the positioning of the
tubes. The weld seam detector SND30 was specifically developed for this task and is an advanced
version of the proven system SND8.
5. Systems components
The system consists of the control unit, the sensor and the cable.
Dimensions in
mm / inch W H D
fixing holes M6
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Note!
In the case of use of the supplied metal rubbers (see chapter 5.5) the overall width of 165 mm
is altered around 50 mm (25 mm each rubber) on 215 mm.
132.5
Attention !
ø10
- B -
92
M6 x 10
26
Attention!
fixing holes M8
Attention!
17.5
3
33 24.8
17.5 35
165
- A - 70
79
- A - magnetic poles - B -
Technical data:
Ambient temperature: 10 - 40OC 50 - 105°F
Protection category: IP53
Weight: 9.5 kg 21lb
Enclosure made of: nickelplated brass
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Note!
In the case of use of the supplied metal rubbers (see chapter 5.5) the overall width of 165 mm
is altered around 50 mm (25mm each rubber) on 215 mm.
132,5
Attention !
The fixing screws should
ø10 NOT be screwed deeper
than 10 mm into the brass
plate. Otherwise the sensor
function could be destroyed.
92
"B"
55
M6 x 10
26
Achtung!
M8
175
M8
ø24
17,5
Achtung!
30
33 35
115 70
165 90
"A" 110
"A" "B"
Technical data:
Ambient temperature: 10 - 40OC 50 - 104°F
Protection category: IP53
Weight: 14 kg 31 lb
Enclosure made of: nickelplated brass
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
receptacle sensor
white
green
brown 6 7 8
yellow
red 5 1 2
grey
pink 4 3
blank
30
M8
8
25
10
M8
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
6. System installation
The sensor should be in continuous contact with the tube during the detection phase.
For this reason the sensor should be metal rubber mounted in order to allow the sensor follow the
movement of the tube.
If the interface output "motor" is used then it is easier to position the weld seam more precisely,
because the PLC is not used for this control purpose.
If the drive is controlled via the PLC, then the PLC must monitor the output "motor" and control the
drives immediatly according to the output signals.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
NS9S
NS12S
N = RPM
ø = tube diameter in mm (1 inch 25.4 mm)
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
The times for placing the tube onto the sensor and removing it after detection have to be added to the
above.
During parameter programming this condition is indicated by the message "weld seam location critical"
(compare section "Parameter programming").
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Minimum wiring
The control unit can be operated with a minimal interface wiring. This means that the selection of the
measuring menues made via the keyboard and not via the PLC.
For this version the output OUT 7 "Motor" or relay contact (Terminal 9, 10) and the input IN0
"Measurement start / Teach-In ENABLE" are required. The timing diagrams for parameter programming
and the measurement process are documented in Attachment B 1 and B 2.
In addition, the interface signal OUT 6 "Reduced detection capability" can be used if required. The
output signals are opto coupled and require an external 24 V power supply.
Standard wiring
For this version the inputs IN 0 to IN 6 and the outputs OUT0 to OUT7 are required. It is possible to
use fewer inputs and outputs if not all of the measuring menues are required.
The standard version allows the selection of measuring menues either with the PLC (see Attachment
B3) or the keyboard.
The timing diagrams for parameter programming and measurement are in Attachment B4 and B5.
7. Start-up
1. All systems components should be connected to power according to the legal requirements of the
country. Attachement A contains the connection diagram of the interface board as well as the
information for grounding the system components; see also installations instructions of the
sensor.
2. Review the position of the voltage selector switch and compare to available power. If necessary
change position of voltage selector switch.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
8. Operation
After applying power the following display appears.
The system is factory adjusted according to the requirements of specific customers. Activation of
function key D is generally only necessary to select a language. Press function key P in order to input
parameters, if no measuring programs have been keyed-in before.
M : Measuring mode
P : Parameter -Programming
D : Diagnostics, Service-Functions and Systems-Installation
↑ : Change of Parameters (forward)
↓ : Change of Parameters (backward)
ENTER : Confirmation of input
BACK : Return to main menu / abort
T : (active only in diagnostics)
Key- : Keyboard Enable : Allows inputs via keyboard
switch RUN : Disables the keyboard; activates the outputs in the measuring mode
FAULT : Lights up, in case of hardware fault. Contact ROLAND ELECTRONIC or your local
representative
RUN : Blinking when keyboard is enabled, or lights up constantly when the system is in the
measuring mode and the key switch is in the position RUN (outputs are active).
ACTIVE : Lights up, if the system accepts measuring data and shows them on the display.
< : Lights up, together with > if reduced detection capability exists.
NORM : Lights up, if weld seam is detected.
> : Lights up, together with > if reduced detection capability exists.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Initial state
(Key switch keyboard Enable)
D6 Tube statistic
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
P12 Parameter
Description M14512 The following display appears if a parameter menue has been
Diameter 50mm previously programmed. Each blinking field can be changed and
has to be confirmed with ENTER.
3. Select one parameter program (P1-P30 are available) with the arrow keys and confirm with
ENTER.
4. Depending on the adjustment in the systems configuration under "parameter optimization" the
following operational sequence is possible:
1. Adjusted systems configuration "parameter optimization automatically only"
Only the automatic parameter optimization procedure available, continue with "8.4.1 parameter
programming - automatic optimization"
P12 Parameter
parameter
optimization
automatically
Now has to be decided whether the parameter optimization should take place automatically
or manually. The automatic parameter optimization is described under 8.4.1. The manual
optimization under 8.4.2.
2. Input of tube diameter with arrow keys and confirmation with ENTER.
3. Input of speed (RPM) of the tube and confirmation with ENTER (approx. by ±15 % is sufficient).
P12 Parameter
Speed 60.0rpm
After-run 120°
In this display the speed is 60 RPM and the after-run is 120°.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
4. Input of after-run (position of the weld seam) with arrow keys; (relative to the direction of the
sensor). Confirmation with ENTER.
5.1 If SND 30 is not able to properly locate the weld seam, it issues a warning. This warning can be
used to mark the tubes and or exclude them from the normal manufacturing process. (Compare
section "Reliability of detection"). Confirm selection with ENTER key.
If the unit indicates that correctly positioned tubes are ”critical“ (difficult to detect), then it is
advisable to repeat parameter programming with a ”critical“ tube.
P12 Parameter
inform at critical
weld seam detection
yes This display means that reduced detection capability is
communicated to the PLC.
5.2 Under this menu the threshold of critical seam detection for the output "reduced detection
capability" is adjusted. Available selections are "very high", "high", "standard", and "very low".
If "very high" is selected for the measuring process many tubes may be classified as "critical
detection". However, it is unlikely that a tube with an incorrectly positioned tube is classified as
"weld seam detected".
In the case of a "very low" selection many tubes with an incorrectly positioned tube may not be
classified as "critical detection" (reduced- detection capability). For this reason the adjustment
"standard" is a reasonable starting point.
P12 Parameter
6. This display appears if the PLC has not yet prepared a tube for parameter programming. It is
replaced as soon as the PLC has prepared the tube for parameter programming.
P12 Parameter
waiting for
clearance from SPS
P12 Parameter
Correlation aktive
please wait
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
8. This display appears if it is not possible to determine the exact rotational speed of the tube
automatically. Then it is necessary to key-in the exact speed (within ± 2%).
9. The SND30 optimizes the filter algorithms for weld seam detection.
P12 Parameter
filter optimization
aktive
please wait
P12 Parameter
tube positioning
aktive
please wait
11. This display appears only, if it is not possible to detect the weld seam.
Repeat with another tube and review the number of revolutions of the tube. If these actions are
not successful then it is not possible to detect the weld seam with the system
P12 Parameter
the weld seam was
not detected
continue with ENTER
P12 Parameter
repeat proceeding
with another tube!
continue with ENTER
P12 Parameter
weld seam detection
good
continue with ENTER Relative values:
very good - good - satisfactory - problematic
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
13. After the positioning process it is necessary to review whether the weld seam is in the desired
position. Select answer with arrow keys.
P12 Parameter
is the positioning
of the w.seam right?
no
If this question has been answered with yes, then parameter programming is completed and the
unit returns to the main menu.
14. This menu only appear, if the question in 13. was answered "no". Input new after-run with the arrow
keys.
P12 Parameter
After-run old 120°
After-run new 115°
In this example the after-run is corrected to 115°
1. Enter the alphanumeric materials number with the arrow keys in the spaces of the 8-digit field and
confirm with ENTER. However this entry is not compulsory.
2. Enter the tube diameter with the arrow keys and confirm with ENTER.
3. Enter the number of revolutions of the tube with the arrow keys and confirm with ENTER
(exactly ±2%).
P12 Parameter
Speed 60.0rpm
After-run 120°
4. Enter the after-run (weld seam positioning) with the arrow keys (relative to the position of the
sensor head) and confirm with ENTER.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
5.1 Select with the arrow keys whether a decreased recognition capability should be signaled to
the machine controls (see section "detection capability"). Confirm selection with the ENTER key.
This message enables the PLC the selection, marking and elimination of the tube from the
process. If correctly positioned tubes are displayed as critical, then the parameter programming
should be repeated with another tube.
P12 Parameter
inform at critical
weld seam detection
yes
5.2 The threshold for the output "decreased recognition reliability" is adjusted here. The following
threshold steps are available "very high", "high", "standard" or "very low" for adjustment.
In the case of "very high" very small detection variations can lead to the message "critical
detection" (decreased recognition reliability). On the other hand however it is unlikely that the two
was a difficult to detect weld seam will be associated with the signal "seam (correctly) detected".
In the other extreme "very low" it can happen that tubes are incorrectly positioned,without the
message "critical detection" (recognition reliability decreased) is issued.
At the beginning of a Teach in of process "normal" should be initially selected as the basic
adjustment.On the basis of the positioning results further fine tuning should then be made.
P12 Parameter
P12 Parameter
Scanning rate
(10=standard) 10
The scanning rate has an influence on the noise suppression during the weld seam detection
operation.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
7. With the filter type the following signal filter procedures can be selected.
P12 Parameter
Filter type
standard flanke (0)
The following example demonstrates the effect of the individual filters selected.
Standard flank:
filter
sensor-signal
Max/min filter:
filter
sensor-signal
Min/max difference:
filter
sensor-signal
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Absolute value:
Filter
Sensor-Signal
Flanke extreme:
filter
sensor-signal
Positive amplitute:
filter
sensor-signal
Negative amplitude:
filter
sensor-signal
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
8. This menu option is available only with the system adjustment "filter optimization manually”.
P12 Parameter
Magn. field stength
100%
The strengths of the magnetic field is adjusted here. As a rule it should be adjusted to 100%.
Only with tubes with a wall thickness smaller than 1.2 mm a reduction to 50% can be advantageous.
The adjustment 30% should not be used.
P12 Parameter
Gain
1
Summary:
- 30 measurement programs are available
- each measuring program contains the following parameter adjustments
- parameter program number
- tube diameter
- number of revolutions of the few
- after run (welding seam position)
- ?Aussonderungsschwelle? threshold
- message in case of reduced to recognition reliability (yes/no)
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
A At the SND30
4. Use arrow keys to select a program previously keyed-in in the parameter program and confirm
with ENTER.
If a measurement program without parameters is selected, an error message is displayed.
! Attention Error !
please teach-in
tube first
5. Turning the key switch to the position RUN after the selection of a measurement program
activates the interface to the PLC. The system is now ready for measurement. Operating the
SND30 via the keyboard is no longer possible.
B Via the external PLC (not during minimum wiring of the interface)
1. Set the SND30 to the base menu and turn to the key switch to RUN (it may be necessary to
turn the key switch to ENABLE, press the BACK key and then turn the key switch back to
RUN).
2. Select the measuring program via the interface of the PLC (see Timing Diagram in the
Appendix B). If a measuring program is selected which does not containing parameter sets,
then an error message is generated. At the same time the input data are not mirrored from IN2
to IN6 at the outputs OUT2 to OUT6, thus the unit is not ready for operation (ENABLE).
! Attention Error !
please teach-in
tube first
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
1. The measurement procedure is now performed in accordance with the timing diagram in the
Attachment B.
2. After the successful weld seam detection the following message appears:
If the option „reduced detection reliability“ has been selected in parameter programming, then an
interface signal „reduced detection capability“ signal will be issued. (see section "Reliability of
detection"). This enables the PLC to issue a command to mark the tube and exclude it from further
processing.
Attention!
If "no" has been selected in the systems configuration menu "automatic menu selection" then it
is necessary to select an existing Parameter program of the SND 30 when recycling power or in
case of a brief power failure. See page 29 for adjustment of "automatic menu selection".
Attention!
A Re-Teach without a properly turning tube can lead to an incorrect determination of parameters
(RPM's); the weld seam detection process resulting in the faulty detection procedure. The timing
diagram is described in the Appendix.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
D1 = Systems installation
D2 = System configuration
D3 = Analogboard test
D4 = Tube signal analysis
D5 = Reset all parameter programs
D6 = Tube statistik
D1 Diagnose
System-Installation
Use arrow keys to select menues D2 to D7 which are used for service purposes. Confirm with
ENTER to reach Systems Installation.
System-Installation
English
Attention!
Modifications change the function of the control unit. After input of the password the following display
appears:
System-Configuration
Backup-Memory
no
This equipment adjustment must be set to "no". A back up memory is not available.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
System-Configuration
Input signals
+24 VDC aktive
In this menu option the logic of the inputs is selected. Selections between 24 VDC active (according
to the timing diagrams) and 0 VDC active are possible.
System-Configuration
Power control
Inputs
yes
Possible adjustments:
yes: The connecting terminal 11 (+24V) and 12 (GND) are monitored for the availability of 24 VDC.
no: The monitoring does not take place.
It is therefore possible to monitor the control cable for a cable break.
The following menu option is for adjusting the logic of the outputs OUT0 to OUT6.
System-Configuration
Outputs
(OUT0 to OUT6)
+24 VDC aktive
Selections between "+24 VDC active" (according to the timing diagrams) and "0 VDC" active are
possible.
System-Configuration
Motor relay and OUT7
Relay normal open
+24 VDC aktive
Possible adjustments:
+24 VDC active/relay N.O.:
The output OUT 7 and the relay work function according to the timing diagrams.
0 VDC active/relay N.C:
The output OUT7 and the relay function with inverted switching logic.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
System-Configuration
Power control
yes
Possible adjustments:
yes: The connecting terminal 21 (+24V) und 22 (GND) are monitor for the available in the of 24 VDC
no: The monitoring does not take place
It is therefore possible to monitor the control cable for a cable break.
Attention!
In order to use OUT0 to OUT7 an external supply voltage has to be applied to terminal 21 (+24V) and
terminal 22 (GND).
The next menu option allows the selection between mm and inch as measurement unit of the tube and
diameter.
System-Configuration
Dimension diameter
mm
System-Configuration
Parameter
optimization
automatically
Possible adjustments:
only automatically:
For parameter programming only the automatic parameter optimization procedure is available.
automatic/manually:
Parameter programming can be selected between manual or automatic parameter optimization.
special manual:
Same as automatic/manually, however with the additional possibility of adjusting the "magnetizing
force" during parameter programming.
System-Configuration
System
run-in periode
1.0 sec
After the adjusted system settl if ing time the following conditions must be fulfilled:
- Sensor must be in the measuring position
- Tube drive must be adjusted to the target number of revolutions
- In case of sensor NS9S and NS12S: The magnetic field must be at full strength
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
The standard adjustment is 1.0 second. It should be reduced only after consultation with ROLAND
ELECTRONIC.
System-Konfiguration
Magnetic field
switch off delay
0.0 sec
After termination of the measuring procedure the magnetic field should be be switched off with a delay.
The tube remains positioned on the sensor and cannot not rotate.
System-Configuration
Default
Speed
81.0 rpm
The adjusted number of revolutions is used as default value after the deletion of the parameters.
System-Configuration
automatic Note:
menu selection If a program change is done very often (i.e. after each measurement),
no this parameter should be set to "no". Otherwise the life time of the
internal storage unit will be shortened.
Possible adjustments:
yes: The program which was used last for measurement is stored and been selected
automatically when reapplying power. The key switch has to be set to "RUN".
no: The control unit remains in the base menu of the applying power and waits for a program
selection via the PLC.
System-Configuration
test sensor cable
yes
This is used to check cable and sensor for defects.
Possible adjustments:
yes: The current for the magnetization of the sensor is monitored. If current is interrupted, the
control unit displays a fault (only meaningful with NS9S and NS12S).
no: Magnetization of the sensor is not monitored (necessary for optical sensors)
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
System-Configuration
Re-teach
via PLC-input
standard
Possible adjustments:
normal: Is active with measurement start IN7, then a Re-Teach is performed.
(see "8.5.3 Re-Teach")
special: Is active with measuring start IN7, then a special Re-Teach is performed.
(see "8.5.3 Re-Teach" )
no: No Re-Teach possible.
System-Configuration
Default filter type
(0=standard)
flanke standard(0)
System-Configuration
maximum variation of
weld turn 1 to 2
ratio 2:1 1:2 Während der Positionierung wird die Konstanz des Schweissnaht-
signals überwacht.
Entered here are the necessary changes of the weld seam signal amplitude in order to determine that
the detected weld seam is correct. If larger changes are detected, the output "decreased recognition
reliability" is activated and the message "critical detection" is issued.
Possible adjustments:
Threshold 2:1 1:2: The amplitude can be smaller by the the factor ½, or larger by the factor 2
Threshold 2:1 1:4: The amplitude can be smaller by the the factor ½, or larger by the factor 4
Threshold 4:1 1:4: The amplitude can be smaller by the the factor ¼, or larger by the factor 4
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
System-Configuration
Masking of weld seam
for calculation
+/- 5%
For the weld seam detection procedure the surrounding environment regarding the weld seam is not
included in the algorithm. In case of broad weld seams this adjustment should be extended +/- 8%
because the system issues the message "critical detection" even with correct weld seam positioning.
The standard adjustment is +/- 5%. For very high requirements the positioning accuracy and good
signal quality the adjustment shall be set to +/-3%.
Analogueboard-Test
D/A-Converter 128
A/D-Converter -5
Gain 2
This point refers to testing the analog part of the SND30. At BNC1 a "saw tooth" type signal is issued.
The gain can be adjusted for the test. The entered A/D values displayed for diagnostic purposes. This
value should be around 0 (+/-50) with disconnected sensor cable and an gain adjustment of 1-800.
sensor module
BNC1
BNC2
BNC
test receptacle
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
If the second channel of the oscilloscope is connected simultaneously to the TESTBNC (switch
position 4), then the following signal is can be measured.
1 revolution
BNC 1
TEST BNC
Explanation:
The signal at the BNC2 is the analog signal. After the High impulse starts in the signal to be measured.
The signal at the TESTBNC indicates with short High impulses the position of the detected weld seam.
1 revolution
BNC 1
TEST BNC
Explanation:
The signal at the BNC1 shows the filtered tube signal . This signal is between 0 and 5 V. The larger
the difference between the level of the weld seam signal (position where short impulses are issued at
the TESTBNC) and the noise signals between weld seam position 1 and 2 is, the better can the weld
seam be detected.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Tube statistic
weld det. 100
critical 1
clear with T-key
After applying power the control unit starts the statistics regarding the tubes with detected weld seams
and those with critical detection.
This statistics is deleted:
a) by pressing the T key in the menu option above
b) when switching the control unit off; the statistics is also deleted!
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
9. Maintenance
9.2 Sensor
The sensors are not affected by oil pollution. Chips and shavings should occasionally be cleaned out
by using compressed air or by simply wiping off.
Adhering chips impair the function of the sensor bearings and the actual sensor element.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
Required:
- SND30
- RS232 cable to connect to SND30 terminals 31-34 and to PC
- Computer with RS232 interface resp. USB-RS232 converter
- Phytec Flash Tools for firmware flashing
- Firmware
Procedure:
1. Install the flashloader from CD (if not already done).
2. Switch-off the supply voltage.
3. Connect the RS232 cable to the SND30 terminals 31-34 and to the PC
4. Press the BOOT key on the board in the upper section of the unit (see previous illustration)
and keep pressed. Switch-on the supply voltage. Then release the pressed BOOT key.
5. Start the „Phytec Flash Tools“ at the PC.
6. Confirm with OK.
7. Select MINIMODUL 515C and press „connect“. If the board is not found,
select the correct RS232 interface under „Conifig, Protocol, Properties“.
8. Select „Download“.
9. Select „Erase needed sectors“.
10. Set „Bank-Offset“ to „Bank1“.
11. Select the download file „V0173“ (example) with „open“.
12. Download with „Start“. Await the completion.
13. Select „Disconnect“.
14. Perform power OFF-ON at the unit.
The unit must then power up with the previously loaded version.
NS9S Bearing suppor ted sensor element for tube-Ø from 10 mm to 250 mm and tube wall
thickness to max. 4.0 mm; with cable KNS9S, standard length 5 m
NS12 Bearing suppor ted sensor element for tube-Ø from 10 mm to 250 mm and tube wall
thickness to max. 3.0 mm; with cable KNS9S, standard length 5 m
KNS9S-G Sensor cable, standard length 5 m (with rigth angle receptacle for sensor connection)
2299700 GM rubber
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT A
Rev. 3.0 Page 36
4 Measuring signal 1 1
5 Measuring signal 2 2
R2000 SND30
1 + 15 V 3
3 AGND 4
NS XX 2 - 15 V 5
6 + Coil 6
7 - Coil 7
8 Cable shield
Motor
Switch
Relay motor
PLC + 24 VDC
Common
Start measurem. Teach-In Enable
Menue select
Data OUT
M1
M2
M4
M8
M16
(Re-teach)
Parameter prog. M2
M4
M8
Reduced detection M16
Motor
RxD
+ GND
GND
24 VDC
TxD
-
Line
Neutral
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT A
Rev. 3.0 Page 37
Relay Motor
Terminal-no. max. 250 VAC / 30 VDC / 10 Amps
9 N.O. if 24 VDC is active / N.C. if 0 V is active
10 (see Systems Configuration page 2)
Connector POWER
Terminal-no. Input power Function
35 Line 230 VAC 80 VA 115 VAC 80 VA
36 Neutral recommended Fuse 1 A Slow blow recommended Fuse 2 A Slow
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 38
t1: Time required by the operator in order to select the parameter program to be programmed (see section 5.3 Parameter
programming).
t2/t6: Time required by the PLC in order to prepare the tube for parameter programming (Placing tube on the sensor)
t3/t7: < 10 milliseconds.
t4/t8: Time required for auto optimizing routine depending on tube diameter and rotational speed.
t5: User to evaluate positioning (see section 5.3 Parameter programming, point 15).
t9: Point t6 to t8 repeated several times depending on the operation of the SND30.
t10: Parameter programming is completed.
The total time of parameter programming depends on the tube diameter, the rotational speed and the inputs of the
parameters.
Estimated time is the time required for 25 revolutions.
* The in- and outputs not described here are not required for parameter programming.
** Not necessary or is repeated several times depending on the operation of the SND30.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 39
In order to start measurement with IN0, a valid measuring menue must have been selected (externally
or via the keyboard) and the key switch must be in RUN position.
* The in- and outputs not described here are not required for parameter programming.
** This output is used only if the option ”Reduced detection reliability“ (see section 5.3 parameter
programming, point 8). A high could mean the weld seam has not been positioned properly (see
section 9. Operating parameters, point 6. Reliability of detection).
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 40
To be able to select a Measurement Menu externally, the key-switch must be in position RUN.
If a measurement menue has been selected, that was the not pre-programmed, than there will be no
release by ENABLE and the input data IN2 to IN6 will not be mirrowed to the outputs OUT2 to OUT6.
On the display a note will appear with the indication of missing parameters.
IN1
Selection of measuring menu
IN2
Binary value 1 M1
IN3
Binary value 2 M2
IN4
Binary value 4 M4
IN5
Binary value 8 M8
IN6
M16
Binary value 16
IN7
OUT0
Measurement active
OUT1
Selection of measuring menu
OUT2
Binary value 1 ** M1 Enable
OUT3
** M2
Binary value 2
OUT4
** M4
Binary value 4
OUT5
** M8
Binary value 8
OUT6
** M16
Binary value 16
OUT7
Motor
IN0 and IN1 are edge triggered interrupt inputs. In the standard-configuration, the positive edge is active. Do not activate
IN0 and IN1 simultaneonsly. A time gap more than 10 milliseconds has to be provided between two command. IN1 is Strobe-
Input for Data-Input IN2 to IN6.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 41
t1: Time required by the operator in order to select the parameter program to be programmed (see section 5.3 Parameter
programming).
t2/t6: Time required by the PLC in order to prepare the tube for parameter programming (Placing tube on the sensor)
t3/t7: <10 milliseconds.
t4/t8: Time required for auto optimizing routine depending on tube diameter and rotational speed.
t5: User to evaluate positioning (see section 8.4 Parameter programming).
t9: Point t6 to t8 repeated several times depending on the operation of the SND30.
t10: Parameter programming is completed.
The total time of parameter programming depends on the tube diameter, the rotational speed and the inputs of the
parameters. Estimated time is the time required for 25 revolutions.
* The in- and outputs not described here are not required for parameter programming.
** Not necessary or is repeated several times depending on the operation of the SND30.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 42
In order to start measurement with IN0, a valid measuring menue must have been selected (externally
or via the keyboard) and the key switch must be in RUN position.
IN0 and IN1 are edge triggered interrupt inputs. In the standard-configuration, the positive edge is active. Do not activate
IN0 and IN1 simultaneonsly. A time gap of more than 10 milliseconds has to be provided between two command. IN1 is
Strobe-Input for Data-Input IN2 to IN6.
Signals of the outputs OUT2 to OUT6 have two different functions. By activating Menue select IN1, inputs IN2 to IN6
are mirrowed at the outputs OUT2 to OUT6 in order to monitor correct transmission.
By activating the external control command Start measurement IN0 Status messages and Measurement results are
reported. In the standard configuration is high level active.
* The in- and outputs not described here are not required for parameter programming.
** This output is used only if the option ”Reduced detection reliability“ (see section 5.3 parameter programming, point 8).
A high could mean the weld seam has not been positioned properly.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 43
In order to start measurement with IN0, a valid measuring menue must have been selected (externally
or via the keyboard) and the key switch must be in RUN position.
IN2 Re-Teach
OUT2 ENABLE
OUT7 Motor
t1
and relay output
terminal 9 and 10 t2 t4 t5
High = closed
Low = open t3
IN0 and IN1 are edge triggered interrupt inputs. In the standard-configuration, the positive edge is active. Do not activate
IN0 and IN1 simultaneonsly. A time gap of more than 10 milliseconds has to be provided between two command. IN1 is
Strobe-Input for Data-Input IN2 to IN6.
Signals of the outputs OUT2 to OUT6 have two different functions. By activating Menue select IN1, inputs IN2 to IN6
are mirrowed at the outputs OUT2 to OUT6 in order to monitor correct transmission.
By activating the external control command Start measurement IN0 Status messages and Measurement results are
reported. In the standard configuration is high level active.
* The in- and outputs not described here are not required for parameter programming.
** This output is used only if the option ”Reduced detection reliability“ (see section 5.3 parameter programming, point 8).
A high could mean the weld seam has not been positioned properly.
ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33