You are on page 1of 45

RO L A N D

WELD SEAM DETECTION SND30

Weld seam detection in tubes Sensor


R 2000 series SND30
Magnetic functional principle
Microcontroller based
Rohr

For positioning tasks


For steel and non magnetic stainless steel tubes with a diameter ranging from 10 to 250 mm
and a wall thickness up to 5 mm depending on the sensor type
Digital display of operations parameter
Programmable for 30 different tubes
Opto coupled 8-Bit PLC parallel-interface for input and output
Output relay for motor control
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 / B0001566 / 26.11.2008 Page 1

Table of Contents

Table of Contents Attachment A Page2


Table of Contents Attachment B Page2
1. General Page3
1.1 Safety instructions and warnings for user Page3
1.2 Declaration of conformity according to EC directives Page3
2. System Configuration Page4
3. Introduction Page6
4. Systems description and measuring principle Page6
5. Systems components Page6
5.1 Technical data Page6
5.2 Technical data sensor NS9S Page7
5.3 Technical data sensor NS12 Page8
5.4 Sensor cable KNS9S Page9
5.5 Metal rubber Page9
6. System installation Page10
6.1 Sensor mounting Page10
6.2 Tube drive Page10
6.3 Ground earth requirements of the system components SND30 Page11
6.4 Operating parameter Page11
6.4.1 Tube diameter and wall thickness Page11
6.4.2 Tube rotational speed Page11
6.4.3 Weld seam positioning Page11
6.4.4 Elapsed time for weld seam detection Page12
6.4.5 Elapsed time for parameter programming Page12
6.4.6 Reliability of detection Page12
6.5 Interface wiring Page13
7. Start-up Page13
8. Operation Page14
8.1 Functions of the keys Page14
8.2 Funktionen der LED´s Page14
8.3 Menu structure Page15
8.4 Parameter programming Page16
8.4.1 Parameter programming with optimization automatically Page16
8.4.2 Parameter programming with manual optimization Page19
8.5 Measurement mode Page24
8.5.1 Parameter program selection Page24
8.5.2 Measurement operation Page25
8.5.3 Re-Teach (automatic Re Teach via the PLC) Page25
8.6 Diagnostics and service functions Page26
8.6.1 D1 - Systems installation Page26
8.6.2 D2 - System configuration Page26
8.6.3 D3 - Analog board test Page31
8.6.4 D4 - Tube signal analysis Page31
8.6.5 D5 - Reset of program parameters Page33
8.6.6 D6 - Tube statistics Page33
9. Maintenance Page34
9.1 Control unit Page34
9.2 Sensor Page34
9.3 Hardware - Diagnostics Page34
9.4 Firmware update Page35
9.5 Order data Page35

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 2

Table of Contents Attachment A


A1 Wiring diagram Optocoupler - Interface - Board (Schematic diagram) Page36
A2 Connection Diagram Optocoupler - Interface - Board Page37

Table of Contents Attachment B


B1 Timing Diagram Optocoupler- Interface - Board, minimum Interface Connection Page38
B2 Timing Diagram Optocoupler- Interface - Board, minimum Interface Connection Page39
B3 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection Page40
B4 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection Page41
B5 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection Page42
B6 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection Page43

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 3

1. General
1.1 Safety instructions and warnings for user
This handbook contains all necessary information for the correct operation of the R 2000 family of
systems.
It has been written for technically qualified personnel.
Unauthorized tampering with the unit, especially ignoring the warnings in this handbook, can cause
malfunction and damage to the unit. Only authorized personnel should be allowed to make changes to
the unit and perform cable connections especially the power supply.
Should it be necessary, e.g. in case of service or repair, to make measurements within the unit, then all
customary accidents prevention procedures should be observed. Only professional electrical tools
should be used.

1.2 Declaration of conformity according to EC directives


Manufacturer: Roland Electronic GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern
Product name: Double Sheet Detector
Product type: R2000 - SND30

Roland Electronic GmbH declare that the product listed above complies with the requirements of the
EMC directives listed below.
Applied Directives:

73/23/EWG: Directive regarding electrical equipment to be used within specified voltage


levels; modified by Directive RL93/68/EWG.
EN61010-1:2001

89/336/EWG: Generic emission standard;


modified by Directive RL 91/263/EWG, 92/31/EWG and 93/68/EWG.

61000-6-3: 2001 61000-6-1: 2001


61000-6-4: 2001 61000-6-2: 2001

Year of mark´s apposition: 1998

Keltern, 01.04.1998 Managing Director


...............................................................................................................................
Place, Date ^ Signature Function of the signer

DIN EN ISO 9001 Reg.-no. 5152

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 4

2. System Configuration

Custom configuration : Type: __________________________

Operating voltage: ( ) 230 VAC ( ) 115 VAC

Language: ()D ()E ()F ( ) NL ()I

Dimension Measuring value: ( ) mm ( ) inch

Input signals: ( ) +24 V aktive ( ) 0 VDC aktive

Input monitoring: ( ) no ( ) yes

Output signals (OUT0 - OUT6): ( ) +24 V aktive ( ) 0 V aktive

Motor relay: ( ) +24 V aktiv / normal closed

( ) 0 VDC aktive / normal closed

Output monitoring: ( ) no ( ) yes

Parameter improvement: ( ) automatically

( ) automatically / manual

( ) extended manual

System settle time: ____________ 0,0 ...5,0 seconds

Turn-off delay magnetic field: ____________ 0,1 ...5,0 seconds

Default revolution: ____________ 5 U/min ...600 U/min

Automatic menu selection: ( ) yes ( ) no

Cbale brak monitoring ( ) yes ( ) yes

Re-teach via PLC: ( ) no ( ) standard ( ) extra

Default filter type: ( ) 0 = standard flanke

( ) 1 = max/min filter

( ) 2 = max/min difference

( ) 3 = absolute valueg

( ) 4 = flanke extreme

( ) 5 = positive amplitude

( ) 6 = negative amplitude

Modification weld seam: ( ) 2:1 / 1:2 ( ) 2:1 / 1:4 ( ) 4:1 / 1:4

Masking of weld seam: ()3% ()5% ()8%

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 5

Parameter table for measuring programs


Measuring Rotation Inform reduced
Description Diameter After run Threshold of critical
program RPM detection capability
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 6

3. Introduction
The processing of tubes requires the fully automatic location of weld seams and the positioning of the
tubes. The weld seam detector SND30 was specifically developed for this task and is an advanced
version of the proven system SND8.

4. Systems description and measuring principle


The SND30 enables the positioning of weld seams in tubes in any pre-determined position. Location
and positioning are based on the magnetic leaking flux principle and auto-optimizing methods (teach-
in) of digital signal proccessing concepts.
The SND30 communicates with a programmable logic controller (PLC) via an 8- bit parallel interface.
The drive to position the weld seam can be controlled via the built-in relay (max. 250 VAC / 30 VDC /
10 Amps). For positioning application where mis-positioning cannot be tolerated, the SND30 issues
an interface signal ”reduced detection capability“.

5. Systems components
The system consists of the control unit, the sensor and the cable.

Dimensions in
mm / inch W H D

R 2000 - SND30 240 / 9.45 160 / 6.30 150 / 5.90

fixing holes M6

5.1 Technical data


Dimensions: see drawing above
Protection category: IP65
Ambient temperature: 0 - 50 °C
Weight: 5.3 kg
Operating voltage: 230 V / 115 VAC switchable; 50 / 60 Hz

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 7

5.2 Technical data sensor NS9S

Note!
In the case of use of the supplied metal rubbers (see chapter 5.5) the overall width of 165 mm
is altered around 50 mm (25 mm each rubber) on 215 mm.

132.5
Attention !
ø10

The fixing screws should


NOT be screwed deeper
than 20 mm into the brass
plate. Otherwise the sensor
function could be destroyed.

- B -
92

M6 x 10

26
Attention!
fixing holes M8

These two screws


175

must not be used


or removed !

Attention!
17.5
3

33 24.8
17.5 35

165
- A - 70
79

active sensor area

- A - magnetic poles - B -

4 pcs. SKF ball bearing 9x24x7 mm


(order no.: 2390924)

2 pcs. SKF ball bearing 8x22x7 mm


(order no.: 2390822)

Technical data:
Ambient temperature: 10 - 40OC 50 - 105°F
Protection category: IP53
Weight: 9.5 kg 21lb
Enclosure made of: nickelplated brass

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 8

5.3 Technical data sensor NS12

Note!
In the case of use of the supplied metal rubbers (see chapter 5.5) the overall width of 165 mm
is altered around 50 mm (25mm each rubber) on 215 mm.

132,5
Attention !
The fixing screws should
ø10 NOT be screwed deeper
than 10 mm into the brass
plate. Otherwise the sensor
function could be destroyed.
92

"B"
55

M6 x 10

26
Achtung!

M8
175

M8
ø24
17,5

Achtung!
30

33 35
115 70
165 90
"A" 110

"A" "B"

Technical data:
Ambient temperature: 10 - 40OC 50 - 104°F
Protection category: IP53
Weight: 14 kg 31 lb
Enclosure made of: nickelplated brass

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 9

5.4 Sensor cable KNS9S


The sensor cable KNS9S must be used for the connection of the sensor to the control unit. The cable has
a cable receptacle at the sensor side and terminal leads for the connection to the control unit.

receptacle sensor
white
green
brown 6 7 8
yellow
red 5 1 2
grey
pink 4 3
blank

5.5 Metal rubber

30

M8
8
25
10

M8

Material: NBR (Acrylnitril-Butadien)


metal parts galvanized and chromated
Hardness: 45+/-5 Shore A

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 10

6. System installation

6.1 Sensor mounting


The sensor can be mounted in any position. Mounting the sensor vertically above the tube is
advantageous to reduce collection of dirt. For best performance there should be no ferrous material
immediately adjacent to the sensor. Keep a distance of 50 mm.

The sensor should be in continuous contact with the tube during the detection phase.
For this reason the sensor should be metal rubber mounted in order to allow the sensor follow the
movement of the tube.

Use Metal Rubber:


GM Type B (30 mm dia., 25 mm height). Metal rubber are supplied with the sensor but can be ordered
also separately from ROLAND ELECTRONIC.

Sensor NS9S: Sensor NS12S:


Four metal rubber Eight metal rubber
M8 mountings come with M8 mountings come with
each sensor. each sensor.
Two of each are mounted Four of each are mounted
diagonally on the narrow on the narrow side of the
side of the sensor. sensor.
M8
M8

6.2 Tube drive


The rotational drive of the tube can be accomplished axially or radially. The rotational speed should
be in the specified range. Within a second the rotational speed should be reached and remain constant
during the whole detection phase. The sensor should touch the tube within 1 second after "Measurement
Start" and should not vibrate at the tube during the detection process. If these conditions cannot be
achieved within 1 second contact Roland Electronic for additional information.
Control of the tube drive can be accomplished:
- via the relay output "motor"
- Über die SPS

If the interface output "motor" is used then it is easier to position the weld seam more precisely,
because the PLC is not used for this control purpose.
If the drive is controlled via the PLC, then the PLC must monitor the output "motor" and control the
drives immediatly according to the output signals.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 11

6.3 Ground earth requirements of the system components SND30


All systems components should use the same ground earth (PA).
The leads should have a cross section of 1.5 mm² minimum.

NS9S
NS12S

6.4 Operating parameter

6.4.1 Tube diameter and wall thickness


The SND 30 can detect and position weld seams in tube diameters ranging from 10 mm to 250 mm (0.4
to 9.8 inch). The tube wall thickness should in general not exceed 3 mm with NS9S resp. 4mm with
NS12.

6.4.2 Tube rotational speed


The possible tube rotational speed (N) is a function of the tube diameter and should be within the range.

<N< but higher than 5 RPM

N = RPM
ø = tube diameter in mm (1 inch 25.4 mm)

Tube rotation should stay constant during the detection phase.

6.4.3 Weld seam positioning


The positioning of the weld seam can be selected in steps of 1O.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 12

6.4.4 Elapsed time for weld seam detection


The necessary detection time per tube depends on the rotation of the tube.

TS = System settle time


TD = TS + 250 N = RPM
N TD = Detection time in seconds

The times for placing the tube onto the sensor and removing it after detection have to be added to the
above.

6.4.5 Elapsed time for parameter programming


The total time for parameter programming depends on the tube diameter, rotational speed and time
necessary to input the parameters. An approximate value is the elapsed time for 25 revolutions.

6.4.6 Reliability of detection


The SND 30 is based on the magnetic leaking flux principle and auto-optimizing methods of digital
signal analysis in order to obtain a high degree of reliability for detecting and positioning the weld seam.
However, poorly manufactured tubes with surface defects or material faults can lead to mispositioning
the weld seam. The option "reduced detection capability" enables the PLC to mark those tubes and
exclude them from the manufacturing process.
If correct positioned tubes are indicated as "critical" then parameter programming should be repeated
with one such tube. If the tubes to be positioned contain many manufacturing faults and material faults,
then it may not be possible to detect and position the weld seam correctly.

During parameter programming this condition is indicated by the message "weld seam location critical"
(compare section "Parameter programming").

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 13

6.5 Interface wiring

Minimum wiring
The control unit can be operated with a minimal interface wiring. This means that the selection of the
measuring menues made via the keyboard and not via the PLC.
For this version the output OUT 7 "Motor" or relay contact (Terminal 9, 10) and the input IN0
"Measurement start / Teach-In ENABLE" are required. The timing diagrams for parameter programming
and the measurement process are documented in Attachment B 1 and B 2.
In addition, the interface signal OUT 6 "Reduced detection capability" can be used if required. The
output signals are opto coupled and require an external 24 V power supply.

Standard wiring
For this version the inputs IN 0 to IN 6 and the outputs OUT0 to OUT7 are required. It is possible to
use fewer inputs and outputs if not all of the measuring menues are required.
The standard version allows the selection of measuring menues either with the PLC (see Attachment
B3) or the keyboard.
The timing diagrams for parameter programming and measurement are in Attachment B4 and B5.

Interface wiring with Re-Teach


If repeated fully automatic teach-in is desired via the PLC interface, then IN7 must also be wired.

7. Start-up

1. All systems components should be connected to power according to the legal requirements of the
country. Attachement A contains the connection diagram of the interface board as well as the
information for grounding the system components; see also installations instructions of the
sensor.
2. Review the position of the voltage selector switch and compare to available power. If necessary
change position of voltage selector switch.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 14

8. Operation
After applying power the following display appears.

LED RUN blinks

The key switch has to be in the


position KEYBOARD ENABLE
in order to input data

The system is factory adjusted according to the requirements of specific customers. Activation of
function key D is generally only necessary to select a language. Press function key P in order to input
parameters, if no measuring programs have been keyed-in before.

8.1 Functions of the keys

M : Measuring mode
P : Parameter -Programming
D : Diagnostics, Service-Functions and Systems-Installation
↑ : Change of Parameters (forward)
↓ : Change of Parameters (backward)
ENTER : Confirmation of input
BACK : Return to main menu / abort
T : (active only in diagnostics)
Key- : Keyboard Enable : Allows inputs via keyboard
switch RUN : Disables the keyboard; activates the outputs in the measuring mode

8.2 Funktionen der LED´s

FAULT : Lights up, in case of hardware fault. Contact ROLAND ELECTRONIC or your local
representative
RUN : Blinking when keyboard is enabled, or lights up constantly when the system is in the
measuring mode and the key switch is in the position RUN (outputs are active).
ACTIVE : Lights up, if the system accepts measuring data and shows them on the display.
< : Lights up, together with > if reduced detection capability exists.
NORM : Lights up, if weld seam is detected.
> : Lights up, together with > if reduced detection capability exists.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 15

8.3 Menu structure

Initial state
(Key switch keyboard Enable)

Key M Key P Key D

Measuring mode Programming mode Installation mode

Select measuring program Select parameter program D1 System installation

Parameter optimization Language


D / E / F / NL / I
automatically
D2 System Configuration
Description 8 digits
Backup memory (fix)
Tube diameter
8 - 250 mm / 0.3 - 9.85 inch Logic input signals
24V active / 0V active
Number of revolutions
5 - 600 rpm Inputs monitoring
ja / nein
After-run (positioning)
0 - 359° Logic output signals OUT0 - 6
24V active / 0V active
Critical detection
yes / no Logik output signals OUT7 / Relay
24V active / normal closed
Treshold of critical
very high / high / standard / Outputs monitoring
very low yes / no

Test run with automatic Dimension diameter


parameter impovement mm / inch

manual Parameter improvement


automatically / automatically-manual /
Description 8 digits extended manual

Tube diameter System settle time


8 - 250 mm / 0.3 - 9.85 inch 0.0 - 5.0 seconds

Speed Switch off delay magnetic field


5 - 600 rpm 0.0 - 5.0 seconds

After-run (positioning) Default speed


0 - 359° 5.0 - 600 rpm

Critical detection automatic menu selection


yes / no yes / no

Treshold of critical Test sensor cable


very high / high / standard / yes / no
very low
Re-teach via PLC
Sampling rate no / standard / extra
4 - 11
Default filter type
Filter type 0-6
0-6
Modification weld seam
Magnetic field strength 2:1, 1:2 / 2:1, 1:4 / 4:1, 1:4
(only with Par. imp.: extented manual)
30% / 50% / 100% Masking of weld seam
3% / 5% / 8%
Signal gain
1 - 800 D3 Analog board test

D4 Tube signal analysis

D5 Reset all parameter programs

D6 Tube statistic

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 16

8.4 Parameter programming


This section explains the menues and the operation of the SND30.
The timing diagram and the communication with the PLC is contained in Attachment B.

1. Key switch is in position keyboard ENABLE.

2. Press key P in order to activate parameter menu.

P12 Parameter
Description M14512 The following display appears if a parameter menue has been
Diameter 50mm previously programmed. Each blinking field can be changed and
has to be confirmed with ENTER.

3. Select one parameter program (P1-P30 are available) with the arrow keys and confirm with
ENTER.

4. Depending on the adjustment in the systems configuration under "parameter optimization" the
following operational sequence is possible:
1. Adjusted systems configuration "parameter optimization automatically only"
Only the automatic parameter optimization procedure available, continue with "8.4.1 parameter
programming - automatic optimization"

2. Adjusted systems configuration "parameter optimization automatic/manual" or "parameter


optimization specifically manually".
The following display appears:

P12 Parameter
parameter
optimization
automatically

Now has to be decided whether the parameter optimization should take place automatically
or manually. The automatic parameter optimization is described under 8.4.1. The manual
optimization under 8.4.2.

8.4.1 Parameter programming with optimization automatically


1. Optional input of an 8 digit alphanumeric material code and confirmation with ENTER. This entry
can remain blank.

2. Input of tube diameter with arrow keys and confirmation with ENTER.

3. Input of speed (RPM) of the tube and confirmation with ENTER (approx. by ±15 % is sufficient).

P12 Parameter
Speed 60.0rpm
After-run 120°
In this display the speed is 60 RPM and the after-run is 120°.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 17

4. Input of after-run (position of the weld seam) with arrow keys; (relative to the direction of the
sensor). Confirmation with ENTER.

5.1 If SND 30 is not able to properly locate the weld seam, it issues a warning. This warning can be
used to mark the tubes and or exclude them from the normal manufacturing process. (Compare
section "Reliability of detection"). Confirm selection with ENTER key.
If the unit indicates that correctly positioned tubes are ”critical“ (difficult to detect), then it is
advisable to repeat parameter programming with a ”critical“ tube.

P12 Parameter
inform at critical
weld seam detection
yes This display means that reduced detection capability is
communicated to the PLC.

5.2 Under this menu the threshold of critical seam detection for the output "reduced detection
capability" is adjusted. Available selections are "very high", "high", "standard", and "very low".
If "very high" is selected for the measuring process many tubes may be classified as "critical
detection". However, it is unlikely that a tube with an incorrectly positioned tube is classified as
"weld seam detected".
In the case of a "very low" selection many tubes with an incorrectly positioned tube may not be
classified as "critical detection" (reduced- detection capability). For this reason the adjustment
"standard" is a reasonable starting point.

P12 Parameter

standard (3) Note:


This menu point is availabe since Software-Version 161.

6. This display appears if the PLC has not yet prepared a tube for parameter programming. It is
replaced as soon as the PLC has prepared the tube for parameter programming.

P12 Parameter
waiting for
clearance from SPS

7. The SND 30 determines the exact rotational speed of the tube.

P12 Parameter
Correlation aktive
please wait

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 18

8. This display appears if it is not possible to determine the exact rotational speed of the tube
automatically. Then it is necessary to key-in the exact speed (within ± 2%).

P12 Parameter P12 Parameter


calculation of exact please put in the
speed not possible exact speed(+/-2%)
continue with ENTER speed 62.9 rpm

9. The SND30 optimizes the filter algorithms for weld seam detection.

P12 Parameter
filter optimization
aktive
please wait

10. The SND 30 positions the weld seam.

P12 Parameter
tube positioning
aktive
please wait

11. This display appears only, if it is not possible to detect the weld seam.
Repeat with another tube and review the number of revolutions of the tube. If these actions are
not successful then it is not possible to detect the weld seam with the system

P12 Parameter
the weld seam was
not detected
continue with ENTER

P12 Parameter
repeat proceeding
with another tube!
continue with ENTER

Return to point 10.


12. User information about the detection reliability of the weld seam.

P12 Parameter
weld seam detection
good
continue with ENTER Relative values:
very good - good - satisfactory - problematic

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 19

13. After the positioning process it is necessary to review whether the weld seam is in the desired
position. Select answer with arrow keys.

P12 Parameter
is the positioning
of the w.seam right?
no

If this question has been answered with yes, then parameter programming is completed and the
unit returns to the main menu.

14. This menu only appear, if the question in 13. was answered "no". Input new after-run with the arrow
keys.

P12 Parameter
After-run old 120°
After-run new 115°
In this example the after-run is corrected to 115°

Return to point 13.

8.4.2 Parameter programming with manual optimization


The individual parameters are entered manually during the manual optimization procedure. An
automatic optimization, determination of the number of revolutions or a test run do not take place. The
verification of the detection must take place in the measurement mode.

1. Enter the alphanumeric materials number with the arrow keys in the spaces of the 8-digit field and
confirm with ENTER. However this entry is not compulsory.

2. Enter the tube diameter with the arrow keys and confirm with ENTER.

3. Enter the number of revolutions of the tube with the arrow keys and confirm with ENTER
(exactly ±2%).

P12 Parameter
Speed 60.0rpm
After-run 120°

4. Enter the after-run (weld seam positioning) with the arrow keys (relative to the position of the
sensor head) and confirm with ENTER.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 20

5.1 Select with the arrow keys whether a decreased recognition capability should be signaled to
the machine controls (see section "detection capability"). Confirm selection with the ENTER key.

This message enables the PLC the selection, marking and elimination of the tube from the
process. If correctly positioned tubes are displayed as critical, then the parameter programming
should be repeated with another tube.

P12 Parameter
inform at critical
weld seam detection
yes

5.2 The threshold for the output "decreased recognition reliability" is adjusted here. The following
threshold steps are available "very high", "high", "standard" or "very low" for adjustment.
In the case of "very high" very small detection variations can lead to the message "critical
detection" (decreased recognition reliability). On the other hand however it is unlikely that the two
was a difficult to detect weld seam will be associated with the signal "seam (correctly) detected".
In the other extreme "very low" it can happen that tubes are incorrectly positioned,without the
message "critical detection" (recognition reliability decreased) is issued.
At the beginning of a Teach in of process "normal" should be initially selected as the basic
adjustment.On the basis of the positioning results further fine tuning should then be made.

P12 Parameter

standard (3) Note:


This menu is only available starting from software version 161.

6. The scanning rate for the measuring operation is entered here.

P12 Parameter
Scanning rate
(10=standard) 10

The scanning rate has an influence on the noise suppression during the weld seam detection
operation.

The following into relationships can be expected:


- Broad weld seams require smaller values (4-6)
- Narrow welding seams (lasers) require values between 6 and 10
- Tube diameter smaller 20 mm require values between 6 and 8
- Values between 4 and 6 suppress fault messages due to scratches on the tube surface
Meaningful values are between 4 and 10. Other adjustments very seldom result in improvements.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 21

7. With the filter type the following signal filter procedures can be selected.

P12 Parameter
Filter type
standard flanke (0)

0 = standard flank 4 = flank extreme


1 = max/min filter 5 = positive amplitude
2 = max/min difference 6 = negative amplitude
3 = absolute value

The following example demonstrates the effect of the individual filters selected.

Standard flank:

filter

sensor-signal

Max/min filter:

filter

sensor-signal

Min/max difference:

filter

sensor-signal

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 22

Absolute value:

Filter

Sensor-Signal

Flanke extreme:

filter

sensor-signal

Positive amplitute:

filter

sensor-signal

Negative amplitude:

filter

sensor-signal

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 23

8. This menu option is available only with the system adjustment "filter optimization manually”.

P12 Parameter
Magn. field stength
100%

The strengths of the magnetic field is adjusted here. As a rule it should be adjusted to 100%.
Only with tubes with a wall thickness smaller than 1.2 mm a reduction to 50% can be advantageous.
The adjustment 30% should not be used.

9. In this menu option the gain of the analog signal is adjusted.


This value should be transferred from the automatic parameter optimization. If it is not known
default values should be set to 1 or 2.The control unit optimizes this adjustment during the
measuring operation.

P12 Parameter
Gain
1

Summary:
- 30 measurement programs are available
- each measuring program contains the following parameter adjustments
- parameter program number
- tube diameter
- number of revolutions of the few
- after run (welding seam position)
- ?Aussonderungsschwelle? threshold
- message in case of reduced to recognition reliability (yes/no)

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 24

8.5 Measurement mode


The measurement mode consists of the selection of the parameter program and the measuring
procedure.

8.5.1 Parameter program selection


There are two alternatives for parameter program selection in the measurement mode:

A At the SND30

1. Place key switch to keyboard ENABLE (LED RUN blinks).

2. SND30 display should be in main menue (press key BACK).

3. Press key M to activate measuring menu.

M12 Measurement G=1


Description M14512
Diameter 50mm

4. Use arrow keys to select a program previously keyed-in in the parameter program and confirm
with ENTER.
If a measurement program without parameters is selected, an error message is displayed.

! Attention Error !
please teach-in
tube first

5. Turning the key switch to the position RUN after the selection of a measurement program
activates the interface to the PLC. The system is now ready for measurement. Operating the
SND30 via the keyboard is no longer possible.

B Via the external PLC (not during minimum wiring of the interface)

1. Set the SND30 to the base menu and turn to the key switch to RUN (it may be necessary to
turn the key switch to ENABLE, press the BACK key and then turn the key switch back to
RUN).

2. Select the measuring program via the interface of the PLC (see Timing Diagram in the
Appendix B). If a measuring program is selected which does not containing parameter sets,
then an error message is generated. At the same time the input data are not mirrored from IN2
to IN6 at the outputs OUT2 to OUT6, thus the unit is not ready for operation (ENABLE).

! Attention Error !
please teach-in
tube first

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 25

8.5.2 Measurement operation


The measurement operation is controlled via the PLC only. The key switch at the SND30 must be in
the position RUN. A valid parameter measurement program must have been selected. The duration of
the measu measuring is described in section "Operating Parameters".

1. The measurement procedure is now performed in accordance with the timing diagram in the
Attachment B.

2. After the successful weld seam detection the following message appears:

M12 Measurement G=1


Description M14512
Diameter 50mm
weled seam detected

In case of a critical weld seam detection the following message appears:

M12 Measurement G=1


Description M14512
Diameter 50mm

If the option „reduced detection reliability“ has been selected in parameter programming, then an
interface signal „reduced detection capability“ signal will be issued. (see section "Reliability of
detection"). This enables the PLC to issue a command to mark the tube and exclude it from further
processing.

Attention!
If "no" has been selected in the systems configuration menu "automatic menu selection" then it
is necessary to select an existing Parameter program of the SND 30 when recycling power or in
case of a brief power failure. See page 29 for adjustment of "automatic menu selection".

8.5.3 Re-Teach (automatic Re Teach via the PLC)


The Re-Teach is available only if it in the systems configuration the "Re-Teach" has been enabled.
There are two modes:
1. normal
If a Re-Teach is activated via the the PLC interface, then the control unit determines again
the best scanning rate and the best gain.
2. separate
If a Re-Teach is activated via the PLC interface, then the control unit determines again the
number of revolutions, the best scanning rate, and the best gain is.

Attention!
A Re-Teach without a properly turning tube can lead to an incorrect determination of parameters
(RPM's); the weld seam detection process resulting in the faulty detection procedure. The timing
diagram is described in the Appendix.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 26

8.6 Diagnostics and service functions

The diagnostics menue D contains the following 7 sub-menus:

D1 = Systems installation
D2 = System configuration
D3 = Analogboard test
D4 = Tube signal analysis
D5 = Reset all parameter programs
D6 = Tube statistik

8.6.1 D1 - Systems installation


1. Press key D and confirm menu D 1, systems installation with ENTER.

D1 Diagnose
System-Installation

Use arrow keys to select menues D2 to D7 which are used for service purposes. Confirm with
ENTER to reach Systems Installation.

2. Select language with arrow keys. Confirm with ENTER.

System-Installation
English

8.6.2 D2 - System configuration


The configuration of the system is adjusted here.

Attention!
Modifications change the function of the control unit. After input of the password the following display
appears:

System-Configuration
Backup-Memory
no

This equipment adjustment must be set to "no". A back up memory is not available.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 27

Press the the ENTER key to continue.

System-Configuration
Input signals
+24 VDC aktive

In this menu option the logic of the inputs is selected. Selections between 24 VDC active (according
to the timing diagrams) and 0 VDC active are possible.

System-Configuration
Power control
Inputs
yes

Possible adjustments:
yes: The connecting terminal 11 (+24V) and 12 (GND) are monitored for the availability of 24 VDC.
no: The monitoring does not take place.
It is therefore possible to monitor the control cable for a cable break.

The following menu option is for adjusting the logic of the outputs OUT0 to OUT6.

System-Configuration
Outputs
(OUT0 to OUT6)
+24 VDC aktive

Selections between "+24 VDC active" (according to the timing diagrams) and "0 VDC" active are
possible.

The logic of the output OUT7 and motor relay is determined.

System-Configuration
Motor relay and OUT7
Relay normal open
+24 VDC aktive

Possible adjustments:
+24 VDC active/relay N.O.:
The output OUT 7 and the relay work function according to the timing diagrams.
0 VDC active/relay N.C:
The output OUT7 and the relay function with inverted switching logic.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 28

System-Configuration
Power control
yes

Possible adjustments:
yes: The connecting terminal 21 (+24V) und 22 (GND) are monitor for the available in the of 24 VDC
no: The monitoring does not take place
It is therefore possible to monitor the control cable for a cable break.

Attention!
In order to use OUT0 to OUT7 an external supply voltage has to be applied to terminal 21 (+24V) and
terminal 22 (GND).

The next menu option allows the selection between mm and inch as measurement unit of the tube and
diameter.

System-Configuration
Dimension diameter
mm

The selections of parameter programming are adjusted here.

System-Configuration
Parameter
optimization
automatically

Possible adjustments:
only automatically:
For parameter programming only the automatic parameter optimization procedure is available.
automatic/manually:
Parameter programming can be selected between manual or automatic parameter optimization.
special manual:
Same as automatic/manually, however with the additional possibility of adjusting the "magnetizing
force" during parameter programming.

System-Configuration
System
run-in periode
1.0 sec

After the adjusted system settl if ing time the following conditions must be fulfilled:
- Sensor must be in the measuring position
- Tube drive must be adjusted to the target number of revolutions
- In case of sensor NS9S and NS12S: The magnetic field must be at full strength

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 29

The standard adjustment is 1.0 second. It should be reduced only after consultation with ROLAND
ELECTRONIC.

System-Konfiguration
Magnetic field
switch off delay
0.0 sec

After termination of the measuring procedure the magnetic field should be be switched off with a delay.
The tube remains positioned on the sensor and cannot not rotate.

System-Configuration
Default
Speed
81.0 rpm

The adjusted number of revolutions is used as default value after the deletion of the parameters.

System-Configuration
automatic Note:
menu selection If a program change is done very often (i.e. after each measurement),
no this parameter should be set to "no". Otherwise the life time of the
internal storage unit will be shortened.
Possible adjustments:
yes: The program which was used last for measurement is stored and been selected
automatically when reapplying power. The key switch has to be set to "RUN".
no: The control unit remains in the base menu of the applying power and waits for a program
selection via the PLC.

System-Configuration
test sensor cable
yes
This is used to check cable and sensor for defects.

Possible adjustments:
yes: The current for the magnetization of the sensor is monitored. If current is interrupted, the
control unit displays a fault (only meaningful with NS9S and NS12S).
no: Magnetization of the sensor is not monitored (necessary for optical sensors)

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 30

System-Configuration
Re-teach
via PLC-input
standard

Possible adjustments:
normal: Is active with measurement start IN7, then a Re-Teach is performed.
(see "8.5.3 Re-Teach")
special: Is active with measuring start IN7, then a special Re-Teach is performed.
(see "8.5.3 Re-Teach" )
no: No Re-Teach possible.

System-Configuration
Default filter type
(0=standard)
flanke standard(0)

The adjusted filter type is used during automatic teach-in.


The following filter types are available for selection:
0 = standard flank
1 = max/min filter
2 = max/min difference
3 = absolute value
4 = Flank extreme
5 = positive amplit.
6 = negative amplit.

System-Configuration
maximum variation of
weld turn 1 to 2
ratio 2:1 1:2 Während der Positionierung wird die Konstanz des Schweissnaht-
signals überwacht.

Entered here are the necessary changes of the weld seam signal amplitude in order to determine that
the detected weld seam is correct. If larger changes are detected, the output "decreased recognition
reliability" is activated and the message "critical detection" is issued.
Possible adjustments:
Threshold 2:1 1:2: The amplitude can be smaller by the the factor ½, or larger by the factor 2
Threshold 2:1 1:4: The amplitude can be smaller by the the factor ½, or larger by the factor 4
Threshold 4:1 1:4: The amplitude can be smaller by the the factor ¼, or larger by the factor 4

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 31

System-Configuration
Masking of weld seam
for calculation
+/- 5%

For the weld seam detection procedure the surrounding environment regarding the weld seam is not
included in the algorithm. In case of broad weld seams this adjustment should be extended +/- 8%
because the system issues the message "critical detection" even with correct weld seam positioning.

The standard adjustment is +/- 5%. For very high requirements the positioning accuracy and good
signal quality the adjustment shall be set to +/-3%.

8.6.3 D3 - Analog board test

Analogueboard-Test
D/A-Converter 128
A/D-Converter -5
Gain 2

This point refers to testing the analog part of the SND30. At BNC1 a "saw tooth" type signal is issued.
The gain can be adjusted for the test. The entered A/D values displayed for diagnostic purposes. This
value should be around 0 (+/-50) with disconnected sensor cable and an gain adjustment of 1-800.

8.6.4 D4 - Tube signal analysis


This analysis serves the purpose of displaying the tube weld seam signal in analog form. An storage
oscilloscope should be used for this purpose.This can contribute to the error identification in case off
fault the weld seam positioning.

without Filter: the BNC 2 signal is the raw signal


with Filter: the BNC 1 signal is the filtered signal

sensor module

BNC1

BNC2

BNC
test receptacle

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 32

If the second channel of the oscilloscope is connected simultaneously to the TESTBNC (switch
position 4), then the following signal is can be measured.

1 revolution

BNC 1

TEST BNC

weld seam weld seam


beginning of detection end of detection

Explanation:
The signal at the BNC2 is the analog signal. After the High impulse starts in the signal to be measured.
The signal at the TESTBNC indicates with short High impulses the position of the detected weld seam.

1 revolution

BNC 1

TEST BNC

weld seam weld seam


beginning of detection end of detection

Explanation:
The signal at the BNC1 shows the filtered tube signal . This signal is between 0 and 5 V. The larger
the difference between the level of the weld seam signal (position where short impulses are issued at
the TESTBNC) and the noise signals between weld seam position 1 and 2 is, the better can the weld
seam be detected.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 33

8.6.5 D5 - Reset of program parameters


After input of the password the parameters are reset to the default values.

8.6.6. D6 - Tube statistics

Tube statistic
weld det. 100
critical 1
clear with T-key

After applying power the control unit starts the statistics regarding the tubes with detected weld seams
and those with critical detection.
This statistics is deleted:
a) by pressing the T key in the menu option above
b) when switching the control unit off; the statistics is also deleted!

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 34

9. Maintenance

9.1 Control unit


The control unit does not require special maintenance. The positions of the fuses are designated in the
sketch:
a) Fuse TR3 1 slow blow for magnetization (sensor)
b) Fuse TR3 200 mAmps. for PLC inputs
c) Fuse TR3 400 mAmps. for PLC outputs
d) 1 Amps. slow blow in case of 230 VAC; 2 Amps. in case of 115 VAC power supply

9.2 Sensor
The sensors are not affected by oil pollution. Chips and shavings should occasionally be cleaned out
by using compressed air or by simply wiping off.
Adhering chips impair the function of the sensor bearings and the actual sensor element.

9.3 Hardware - Diagnostics


On the back of the enclosure cover is a BNC-receptacle located and a switch with twelve switching
positions.
Signals can be entered into the BNC-receptacle for analysis with an oscilloscope of the various switch
positions.
These signals can be used to make a quick evaluation of faults in case of service requirements.
For the user the first four switching positions are valuable for measuring the operating voltages.

Switching position 1 +5 VDC


Switching position 2 +15 VDC
Switching position 3 -15 VDC
Switching position 4 Diagnostic signal for signal analysis
The signals of the switching positions 5 - 12 are not assigned.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30

Rev. 3.0 Page 35

9.4 Firmware update


The revised SND30 mainboard offers the feature of firmware update.
(new mainboard with BOOT and MENUE key on board)

Required:
- SND30
- RS232 cable to connect to SND30 terminals 31-34 and to PC
- Computer with RS232 interface resp. USB-RS232 converter
- Phytec Flash Tools for firmware flashing
- Firmware

Procedure:
1. Install the flashloader from CD (if not already done).
2. Switch-off the supply voltage.
3. Connect the RS232 cable to the SND30 terminals 31-34 and to the PC
4. Press the BOOT key on the board in the upper section of the unit (see previous illustration)
and keep pressed. Switch-on the supply voltage. Then release the pressed BOOT key.
5. Start the „Phytec Flash Tools“ at the PC.
6. Confirm with OK.
7. Select MINIMODUL 515C and press „connect“. If the board is not found,
select the correct RS232 interface under „Conifig, Protocol, Properties“.
8. Select „Download“.
9. Select „Erase needed sectors“.
10. Set „Bank-Offset“ to „Bank1“.
11. Select the download file „V0173“ (example) with „open“.
12. Download with „Start“. Await the completion.
13. Select „Disconnect“.
14. Perform power OFF-ON at the unit.
The unit must then power up with the previously loaded version.

9.5 Order data


Order-no. Description

SND30 Control unit

NS9S Bearing suppor ted sensor element for tube-Ø from 10 mm to 250 mm and tube wall
thickness to max. 4.0 mm; with cable KNS9S, standard length 5 m

NS12 Bearing suppor ted sensor element for tube-Ø from 10 mm to 250 mm and tube wall
thickness to max. 3.0 mm; with cable KNS9S, standard length 5 m

KNS9S Sensor cable, standard length 5 m (other length on inquiry)

KNS9S-G Sensor cable, standard length 5 m (with rigth angle receptacle for sensor connection)

2299700 GM rubber

2390924 SKF ball bearing 9x24x7 mm for magnetic poles

2390822 Ball bearing 8x22x7 mm for sensor element

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT A
Rev. 3.0 Page 36

A1 Wiring diagram Optocoupler - Interface - Board (Schematic diagram)

4 Measuring signal 1 1
5 Measuring signal 2 2
R2000 SND30
1 + 15 V 3
3 AGND 4
NS XX 2 - 15 V 5
6 + Coil 6
7 - Coil 7

8 Cable shield

Motor
Switch

Relay motor
PLC + 24 VDC
Common
Start measurem. Teach-In Enable
Menue select
Data OUT

M1
M2
M4
M8
M16
(Re-teach)

PLC earth ground


+ 24 VDC
Common
Measurement active
Menu select
ENABLE M1
Data IN

Parameter prog. M2
M4
M8
Reduced detection M16
Motor

RxD
+ GND
GND
24 VDC
TxD
-
Line
Neutral

Central machine ground Earth ground


R 2000

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT A
Rev. 3.0 Page 37

A2 Connection Diagram Optocoupler - Interface - Board

Connector Sensor / Sensors


Sensor Cablecore
Terminal-no. Connector colour Function
1 Pin 4 yellow Sensor Measuring signal 1
2 Pin 5 red Sensor Measuring signal 2
3 Pin 1 white Sensor +15 V
4 Pin 3 brown Sensor AGND
5 Pin 2 green Sensor -15 V
6 Pin 6 grey Sensor + Coil
7 Pin 7 pink Sensor - Coil
8 n.c. blank Sensor Cable shield

Relay Motor
Terminal-no. max. 250 VAC / 30 VDC / 10 Amps
9 N.O. if 24 VDC is active / N.C. if 0 V is active
10 (see Systems Configuration page 2)

Connector Parallel Data Inputs


Terminal-no. Inputs Specification Function
11 PWR + 24 VDC min. 13VDC max. 30VDC Power control (only used when configurated)
12 Common ( - ) 0 VDC Common for all inputs
13 IN 0 + 24 VDC min. 13VDC max. 30VDC Start measurement / Teach-in ENABLE
14 IN 1 + 24 VDC min. 13VDC max. 30VDC Menu select
15 IN 2 + 24 VDC min. 13VDC max. 30VDC M1
16 IN 3 + 24 VDC min. 13VDC max. 30VDC M2
17 IN 4 + 24 VDC min. 13VDC max. 30VDC M4 Menu number
18 IN 5 + 24 VDC min. 13VDC max. 30VDC M8 Binary coded
19 IN 6 + 24 VDC min. 13VDC max. 30VDC M 16
20 IN 7 + 24 VDC min. 13VDC max. 30VDC (Re-teach)

Connector Parallel Data Outputs


Terminal-no. Outputs Specification Function
21 PWR-Input + 24 VDC min. 18VDC max. 30VDC Power input (+24VDC max.500mA) supplied by Customer
22 Common ( - ) 0 VDC Common for all outputs and PWR input
23 OUT 0 UOUT = UPWR - 1 V R > 1200
L Ohm Measurement active
24 OUT 1 UOUT = UPWR - 1 V R > 1200
L Ohm Menu select
25 OUT 2 UOUT = UPWR - 1 V R > 1200
L Ohm ENABLE M1
26 OUT 3 UOUT = UPWR - 1 V R > 1200
L Ohm Parameter programming M2
27 OUT 4 UOUT = UPWR - 1 V R > 1200
L Ohm M 4 Menue number
28 OUT 5 UOUT = UPWR - 1 V R > 1200
L Ohm M 8 Binary coded
29 OUT 6 UOUT = UPWR - 1 V R > 1200
L Ohm Reduced detection reliability M 16
30 OUT 7 UOUT = UPWR - 1 V R > 1200
L Ohm Motor

Connector Serial Interface RS232 (optional )


Terminal-no. Input Output Function
31 RxD Receiver Input RxD RS 232
32 GND Receiver Input GND RS 232
33 GND Transmitter Output GND RS 232
34 TxD Transmitter Output TxD RS 232

Connector POWER
Terminal-no. Input power Function
35 Line 230 VAC 80 VA 115 VAC 80 VA
36 Neutral recommended Fuse 1 A Slow blow recommended Fuse 2 A Slow

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 38

B1 Timing Diagram Optocoupler- Interface - Board, minimum Interface Connection


Parameter-Programming

t1: Time required by the operator in order to select the parameter program to be programmed (see section 5.3 Parameter
programming).
t2/t6: Time required by the PLC in order to prepare the tube for parameter programming (Placing tube on the sensor)
t3/t7: < 10 milliseconds.
t4/t8: Time required for auto optimizing routine depending on tube diameter and rotational speed.
t5: User to evaluate positioning (see section 5.3 Parameter programming, point 15).
t9: Point t6 to t8 repeated several times depending on the operation of the SND30.
t10: Parameter programming is completed.

The total time of parameter programming depends on the tube diameter, the rotational speed and the inputs of the
parameters.
Estimated time is the time required for 25 revolutions.

* The in- and outputs not described here are not required for parameter programming.
** Not necessary or is repeated several times depending on the operation of the SND30.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 39

B2 Timing Diagram Optocoupler- Interface - Board, minimum Interface Connection


Measurement by external PLC

In order to start measurement with IN0, a valid measuring menue must have been selected (externally
or via the keyboard) and the key switch must be in RUN position.

t1: < 5 milliseconds.


t2: > 10 milliseconds.
t3: Depending on tube diameter and rotational speed.
t4: < 20 milliseconds.

* The in- and outputs not described here are not required for parameter programming.
** This output is used only if the option ”Reduced detection reliability“ (see section 5.3 parameter
programming, point 8). A high could mean the weld seam has not been positioned properly (see
section 9. Operating parameters, point 6. Reliability of detection).

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 40

B3 Timing Diagram Optocoupler - Interface - Board, Standard Interface Connection


Measurement Menue select by external PLC, Menue adress Binary coded.
(Strobe-Input IN1, Data-Inputs IN2 to IN6)

To be able to select a Measurement Menu externally, the key-switch must be in position RUN.
If a measurement menue has been selected, that was the not pre-programmed, than there will be no
release by ENABLE and the input data IN2 to IN6 will not be mirrowed to the outputs OUT2 to OUT6.
On the display a note will appear with the indication of missing parameters.

Parallel Data Inputs


IN0
Measurement Start

IN1
Selection of measuring menu

IN2
Binary value 1 M1

IN3
Binary value 2 M2

IN4
Binary value 4 M4

IN5
Binary value 8 M8

IN6
M16
Binary value 16

IN7

Parallel Data Outputs ≥ 0 ms ca. 25ms ≤ 5 ms

OUT0
Measurement active

OUT1
Selection of measuring menu

OUT2
Binary value 1 ** M1 Enable

OUT3
** M2
Binary value 2

OUT4
** M4
Binary value 4

OUT5
** M8
Binary value 8

OUT6
** M16
Binary value 16

OUT7
Motor

IN0 and IN1 are edge triggered interrupt inputs. In the standard-configuration, the positive edge is active. Do not activate
IN0 and IN1 simultaneonsly. A time gap more than 10 milliseconds has to be provided between two command. IN1 is Strobe-
Input for Data-Input IN2 to IN6.

** Signals of the outputs OUT2 to OUT6 have two different functions.


By activating Menue select IN1, inputs IN2 to IN6 are mirrowed at the outputs OUT2 to OUT6 in order to monitor correct
transmission.
By activating the external control command Start measurement IN0, Status messages and Measurement results are
reported. In the standard configuration high level active.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 41

B4 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection


Parameter-Programming

t1: Time required by the operator in order to select the parameter program to be programmed (see section 5.3 Parameter
programming).
t2/t6: Time required by the PLC in order to prepare the tube for parameter programming (Placing tube on the sensor)
t3/t7: <10 milliseconds.
t4/t8: Time required for auto optimizing routine depending on tube diameter and rotational speed.
t5: User to evaluate positioning (see section 8.4 Parameter programming).
t9: Point t6 to t8 repeated several times depending on the operation of the SND30.
t10: Parameter programming is completed.

The total time of parameter programming depends on the tube diameter, the rotational speed and the inputs of the
parameters. Estimated time is the time required for 25 revolutions.

* The in- and outputs not described here are not required for parameter programming.
** Not necessary or is repeated several times depending on the operation of the SND30.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 42

B5 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection


Measurement by external PLC

In order to start measurement with IN0, a valid measuring menue must have been selected (externally
or via the keyboard) and the key switch must be in RUN position.

t1: < 5 milliseconds.


t2: > 10 milliseconds.
t3: Depending on tube diameter and rotational speed.
t4: < 10 milliseconds.
t5: > 20 milliseconds.

IN0 and IN1 are edge triggered interrupt inputs. In the standard-configuration, the positive edge is active. Do not activate
IN0 and IN1 simultaneonsly. A time gap of more than 10 milliseconds has to be provided between two command. IN1 is
Strobe-Input for Data-Input IN2 to IN6.

Signals of the outputs OUT2 to OUT6 have two different functions. By activating Menue select IN1, inputs IN2 to IN6
are mirrowed at the outputs OUT2 to OUT6 in order to monitor correct transmission.
By activating the external control command Start measurement IN0 Status messages and Measurement results are
reported. In the standard configuration is high level active.

* The in- and outputs not described here are not required for parameter programming.
** This output is used only if the option ”Reduced detection reliability“ (see section 5.3 parameter programming, point 8).
A high could mean the weld seam has not been positioned properly.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33
ROLAND
OPERATING INSTRUCTIONS
WELD SEAM DETECTOR SND30
ATTACHMENT B
Rev. 3.0 Page 43

B6 Timing Diagram Optocoupler- Interface - Board, Standard Interface Connection


Re-Teach

In order to start measurement with IN0, a valid measuring menue must have been selected (externally
or via the keyboard) and the key switch must be in RUN position.

Condition for starting a


Mode detection cycle from the PLC

Position key switch

Parallel Data Inputs * Start of Re-Teach

IN0 Measurement start

IN1 Selection of measuring menu

IN2 Re-Teach

Parallel Data Outputs *

OUT0 Measurement active

OUT2 ENABLE

OUT3 Parameter programming

OUT6 Reduced detection reliability

OUT7 Motor

t1
and relay output
terminal 9 and 10 t2 t4 t5
High = closed
Low = open t3

t1: > 5 milliseconds


t2: < 5 milliseconds
t3: Depending on tube diameter and rotational speed
t4: < 10 milliseconds
t5: > 5 milliseconds

IN0 and IN1 are edge triggered interrupt inputs. In the standard-configuration, the positive edge is active. Do not activate
IN0 and IN1 simultaneonsly. A time gap of more than 10 milliseconds has to be provided between two command. IN1 is
Strobe-Input for Data-Input IN2 to IN6.

Signals of the outputs OUT2 to OUT6 have two different functions. By activating Menue select IN1, inputs IN2 to IN6
are mirrowed at the outputs OUT2 to OUT6 in order to monitor correct transmission.
By activating the external control command Start measurement IN0 Status messages and Measurement results are
reported. In the standard configuration is high level active.

* The in- and outputs not described here are not required for parameter programming.
** This output is used only if the option ”Reduced detection reliability“ (see section 5.3 parameter programming, point 8).
A high could mean the weld seam has not been positioned properly.

ROLAND ELECTRONIC GMBH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Telefon +49 (0)7236-93 92-0 · Telefax +49 (0)72 36-9392-33

You might also like