You are on page 1of 12

PS 431 T&D

Time-Overcurrent Protection
Device
Numerical Time-Overcurrent Protection with
Definite -Time and Inverse -Time Characteristics
PS 431 time-overcurrent The PS 431 is constructed
protection devices are used with a multifunctional case
for selective short-circuit design that is equally well
protection in high-voltage suited to wall surface moun-
networks. ting or panel flush mounting
due to the reversible terminal
The networks can be opera- blocks and reversible moun-
ted with impedance neutral ting brackets.
grounding, with resonant
grounding or with an isolated The auxiliary voltage for the
neutral. power supply can be separa-
tely switched internally from
The PS 431 time-overcurrent 110-250 V DC to 24-60 V DC.
protection device has the
following features: The binary signal inputs may
❑ Four-pole measurement be operated with control
(A, B, C, N) voltages of 24-250 V DC.
❑ Phase-selective phase
current timer stage with Current measurement inputs
DTOC and IDMT characte- having a frequency range of
ristics (IDMT can be set to 45-65 Hz, input transducers
normally inverse, very with 1 A and 5 A taps, and
inverse, extremely inverse, the surface-mounting design
long time ground fault or RI provide for optimum use and
inverse) versatility without variance.
❑ Time-lag high set phase
1 PS 431 in case for wall surface or panel flush mounting current timer stage The PS 431 has the following
❑ Residual current timer inputs and outputs:
stage with DTOC and IDMT ❑ 4 current measurement
characteristics (IDMT can inputs
be set to normally inverse, ❑ 2 binary signal inputs
very inverse, extremely (optical couplers) with
inverse, long time ground freely configurable function
fault or RI inverse) assignment
❑ Time-lag high set residual ❑ 4 output relays with freely
current timer stage configurable function
❑ Tripping matrix assignment
❑ Optional latching of the
individual tripping criteria Control and display:
❑ Possibility of reverse inter- ❑ Local control panel
locking ❑ 8 LED indicators, including
❑ Circuit-breaker failure 6 with freely configurable
protection function assignment
❑ PC interface
The protection functions
listed above are complemen- Parameters may be set either
ted by comprehensive self- from the local control panel or
monitoring and fault diagno- through the PC interface, as
sis. In addition, the PS 431 is desired.
equipped with the following
supplementary functions:
❑ Measuring circuit monito-
ring
❑ Operating data measure-
ment
❑ Event counting
❑ Fault data acquisition
❑ Fault logging
PS 431 Time-Overcurrent Protection Device
Functions

Definite or IDMT Mode Tripping Matrix and Latch Reverse Interlocking


Inverse Time-Delay
Short-Circuit Protection In the IDMT (inverse definite The tripping matrix is used to The individual overcurrent
minimum time) mode the decide which of the individu- timer stages can be blocked
The PS 431 time-overcurrent phase current timer stage tI> al overcurrent timer stages externally by way of two
protection device is generally and/or the residual current shall participate in forming independent signals. In this
equipped with four current timer stage tIN> are delayed the general trip command. connection it is possible by
measurement inputs A, B, C by an inverse time lag. The The phase-selective phase using the selection matrix to
and N. other stages and functions current timer stage is perma- determine which of the timer
correspond to the DTOC nently assigned to the gene- stages shall be included in
DTOC Mode mode. ral trip command; this cannot the blocking. This makes it
be changed. Another matrix possible to add on a feature
In DTOC mode (Definite Time For inverse-time delay the is used to determine which of such as reverse interlocking,
Overcurrent), PS 431 has the following tripping time cha- the individual tripping criteria for example (”busbar protec-
following overcurrent timer racteristics can be selected: shall result in latching of the tion with starting the corre-
stages: ❑ Normally inverse general trip command. sponding scan”).
❑ Phase-selective phase ❑ Very inverse
current timer stage I>/tI> ❑ Extremely inverse The function of circuit brea-
❑ Residual current timer ❑ Long time ground fault ker failure protection is also
stage IN>/tIN> ❑ RI inverse considered in the tripping
❑ High set phase current matrix and in the matrix for
timer stage I>>/tI>> The mode, base current, setting the latching function.
❑ High set residual current characteristic type and cha-
timer stage IN>>/tIN>> racteristic factor can be set
independently for the phase
The effect of the timer stages current timer stage and the
measuring in the ground path residual current timer stage.
on the general starting signal
and therefore on the start of a
fault record can be suppres-
sed, if desired. Formation of
the general trip command by
the residual current timer
stages is then automatically
disabled.

All threshold operate values


and lag times can be set
independently.

2 Inverse-time characteristics

Normally inverse
0.14
t = characteristic · ––––––––––– s
factor (I /Iref)0.02 – 1

Very inverse
13.5
t = characteristic · ––––––––––– s
factor (I /I ref) – 1

Extremely inverse
80
t = characteristic · ––––––––––– s
factor (I /Iref)2 – 1

Long time ground fault


120
t = characteristic · ––––––––––– s
factor (I /I ref) – 1

RI inverse
1
t = characteristic · ––––––––––– s
factor 0.236
0.339 – –––––
(I /Iref)

2
PS 431 Time-Overcurrent Protection Device
Functions
(continued)

Cir cuit Br
Circuit eaker Failur
Breaker Failuree Measuring Cir cuit
Circuit Event Counting Self-Monitoring
Pr otection
Protection Monitoring
The following events are Extensive monitoring routines
When the trip command is Measuring circuit monitoring counted by the PS 431 time- in the PS 431 ensure that
issued a timer stage for of the phase currents is overcurrent protection de- internal hardware or software
monitoring the circuit breaker based on the principle of vice: faults will not lead to mal-
is also started. When this maximum allowable magnitu- ❑ Tripping on faults functioning of the protective
timer stage has elapsed due de unbalance. In this case ❑ Faults relaying system. When the
to a sustained general star- the arithmetic difference ❑ Warning entries auxiliary voltage VA is turned
ting condition, then the circuit between the maximum and on, a function test is carried
breaker failure signal is minimum phase currents as Fault Data Acquisition out. Cyclic self-monitoring
issued. referred to the maximum tests are run during operati-
phase current is compared After the end of a general on. If test results deviate
The input of a circuit breaker with the set threshold operate starting condition, the follo- from the default value, a fault
failure signal through an value. With the appropriate wing measured fault data are signal is issued. The result of
appropriately configured settings it is also possible to acquired: fault diagnosis determines
binary input brings about a monitor the phase currents ❑ Running time whether a protective blocking
non-delayed trip command if even with an economy-type ❑ Short-circuit current will occur or whether only a
the general starting signal is CT connection (CTs in only warning will be issued. The
present. two phases). Fault Logging faults diagnosed in con-
junction with self-monitoring
Operating Data Protection signals at the time are stored in a memory
Measur ement
Measurement of a fault are stored in chro- (monitoring signal memory).
nological order. A total of five The contents of the monito-
The PS 431 time-overcurrent faults with a maximum of 64 ring signal memory can be
protection device acquires start/end signals each, can read from the local control
the following measured be held in a circular memory panel.
operating data and updates - the signal memory. If more
them at approximately 1 s than five faults occur and no
intervals, as long as a fault is faults have been erased in
not being processed at the the interim, the oldest fault
time: record will be overwritten. A
❑ Maximum value of the four-digit resettable counter
three phase currents identifies the individual faults
❑ Phase currents by serial number.
❑ Residual current The fault records can be read
from the local control panel.
The measured data are
displayed as r.m.s. values
and are normalized to the
corresponding nominal value
of the protection device.

3
PS 431 Time-Overcurrent Protection Device
Design

Mechanical Design Local Contr ol Panel


Control

The PS 431 consists of an The integrated local control


aluminum case with reversi- panel comprises two 4-digit,
ble connector blocks and 7-segment LCD displays and
adjustable side brackets. six function keys. The set-
The case can be used for tings, signals and measured
wall surface mounting or for variables are numerically
panel flush mounting, as coded. This code is called
desired. In either case the the address and is displayed
unit is connected by in the lower 4-digit 7-segment
threaded terminal ends. display. Access barriers
safeguard against accidental
The processor module car- or unauthorized changing of
rying the local control panel settings.
is mounted directly on the
rear of the removable front Eight LED indicators are
panel. It is connected to the provided for visual signaling.
combined I/O (input/output) The first two have permanent
module by a flat connecting signal assignments, while the
cable. The I/O module con- other six can be configured
tains the voltage supply, the as desired (see Page 9).
input transformers, the output
relays, and the optical coup- The control panel has two
lers for the binary inputs. label strips. The strip on the
left is used to label the LED
In the front panel are win- indicators, and the strip on
dows for the display and the right provides a visual
label strips located behind record of frequently
them. The keyboard for the performed control steps.
integrated local control panel Both strips can be replaced
is also located in the front and labeled by the user as
panel. desired.

Figure 4 on Page 10 shows


the case and mounting
dimensions.

3 Local control panel

4
PS 431 Time-Overcurrent Protection Device
Technical Data

Notices General Data Type Tests Type Tests (continued)


Manufacturer’s Conformity Statement Design All tests according to EN 60255-6 Insulation
The product designated as ”PS 431 Case suitable for wall surface and DIN 57435 Teil 303
Voltage test
Time-Overcurrent Protection Device” mounting or panel flush mounting.
According to IEC 255-5
has been developed and manufac- Electromagnetic Compatibility
Installation Position 2 kV AC, 60 s
tured in conformity with the interna- (EMC)
Vertical ± 30° For the voltage test of the power
tional standard series EN 60255-6
Interference suppression supply inputs, direct voltage
and in accordance with the provisions Degree of Protection
According to EN 55022 and (2.8 kV DC) must be used.
of the Low Voltage Directive issued IP 51 according to DIN VDE 0470
DIN VDE 0878 Part 3, class B The PC interface must not be subject-
by the European Community. and EN 60259 or IEC 529
ed to the voltage test.
1 MHz burst disturbance test
Weight
Membership in ALPHA According to IEC 255 Part 22-1, Impulse voltage withstand test
3.4 kg
AEG and the company that manufac- class III According to IEC 255-5
tures our measurement and protective Dimensions Common mode test voltage: 2.5 kV Front time: 1.2 µs
relays, Hartmann & Braun, are See Page 10 Differential test voltage: 1.0 kV Time to half-value: 50 µs
members of the low-voltage equip- Test duration: > 2 s Peak value: 5 kV
Terminal Connection Diagram
ment testing and certification associa- Source impedance: 200 Ω Source impedance: 500 Ω
See Page 10
tion called ALPHA (Frankfurt am
Immunity to electrostatic discharge
Main, Germany). ALPHA promotes Mechanical Robustness
PC Interface According to EN 60801 Part 2,
independent responsibility on the part
DIN 41652 connector, type severity level 3 Vibration test
of the manufacturer and the assur-
Submin-D, 9-pin. Contact discharge, According to IEC 255-21-1,
ance of high product quality through
A special connecting cable is Single discharges: > 10 test severity class 1
basic process specifications for
required for electrical isolation. Holding time: > 5 s Frequency range, in operation:
equipment inspection and testing in
Test voltage: 6 kV 10 to 60 Hz, 0.035 mm,
compliance with applicable stand-
Terminals Test generator: 60 to 150 Hz, 0.5 g
ards. When certain conditions are
Threaded terminal ends M4, 50 to 100 MW, 150 pF/330 Ω Frequency range, during transport:
met, ALPHA also issues officially
self-centering with wire protection for 10 to 150 Hz, 1 g
recognized product certificates if Immunity to radiated electromagnetic
conductor cross-sections of 0.5 to
required. Furthermore, ALPHA is energy Shock response and withstand test,
6 mm2 or 2 x 2.5 mm2
working toward international recogni- According to ENV 50140, level 3 bump test
tion of conformity declarations and Antenna distance to tested device: According to IEC 255-21-2,
Creepage Distances and Clearances
certificates. > 1 m on all sides test severity class 1
Per IEC 255-5, series C
Test field strength, frequ. band Acceleration: 5 g/15 g
DQS Certificate 80 to 1000 MHz: 10 V/m Pulse duration: 11 ms
The internationally recognized, Test using AM: 1 kHz / 80 %
Seismic test
independent and impartial associa- Single test at 900 MHz:
According to EN 60255-21-3, test
tion for the certification of quality AM 200 Hz /100 %
procedure A, class 1
assurance systems, DQS (Deutsche
Electrical fast transient / burst 5 to 8 Hz, 3.5/1.5 mm,
Gesellschaft zur Zertifizierung von
requirements 8 to 35 Hz, 10/5 m/s2
Qualitätssicherungssystemen), has
According to IEC 801-4, test severity 3 × 1 cycle
awarded AEG the DQS certificate,
level 3
thereby certifying that AEG has
Rise time of one pulse: 5 ns
introduced and uses a state-of-the-art
Impulse duration (50% value): 50 ns Routine Tests
quality assurance system that
Amplitude: 2 kV / 1 kV
complies with all requirements stated
Burst duration: 15 ms
in EN ISO 9001 that apply to its All tests according to EN 60255-6
Burst period: 300 ms
products and services. and DIN 57 435 Part 303
Source impedance: 50 Ω
Surge immunity test Additional thermal test
According to IEC 1000-4-5, 100 % controlled thermal endurance
test level 3 test, inputs loaded
Testing of power supply circuits,
unsymmetrically / symmetrically
operated lines
Open-circuit voltage front time / time Environmental
to half-value: 1.2 / 50 ms Conditions
Short-circuit current front time / time
to half-value: 8 / 20 ms
Allowable ambient temperatures
Amplitude: 1 / 2 kV
Operating temp.: – 5 °C to + 55 °C
Pulse frequency: > 5 / min
Storage temp.: – 25 °C to + 55 °C
Source impedance: 12 / 42 Ω
Shipping temp.: – 25 °C to + 70 °C
Immunity to conducted disturbances
Ambient humidity range
induced by radio frequency fields
Relative humidity to preclude any
According to IEC 65A/
condensation;
77B (Sec) 145/110, test level 2
45 to 75 % (annual mean)
Disturbing test voltage: 3 V
Power frequency magnetic field
immunity
According to EN 61000-4-8, level 4
Frequency: 50 Hz
Test field strength: 30 A/m
Alternating component (ripple) in d.c.
auxiliary energizing quantity of
measuring relays
According to IEC 255-11
12%

5
PS 431 Time-Overcurrent Protection Device
Technical Data
(continued)

Inputs and Outputs Information Output Settings


Measurement Inputs Operating Data Measurement Global Function Parameters Definite-Time Overcurrent
Protection (DTOC)
Current Max. phase current Increments General Starting
Nominal current I nom: I P,max: 0.00-18.00 I nom 0.01 without I N> or IN>> Phase Current
1 and 5 A (terminal choice) with IN> or IN>>
Phase currents Threshold operate value I>: Increments:
Nominal consumption per phase: I A: 0.00-18.00 Inom 0.01 Trip Command 1/2 0.4-4.0 Inom 0.1
< 0.3 VA at Inom I B: 0.00-18.00 Inom 0.01 tI>
Delay time tI>: Increments:
I C: 0.00-18.00 I nom 0.01 tI> CBF
Load rating: 0.00-9.99 s 0.01
tI> tIN>
continuous: 4 Inom Residual current 10.0-99.9/∞ s 0.1
tI> tIN> CBF
for 10 s: 30 Inom I N: 0.00-3.50 Inom 0.01
tI> tI>> Threshold operate value I>>: Increments:
for 1 s: 100 Inom
tI> tI>> CBF 0.4-40.0/∞ Inom 0.1
Event Counting
Frequency tI> tI>> tIN>
Delay time tI>>: Increments:
Nominal frequency f nom: Number of trip commands: tI> tI>> tIN> CBF
0.00-9.99 s 0.01
50 or 60 Hz 0 to 9999
Latching 1/2
Number of faults: 0 to 9999 Residual Current
Operating range: without latching
45 to 65 Hz
– CBF Threshold operate value IN>: Increments:
Fault Data Acquisition
tIN> 0.05-2.00/∞ Inom 0.05
Increments
Binary Signal Inputs tIN> CBF
Running time: Delay time tI N>: Increments:
tI>>
Equipment: 0.00-99.99 s 0.01 0.00-9.99 s 0.01
tI>> CBF
2 optical coupler inputs (freely Short-circuit current: 10.0-99.9/∞ s 0.1
tI>> tIN>
configurable) 0.00-36.00 I nom 0.01
tI>> tIN> CBF Threshold operate value IN>>:Increments:
Function assignment: tI> 0.10-8.00/∞ Inom 0.05
Fault Logging
see Page 9 tI> CBF
Delay time tI N>>: Increments:
Up to 5 faults are stored, then the tI> tIN>
Nominal V In,nom : 0.00-9.99 s 0.01
oldest fault is erased. tI> tIN> CBF
24-250 V DC 10.0-99.9/∞ s 0.1
tI> tI>>
Operating range: Up to 64 signals per fault can be tI> tI>> CBF
Inverse Definite Minimum Time
0.8-1.1 VIn,nom with a residual ripple of stored, subsequent signals trigger the tI> tI>> tIN>
Overcurrent Protection (IDMT)
up to 12% of V In,nom overflow indication. tI> tI>> tIN> CBF
Phase Current
Power consumption per input: Trip Command 2/2
35 mA ± 30% at V In, nom = 24 V DC without tIN>> Base current IB : Increments:
15 mA ± 30% at V In,nom = 48 V DC with tIN>> 0.40-4.00 Inom 0.01
4 mA ± 30% at VIn,nom = 60-250 V DC
Latching 2/2 Characteristic factor: Increments:
without latching at tIN>> 0.10-1.00 Inom 0.05
Output Relays
with latching at tIN>>
Characteristic type:
Equipment:
Blocking E1 Normally inverse
4 output relays (freely configurable)
without block Very inverse
Function assignment: tIN>> Extremely inverse
see Page 9 tIN> Long time ground fault
tIN> tIN>> RI inverse
Contact rating
tI>>
Threshold operate value I>>: Increments:
Rated voltage: tI>> tIN>>
0.4-40.0/∞ Inom 0.1
300 V DC, 250 V AC tI>> tIN>
tI>> tIN> tIN>> Delay time tI>>: Increments:
Continuous current: 5 A
tI> 0.00-9.99 s 0.01
Short-time current: tI> tIN>>
Residual Current
30 A for 0.5 s tI> tIN>
tI> tIN> tIN>> Base current I NB or
Making capacity:
tI> tI>> Threshold operate value I>: Increments:
1000 W (VA) at L/R = 40 ms
tI> tI>> tIN>> 0.04-0.40/∞ Inom 0.01
Breaking capacity: tI> tI>> tIN> 0.08-0.80/∞ Inom 0.01
0.2 A at 220 V DC and tI> tI>> tIN> tIN>>
Characteristic factor: Increments:
L/R = 40 ms
Blocking E2 0.10-1.00 Inom 0.05
4 A at 230 V AC and cos ϕ = 0.4
See selection for blocking E1
Characteristic type:
Local Control Panel Mode for Current Timer Stages Normally inverse
Definite-time-lag (DTOC) Very inverse
Input or output of protection data:
Inverse-time-lag (IDMT) Extremely inverse
via six keys and two 4-digit displays
Long time ground fault
State and fault signals: RI inverse
8 LED indicators
Delay time tI N>: Increments:
(2 permanently assigned,
0.00-9.99 s 0.01
6 freely configurable)
10.0-99.9/∞ s 0.1
Function assignment:
Threshold operate value IN>>: Increments:
see Page 9
0.10-8.00/∞ Inom 0.05
PC Interface Delay time tI N>>: Increments:
0.00-9.99 s 0.01
Transmission speed:
10.0-99.9/∞ s 0.1
4800 baud
A special PC connecting cable is
required for connecting to a PC
(see Page 12).

6
PS 431 Time-Overcurrent Protection Device
Technical Data
(continued)

Settings (continued) Typical Characteristic Deviations Power Supply


Data
Circuit Breaker Failure Time-Overcurrent Protection 1) Nominal auxiliary voltage VA,nom:
Protection Reset time 24-60 V DC and (internally switcha-
Threshold Operate Values, Phase-
from 2-fold threshold operating value ble) 110-250 V DC / 100-230 V AC 3)
tCBF: 0.00-9.99/∞ s; increments: 0.01 Current Stages
to 0: Deviation when I < 0.2 Inom: ± 15% Operating range for direct voltage:
Measuring-Circuit Monitoring ≤ 25 ms Deviation when I ≥ 0.2 I nom: ± 5% 0.8 to 1.1 Vnom
Resetting ratio: Variation at 20°C ± 20 K: ± 2.5% with a residual ripple of
Mode:
without ≥ 0.95 Variation at V A,nom ± 20%: ± 1% up to 12% of V A,nom
Variation at f nom ± 5%: ± 5%
IA , IB Minimum output pulse for trip com- For alternating voltage:
IA , IB , I C mand: Threshold Operate Values, Residual 0.9-1.1 V A,nom
Imcm >: 0.25-0.50 IPmax; increments: 0.05 100 ms Current Stages
Nominal consumption:
tmcm: 0.00-9.99s; increments: 0.01 Deviation: ± 5%
approx. 5 W at VA = 220 V DC
0.0-99.9/∞ s; increments: 0.1 Variation at 20°C ± 20 K: ± 2.5%
Variation at V A,nom ± 20%: ± 1%
Variation at f nom ± 5%: ± 5%
Delay Time of Definite-Time-Delayed
Stages
Deviation: ± 1% or ± 30 ms
Variation at 20°C ± 20 K: ± 1%
Delay Time of Inverse-Time-Delayed
Stages
Deviation: ± 7.5%
Variation at 20°C ± 20 K: ± 2.5%
Variation at V A,nom ± 20%: ± 1%
Variation at f nom ± 5%: ± 5%

Operating Data Measurement2)


Currents IA , I B, I C, IN each > 0.4 I nom
Deviation: ± 5%
Variation at 20°C ± 20 K: ± 2.5%
Variation at V A,nom ± 20%: ± 1%
Variation at f nom ± 5%: ± 5%

Fault Data Acquisition2)


Short-circuit current > 0.4 Inom :
Deviation: ± 5%
Variation at 20°C ± 20 K: ± 2.5%
Variation at V A,nom ± 20%: ± 1%
Variation at f nom ± 5%: ± 5%

1)
Deviations referred to the set value
with sinusoidal measured variables,
total harmonic distortion ≤ 2%,
ambient temperature 20°C, and
nominal auxiliary voltage V A,nom
2)
Deviations referred to the
respective nominal value with
3)
sinusoidal measured variables, V A,nom = 230 V AC only for units with
total harmonic distortion ≤ 2%, a corresponding indication on the
ambient temperature 20°C, and type identification label (beginning
nominal auxiliary voltage V A,nom with hardware version 302)

7
PS 431 Time-Overcurrent Protection Device
Signal List

Signal Inputs LED Indicators Output Relays Abbreviations for


Function Groups
The signal inputs allow inter- Two LED indicators on the The output relays are freely CBF: Circuit breaker
vention in the Protection local control panel have configurable and can be failure protection
sequence. Each input can be permanently assigned sig- assigned any of the signals
set for one of the signals nals (Table 2a). The other six listed in Table 3. Any signal DTOC: Definite-time
given in Table 1. However, a LED indicators are freely can also be assigned to more overcurrent
given signal may be as- configurable and can be than one free output relay for protection
signed to only one input. The assigned any of the signals contact multiplication purpo- IDMT: Inverse definite
signal names refer to the listed in Table 2b. ses. minimum time
”active” state of the input overcurrent
signal. Each input can be set All relays are operated in an protection
as follows: energize-on-signal arrange-
active = low signal or ment (‘open-circuit function’, MAIN: Main function
active = high signal. the make contact is closed MON: Self-monitoring
when the signal is present)
except for the case where an
output relay is configured for
the signal ”MAIN: Blocked/
faulty.” In this case the relay
operates in an normally-
energized arrangement
(‘closed-circuit function’) and
the break contact is closed
for the blocked/faulty conditi-
on.

8
PS 431 Time-Overcurrent Protection Device
Signal List
(continued)

Table 1: Table 2a: Table 2b: Table 3:


Freely Configurable Signal Permanently Configured LED Freely Configurable LED Freely Configurable Output
Inputs Indicators Indicators Relays
Input Func- Signal Indi- Func- Signal Indi- Func- Signal Re- Func- Signal
tion cator tion cator tion lays tion
Group Group Group Group
U1 Without function H1 MON: Warning H3 Without function K1 Without function
U2 MAIN: Block outp. rel. EXT H2 MAIN: Blocked/faulty H4 MAIN: Trip command K2 MAIN: Trip command
E1 block. EXT H5 E1 block. EXT K3 Blocked/faulty
E2 block. EXT E2 block. EXT IDMT/
H6 K4
Reset latch. + indic. IDMT/ DTOC: Starting I> or Iref>
Reset latch. EXT H7 DTOC: Starting I> or Iref> Starting I>>
Reset indicat. EXT H8 Starting I>> Starting GF
CBF: Input EXT Starting A Gen. starting
Starting B tI>> elapsed
Starting C tI> or tI>>
Starting GF tIN> elapsed
Gen. starting tIN>> elapsed
tI>> elapsed tIN> or tIN>>
tI> or tI>> tIref elapsed inv.
tIN> elapsed tINref elapsed inv.
tIN>> elapsed
tIN> or tIN>> CBF: tCBF elapsed
tIref elapsed inv.
tINref elapsed inv. MON: tmcm
Warning
CBF: Input EXT
tCBF elapsed DTOC: tI> elapsed def.
MON: tmcm
DTOC: tI> elapsed def.

9
PS 431 Time-Overcurrent Protection Device
Dimensional Drawing and Terminal Connection Diagram

4 Dimensional drawing and panel cutout

20.6
20.6
Æ 6.4
19 X3 X3 36

F PS 431

x y
294.2

254

294.2
299

256 +1
281 +1
E R

279
289
309

300
X6
!

1 X1 X1 18

48.6 65.6 +
6.4 9 125 - 0.5

11800.DS4
+ 0.5
125 93 162.5 -
175.6 172
Surface-mounting Surface-mounting Flush-mounting Panel cut-out and mounting frame outline

5 Terminal connection diagram

Power Supply LED


Indicators
X1
L+ 13 H1 MON: Warning
Aux. voltage VA 2)
L– 14 U100 H2 MAIN: Blocked/Faulty

H3 IDMT/DTOC: Starting A 1)

H4 IDMT/DTOC: Starting B 1)
Meas. Inputs H5 IDMT/DTOC: Starting C 1)
X1 H6 IDMT/DTOC: Starting GF 1)
A1 1 (1 A)
A2 2 (5 A) T1 H7 IDMT/DTOC: tI> V tI>> 1)
A3 3
B1 4 (1 A) H8 IDMT/DTO C: tIN> V tIN>> 1)
B2 5 (5 A) T2
B3 6
C1 7 (1 A)
C2 8 (5 A) T3
C3 9
N1 10 (1 A)
N2 11 (5 A) T4
N3 12

Signal Inputs Output Relays


X3
X1 36
MAIN: Reset latch.+indic. 1) L+ 15 35 MAIN: Trip command 1)
L– 16 U1 K1 33
MAIN: Block. outp. rel. EXT 1) L+ 17 32
L– 18 U2 34
31
30 IDMT/DTOC: Gen. starting 1)
PC Interface K2 28
27
29
1) Freely configurable (see signal list on X6 26
page 9); signals as per factory setting D1 2 25 1)

are entered in the diagram


1)
D2 3 K3 23
E2 5 22
24
2) L+ und L- circuit may be tested only 20
K4 19 Main: Blocked/Faulty 1)
11801.DS4

with 2.8 kV DC to ground


PS 431 21
3) Internal interface, voltage test is
prohibited

10
PS 431 Time-Overcurrent Protection Device
Connection Example

6 PS 431 connection example

A
B
C Power Supply LED
Indicators
X1
L+ 13 H1
Aux. voltage VA 2)
L– 14 U100 H2

H3

H4
Meas. Inputs H5
X1 H6
A1 1 (1 A)
A2 2 (5 A) T1 H7
A3 3
B1 4 (1 A) H8
B2 5 (5 A) T2
B3 6
C1 7 (1 A)
C2 8 (5 A) T3
C3 9
N1 10 (1 A)
N2 11 (5 A) T4
N3 12

Signal Inputs Output Relays


X3
X1 36
L+ 15 35
L– 16 U1 K1 33
L+ 17 32
L– 18 U2 34
31
30
PC Interface K2 28
27
29
X6 26
D1 2 25
1) D2 3 K3 23
E2 5 22
24
20
K4 19
11801.DS4

11802.ds4

PS 431 21

11
PS 431 Time-Overcurrent Protection Device AEG Energietechnik GmbH AEG Starkstromanlagen Dresden GmbH
Bereich Schutz- und Schaltanlagenleittechnik Bereich Schutz- und Schaltanlagenleittechnik
Ordering Information System Protection and Control System Protection and Control
Lyoner Straße 44-48 Königsbrücker Straße 124
D-60528 Frankfurt D - 01099 Dresden
P.O. Box 71 01 07 P.O. Box 10 03 60
D-60491 Frankfurt D-01073 Dresden
Phone +49 69 6632 1521 Phone +49 351 820 3360
Fax +49 69 6632 2548 Fax +49 351 820 3366

Numerical time-overcurrent protection


device with inverse-time and definite- Designs Order No. Extension No.
time characteristics (append to order no.)

Case for panel surface or flush PS 431


mounting Wall-mounting case with 36 terminals
4-pole measurement (A, B, C, N) for wall surface mounting 89431-0- 1 1 2 3 3 1 0
for panel flush mounting with cover frame 89431-0- 2 1 2 3 3 1 0
User-selection of IDMT or DTOC mode
Phase-selective overcurrent timer Nominal current Inom : Phase current inputs 1 A, residual current input 5 A
stage and starting signals Nominal frequency fnom : 50 Hz and 60 Hz
Nominal auxiliary voltage for power supply V A,nom:
Time-lag high set phase current and 24-60 V DC and 110-250 V DC or 100-230 V AC 1)
high set residual current stages Nominal auxiliary voltage for signal inputs V In,nom:
Tripping matrix 24-250 V DC

Optional latching of individual Additional Options


tripping criteria
Circuit breaker failure protection Labeling and documentation in English -598

Option of reverse interlocking Accessories


Measuring circuit monitoring
PC connecting cable (2.5 m) 255 002 096
Operating data measurement FPCC parameter setting program 251 254 271
Event counting
Fault data acquisition
1) Range selection via plug-in jumper, factory setting underlined.

Fault logging
Comprehensive self-monitoring
2 signal inputs (freely configurable)

Subject to modifications · Printed in Germany


4 output relays (freely configurable)
Integrated local control panel
8 LED indicators (6 freely configurable)
PC interface

SLTS.06.04185PDF/0597EN · Ti

You might also like