Professional Documents
Culture Documents
Time-Overcurrent Protection
Device
Numerical Time-Overcurrent Protection with
Definite -Time and Inverse -Time Characteristics
PS 431 time-overcurrent The PS 431 is constructed
protection devices are used with a multifunctional case
for selective short-circuit design that is equally well
protection in high-voltage suited to wall surface moun-
networks. ting or panel flush mounting
due to the reversible terminal
The networks can be opera- blocks and reversible moun-
ted with impedance neutral ting brackets.
grounding, with resonant
grounding or with an isolated The auxiliary voltage for the
neutral. power supply can be separa-
tely switched internally from
The PS 431 time-overcurrent 110-250 V DC to 24-60 V DC.
protection device has the
following features: The binary signal inputs may
❑ Four-pole measurement be operated with control
(A, B, C, N) voltages of 24-250 V DC.
❑ Phase-selective phase
current timer stage with Current measurement inputs
DTOC and IDMT characte- having a frequency range of
ristics (IDMT can be set to 45-65 Hz, input transducers
normally inverse, very with 1 A and 5 A taps, and
inverse, extremely inverse, the surface-mounting design
long time ground fault or RI provide for optimum use and
inverse) versatility without variance.
❑ Time-lag high set phase
1 PS 431 in case for wall surface or panel flush mounting current timer stage The PS 431 has the following
❑ Residual current timer inputs and outputs:
stage with DTOC and IDMT ❑ 4 current measurement
characteristics (IDMT can inputs
be set to normally inverse, ❑ 2 binary signal inputs
very inverse, extremely (optical couplers) with
inverse, long time ground freely configurable function
fault or RI inverse) assignment
❑ Time-lag high set residual ❑ 4 output relays with freely
current timer stage configurable function
❑ Tripping matrix assignment
❑ Optional latching of the
individual tripping criteria Control and display:
❑ Possibility of reverse inter- ❑ Local control panel
locking ❑ 8 LED indicators, including
❑ Circuit-breaker failure 6 with freely configurable
protection function assignment
❑ PC interface
The protection functions
listed above are complemen- Parameters may be set either
ted by comprehensive self- from the local control panel or
monitoring and fault diagno- through the PC interface, as
sis. In addition, the PS 431 is desired.
equipped with the following
supplementary functions:
❑ Measuring circuit monito-
ring
❑ Operating data measure-
ment
❑ Event counting
❑ Fault data acquisition
❑ Fault logging
PS 431 Time-Overcurrent Protection Device
Functions
2 Inverse-time characteristics
Normally inverse
0.14
t = characteristic · ––––––––––– s
factor (I /Iref)0.02 – 1
Very inverse
13.5
t = characteristic · ––––––––––– s
factor (I /I ref) – 1
Extremely inverse
80
t = characteristic · ––––––––––– s
factor (I /Iref)2 – 1
RI inverse
1
t = characteristic · ––––––––––– s
factor 0.236
0.339 – –––––
(I /Iref)
2
PS 431 Time-Overcurrent Protection Device
Functions
(continued)
Cir cuit Br
Circuit eaker Failur
Breaker Failuree Measuring Cir cuit
Circuit Event Counting Self-Monitoring
Pr otection
Protection Monitoring
The following events are Extensive monitoring routines
When the trip command is Measuring circuit monitoring counted by the PS 431 time- in the PS 431 ensure that
issued a timer stage for of the phase currents is overcurrent protection de- internal hardware or software
monitoring the circuit breaker based on the principle of vice: faults will not lead to mal-
is also started. When this maximum allowable magnitu- ❑ Tripping on faults functioning of the protective
timer stage has elapsed due de unbalance. In this case ❑ Faults relaying system. When the
to a sustained general star- the arithmetic difference ❑ Warning entries auxiliary voltage VA is turned
ting condition, then the circuit between the maximum and on, a function test is carried
breaker failure signal is minimum phase currents as Fault Data Acquisition out. Cyclic self-monitoring
issued. referred to the maximum tests are run during operati-
phase current is compared After the end of a general on. If test results deviate
The input of a circuit breaker with the set threshold operate starting condition, the follo- from the default value, a fault
failure signal through an value. With the appropriate wing measured fault data are signal is issued. The result of
appropriately configured settings it is also possible to acquired: fault diagnosis determines
binary input brings about a monitor the phase currents ❑ Running time whether a protective blocking
non-delayed trip command if even with an economy-type ❑ Short-circuit current will occur or whether only a
the general starting signal is CT connection (CTs in only warning will be issued. The
present. two phases). Fault Logging faults diagnosed in con-
junction with self-monitoring
Operating Data Protection signals at the time are stored in a memory
Measur ement
Measurement of a fault are stored in chro- (monitoring signal memory).
nological order. A total of five The contents of the monito-
The PS 431 time-overcurrent faults with a maximum of 64 ring signal memory can be
protection device acquires start/end signals each, can read from the local control
the following measured be held in a circular memory panel.
operating data and updates - the signal memory. If more
them at approximately 1 s than five faults occur and no
intervals, as long as a fault is faults have been erased in
not being processed at the the interim, the oldest fault
time: record will be overwritten. A
❑ Maximum value of the four-digit resettable counter
three phase currents identifies the individual faults
❑ Phase currents by serial number.
❑ Residual current The fault records can be read
from the local control panel.
The measured data are
displayed as r.m.s. values
and are normalized to the
corresponding nominal value
of the protection device.
3
PS 431 Time-Overcurrent Protection Device
Design
4
PS 431 Time-Overcurrent Protection Device
Technical Data
5
PS 431 Time-Overcurrent Protection Device
Technical Data
(continued)
6
PS 431 Time-Overcurrent Protection Device
Technical Data
(continued)
1)
Deviations referred to the set value
with sinusoidal measured variables,
total harmonic distortion ≤ 2%,
ambient temperature 20°C, and
nominal auxiliary voltage V A,nom
2)
Deviations referred to the
respective nominal value with
3)
sinusoidal measured variables, V A,nom = 230 V AC only for units with
total harmonic distortion ≤ 2%, a corresponding indication on the
ambient temperature 20°C, and type identification label (beginning
nominal auxiliary voltage V A,nom with hardware version 302)
7
PS 431 Time-Overcurrent Protection Device
Signal List
8
PS 431 Time-Overcurrent Protection Device
Signal List
(continued)
9
PS 431 Time-Overcurrent Protection Device
Dimensional Drawing and Terminal Connection Diagram
20.6
20.6
Æ 6.4
19 X3 X3 36
F PS 431
x y
294.2
254
294.2
299
256 +1
281 +1
E R
279
289
309
300
X6
!
1 X1 X1 18
48.6 65.6 +
6.4 9 125 - 0.5
11800.DS4
+ 0.5
125 93 162.5 -
175.6 172
Surface-mounting Surface-mounting Flush-mounting Panel cut-out and mounting frame outline
H3 IDMT/DTOC: Starting A 1)
H4 IDMT/DTOC: Starting B 1)
Meas. Inputs H5 IDMT/DTOC: Starting C 1)
X1 H6 IDMT/DTOC: Starting GF 1)
A1 1 (1 A)
A2 2 (5 A) T1 H7 IDMT/DTOC: tI> V tI>> 1)
A3 3
B1 4 (1 A) H8 IDMT/DTO C: tIN> V tIN>> 1)
B2 5 (5 A) T2
B3 6
C1 7 (1 A)
C2 8 (5 A) T3
C3 9
N1 10 (1 A)
N2 11 (5 A) T4
N3 12
10
PS 431 Time-Overcurrent Protection Device
Connection Example
A
B
C Power Supply LED
Indicators
X1
L+ 13 H1
Aux. voltage VA 2)
L– 14 U100 H2
H3
H4
Meas. Inputs H5
X1 H6
A1 1 (1 A)
A2 2 (5 A) T1 H7
A3 3
B1 4 (1 A) H8
B2 5 (5 A) T2
B3 6
C1 7 (1 A)
C2 8 (5 A) T3
C3 9
N1 10 (1 A)
N2 11 (5 A) T4
N3 12
11802.ds4
PS 431 21
11
PS 431 Time-Overcurrent Protection Device AEG Energietechnik GmbH AEG Starkstromanlagen Dresden GmbH
Bereich Schutz- und Schaltanlagenleittechnik Bereich Schutz- und Schaltanlagenleittechnik
Ordering Information System Protection and Control System Protection and Control
Lyoner Straße 44-48 Königsbrücker Straße 124
D-60528 Frankfurt D - 01099 Dresden
P.O. Box 71 01 07 P.O. Box 10 03 60
D-60491 Frankfurt D-01073 Dresden
Phone +49 69 6632 1521 Phone +49 351 820 3360
Fax +49 69 6632 2548 Fax +49 351 820 3366
Fault logging
Comprehensive self-monitoring
2 signal inputs (freely configurable)
SLTS.06.04185PDF/0597EN · Ti