Communicating to a Siemens Logo! Basic


Module via Ethernet
Red Lion Controls

👤 1 year ago ·
Updated

Follow

Abstract

This document describes using the Siemens S7-300/400 TCP/IP Master driver to communicate with a
Siemens Logo! Basic module.

Products

Red Lion Controls CR1000 Human Machine Interface (HMI), CR3000 HMI, Data Acquisition (DA10,
DA30), Data Station Plus, FlexEdge™ (DA50D, DA70D), G3 HMI, G3 Kadet HMI, Graphite® Controller,
Graphite HMI, Modular Controller, and ProducTVity Station™ 

Use Case

Communicating with a Siemens Logo! module.


Support
Introduction
https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 1/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support

Red Lion has not had the chance to test all of the Logo! modules, the mapping mentioned below are the
ones that Red Lion or customers have verified with the modules that have been tested.

Crimson Communication Configuration

1. Navigate to the COmmunications section.

2. Click on Network (Crimson 3.x) or Ethernet (Crimson 2.0).

3. Configure the Ethernet port as required for the application.

4. Click on the first available Protocol under Network (or Ethernet).

5. Click the Pick button in the Driver Selection section.

6. Under Manufacturer, choose Siemens.

7. Under Driver, select S7-300/400 TCP/IP Master, as shown in Figure 1.

Figure 1.

8. Click OK.

9. Click on the device below the protocol, PLC1 as shown in Figure 2.


https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 2/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support

Figure 2.

10. Set the IP Address to the IP address of the Logo! module.

Crimson Tag Mapping

The following sections show how the addresses in the Logo! correspond to the addresses available in
Crimson.  In the case of bits, the Red Lion address is listed as Byte.Bit. Figure 3 shows a Flag tag mapped
to MB1.3 (M12 in the Logo!).

https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 3/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support

Figure 3.

The following data is available for access from the Logo! modules that have been tested:

M Flags

Logo! Red Lion


M1 MB0.0
M2 MB0.1
M3 MB0.2
M4 MB0.3
M5 MB0.4
M6 MB0.5
M7 MB0.6
M8 MB0.7
M9 MB1.0
M10 MB1.1
M11 MB1.2
M12 MB1.3
M13 MB1.4
https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 4/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support

M14 MB1.5
M15 MB1.6

M16 MB1.7
M17 MB2.0
M18 MB2.1
M19 MB2.2
M20 MB2.3
M21 MB2.4
M22 MB2.5
M23 MB2.6
M24 MB2.7
M25 MB3.0
M26 MB3.1
M27 MB3.2
M28 MB3.3
M29 MB3.4
M30 MB3.5
M31 MB3.6
M32 MB3.7
Input Bits

Logo! Red Lion


I1 IB0.0
I2 IB0.1
I3 IB0.2
I4 IB0.3
I5 IB0.4
I6 IB0.5
I7 IB0.6
I8 IB0.7
Output Bits

Logo! Red Lion


Q1 QB0.0
Q2 QB0.1
Q3 QB0.2
Q4 QB0.3
Analog Inputs and Outputs

https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 5/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support

Analog inputs and outputs will most likely be mapped to I or Q registers, respectively.  They are 16-bit
values, so Numeric tags would need to be mapped with the Byte as Word data type. 

Disclaimer

It is the customer's responsibility to review the advice provided herein and its applicability to the system.
Red Lion makes no representation about specific knowledge of the customer's system or the specific
performance of the system. Red Lion is not responsible for any damage to equipment or connected
systems. The use of this document is at your own risk. Red Lion standard product warranty applies.

Red Lion Technical Support

If you have any questions or trouble contact Red Lion Technical Support by clicking here or calling 1-877-
432-9908.

For more information: http://www.redlion.net/support/policies-statements/warranty-statement



Was this article helpful?

✓ Yes
✕ No

0 out of 0 found this helpful

Have more questions? Submit a request

Return to top ⬆

Related articles

Red Lion Communication with Siemens S7‐300/400 PLCs via Ethernet

Crimson 3.x: Best Practices

Secure Remote Access Platform - Driver List

Converting Parker SSD DSI Files to Red Lion Crimson Files

Crimson 3.1: Packet Capture


https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 6/7