Abstract
This document describes using the Siemens S7-300/400 TCP/IP Master driver to communicate with a
Siemens Logo! Basic module.
Products
Red Lion Controls CR1000 Human Machine Interface (HMI), CR3000 HMI, Data Acquisition (DA10,
DA30), Data Station Plus, FlexEdge™ (DA50D, DA70D), G3 HMI, G3 Kadet HMI, Graphite® Controller,
Graphite HMI, Modular Controller, and ProducTVity Station™
Use Case
Red Lion has not had the chance to test all of the Logo! modules, the mapping mentioned below are the
ones that Red Lion or customers have verified with the modules that have been tested.
Figure 1.
8. Click OK.
Figure 2.
The following sections show how the addresses in the Logo! correspond to the addresses available in
Crimson. In the case of bits, the Red Lion address is listed as Byte.Bit. Figure 3 shows a Flag tag mapped
to MB1.3 (M12 in the Logo!).
https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 3/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support
Figure 3.
The following data is available for access from the Logo! modules that have been tested:
M Flags
M14 MB1.5
M15 MB1.6
M16 MB1.7
M17 MB2.0
M18 MB2.1
M19 MB2.2
M20 MB2.3
M21 MB2.4
M22 MB2.5
M23 MB2.6
M24 MB2.7
M25 MB3.0
M26 MB3.1
M27 MB3.2
M28 MB3.3
M29 MB3.4
M30 MB3.5
M31 MB3.6
M32 MB3.7
Input Bits
https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 5/7
23/7/2021 Communicating to a Siemens Logo! Basic Module via Ethernet – Red Lion Support
Analog inputs and outputs will most likely be mapped to I or Q registers, respectively. They are 16-bit
values, so Numeric tags would need to be mapped with the Byte as Word data type.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system.
Red Lion makes no representation about specific knowledge of the customer's system or the specific
performance of the system. Red Lion is not responsible for any damage to equipment or connected
systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
If you have any questions or trouble contact Red Lion Technical Support by clicking here or calling 1-877-
432-9908.
✓ Yes
✕ No
Return to top ⬆
Related articles
.
Red Lion Support English (US) TEL: 877-432-9908
Powered by Zendesk
https://support.redlion.net/hc/en-us/articles/360041292272-Communicating-to-a-Siemens-Logo-Basic-Module-via-Ethernet 7/7