TRANSFORMER TEST REPORT – AYO NIO 2 300kVA

01/04/2020
1. TRANSFORMER DATA:
MAKE: -
RATING: 300kVA
SERIAL No: -
%IMPEDANCE: -
VECTOR GROUP: Dyn11
YEAR OF MANUFACTURE: -
VOLTAGE LEVEL: 11/0.415kV

2. INSULATION RESISTANCE TEST (Using 5kV


a. HV-Ground: 27.2 MOhms
LV-Ground: 27.7 MOhms
HV-LV: 17.8 MOhms

3. TRANSFORMER RATIO TEST: Using 1phase, 240V Supply


H.T INPUT VOLTAGE (V) L.V MEASURED VOLTAGE (V)
R-Y Y-B B-R r-y y-b b-r r-n y-n b-n
R-Y
Y-B
B-R

4. CONTINUITY TEST: OK

5. EXCITATION TEST
rn: 10.4A
yn: 14.6A
bn: 19.9A

Remark: The Transformer has low insulation resistance across all three tested points and high
excitation current.

Tested by: Akute TTT.

Gogo Ndulue
OMC Akute Undertaking.