I first began using ControlLogix in 2001, back when the software and firmware

were both at version 7.

In those early days it wasn't so easy to add a new remote I/O Chassis to an
existing ControlLogix system as most of the systems at that time were networked
together using ControlNet.

Image by Brandon Cooper

While ControlNet is a truly deterministic network, first the hurdle most users ran into when
adding new I/O to an existing network was they needed to use a separate software package called
“RSNetworx for ControlNet” to configure (aka “schedule”) the network.
And to schedule the network you not only had to put your ControlLogix into program mode, you
also had to understand the nuances of the network's NUT (network update time) and RPI
(Requested Packet Interval) settings.

As the hardware and software of ControlLogix has evolved, so has the ease of configuration and
capabilities of adding a new I/O Chassis without taking the Controller to “program  mode.”

You can now even add a new 1756 remote I/O chassis at any time while the controller is in run
mode, all without disturbing the currently running process.

That said, there's always a risk when modifying a control system during operation, so take all
risks into consideration before attempting any of these modifications to a control system that is
on process.

In our facility we now use EtherNet/IP to connect to remote racks of I/O, and many of our
systems implement Rockwell's DLR (Device Level Ring) architecture.

DLR was developed by Rockwell to provide network redundancy to devices in an EtherNet/IP


ring.

In today's article I walk you through the basic setup instructions to configure a new DLR
connection from a primary ControlLogix chassis to a remote chassis of 1756 I/O:

Setting Up DLR For A Remote I/O Chassis

Step 1) In Studio 5000, add a 1756-EN2TR in your controller's chassis to be the primary device
on a new DLR network:
Image by Brandon Cooper

Step 2) On the network tab of the module properties window, enable “Supervisor Mode”:
Image by Brandon Cooper

Step 3) Next, click on the “Advance Button” and set the “Supervisor Precedence” to 20 (the
higher the number the higher the voting priority for determining the supervisor node)
Image by Brandon Cooper

Step 4) Next, add a second 1756-EN2TR on the Ethernet network under the primary EN2TR.
This represents the network adapter for the remote I/O chassis, and preferably the slot of the
module will be set to 0. This remote EN2TR will also need to have a unique IP Address on the
same subnet as the primary EN2TR.

Step 5) On the network tab of the module properties window for the remote EN2TR, enable the
“Supervisor Mode” as well:
Image by Brandon Cooper

Step 6) Then click the “Advanced” button, and set the supervisor precedence to 10 (This node
will be the backup supervisor)

I
mage by Brandon Cooper
Step 7) Now create a message in ladder to read diagnostic information from the DLR
Supervisor:

Image by Brandon Cooper

Step 8) In this example, the Message instruction is configured as follows:

The “Destination Element” Tag, “DLR_SUPV_DIAG,” is a SINT[54] data type: