PMU LSS CORE 3

INSTRUMENT CORE

CLASS CT CLASS 0.2

VA BURDEN 30

IPN THE RATED PRIMARY CT CURRENT 300

ISN THE RATED SECONDARY CT CURRENT 1

IPN : THE CT PRIMARY CURRENT 900

CONNECTED DEVICES BURDENS:

WATT/VAR TRANSDUCER : 0.1

CURRENT TRANSDUCER : 1.5

AMMETER : 1.2

LEAD LENGTH : 0.57

TOTAL : 3.37

HENCE THE PROPOSED BURDEN OF 30 VA IS GREATER THAN THE REQUIRED BURDEN OF


THEREFORE , THE CT IS SUITABLE FOR ITS INTENDED PURPOSE.
VA

VA

VA

VA

VA

VA #

E REQUIRED BURDEN OF 3.37 VA