DISASTER

MANAGEMENT AUDIT
REPORT

Gujarat Alkalies & Chemicals Ltd. TSM TheSafetyMaster Private Limited


Promoted by Govt. of Gujarat
S219-221, Sun Square, RIICO Industrial Area,
Plot D-II/9, P.O. Tal.- Vagra, Dahej,
Bhiwadi, Rajasthan, India 301019
Gujarat 392130, India. +91-1493-220093 info@thesafetymaster.com
Web: www.thesafetymaster.com
Plot 3

122
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM18027072020 Kalpataru Power (Padampur)
TABLE OF CONTENTS

1. Acknowledgement 04
2. Executive Summary 05
3. Acronyms 06
4. Glossary 07
5. Objective 10
6. Background 11
7. Project Detail 12
8. Team Detail 12
9. Assessment Methodology 13
10 Section 1 - Audit Sheet 14
11 Section 2 - Disaster Management Scenario 64
12. Section 3 – Disaster Management Team 87
13. Section 4 – Key recommendations 122

The Document is confidential. For internal use of GACL and


TheSafetyMaster only.
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Report Title DISASTER MANAGEMENT AUDIT

Gujarat Alkalies & Chemicals Ltd –


Client Name
Dahej Plant

Assessment Date 2nd – 5th December 2020

Report No. TSM22002122020

TSM Project No. TSM220-2020

Submitted to Mr. Pravinchandra Rana

Submission Date 17-12-2020

Prepared by Mr. Maruti Patil

Reviewed by Mr. Arvind Arya

Approved by Mr. Gangaram Jansari

TSM TheSafetyMasterTM Pvt Ltd


S 221 – 2nd floor, SPL 1/J, RIICO
Indus. Area, Bhiwadi-301019, India
Assessor Details Tel. +91-1493-220093,
+917665231743
Email: info@thesafetymaster.com
Web: www.thesafetymaster.com

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Acknowledgement

TheSafetyMasterTM Team is thankful to Gujarat Alkalies And Chemicals


Limited, Dahej, for providing an opportunity to undertake the Disaster
management Audit.

TSM TheSafetyMaster™ Private Limited would like to express sincere


gratitude to all HODs, Process people, Maintenance people, operators,
engineers, workmen, contractors, and house-keeping for their assistance,
services, coordination, and willingness to share their knowledge and experience
during the visit. We would also like to express our special thanks of gratitude to
Top Management & site team who gave us the opportunity to do the Disaster
management Audit. We would like to mention that without above coordination
the completion of this assessment would have been impossible. We are really
thankful to them.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Executive Summary

TSM- The Safety Master Pvt. Ltd has carried out disaster management audit at
Gujarat Alkalies and Chemicals Limited, Dahej. During the visit a detailed study of
on –site and off-site emergency plan has been carried out along with field visit of
each plant. The EHS system at GACL, Dahej has required infrastructure like very
much experienced team with adequate number of manpower, adequate
infrastructure, and availability of safety equipments / PPEs etc.
The documentation & their upkeep are very good. Onsite & off site emergency plans
are in details for sequence of actions to be taken during disaster / emergencies,
roles & responsibilities of individuals including the team designated to handle the
situations. These plans are periodically revised. EHS team understating the need of
expert’s opinion for review of disaster management plan, the assignment was given
to The Safety Master Pvt. Ltd. To visualize the possible scenarios & preparation of
handling with present existing system. As learnt GACL is providing emergency
handling services to nearby area on directives of local Disaster Management
Authority. This adds to the practical experience to handle the emergency situations.

The entire assignment was done at site by team with close coordination of GACL
team through documents checking, field visits, interacting / interviewing in person,
brain storming sessions & recording the outcomes. The areas where scope of
improvement was felt during assignment are placed at recommendations & should
be complied on priority.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Acronyms

ANSI American National Standard Institute


ASME American Society of Mechanical Engineers
CCPS Center for Chemical Process Safety
HAZOP Hazard and Operability (Study)
SWP Safe Work Practices
LOTO Lockout/Tag out
MSDS Material Safety Data Sheet
NFPA National Fire Protection Association
OSHA Occupational Safety and Health Administration
P&ID Piping and instrument diagram
PSM Process Safety Management
RAGAGEP Recognized and generally accepted good engineering practice
RBPS Risk Based Process Safety
OSHA Occupational Safety Health Administration
PSSR Prestart up Safety Review
MI Mechanical Integrity
PSI Process Safety Information
MOC Management of change
PHA Process Hazards Analysis
ERP Emergency Response Plan

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Glossary
Accident: An incident that results in significant human loss (either injury or death), significant
property damage, and/or a significant environmental impact.
Accountability: The obligation to explain and answer for one's actions that are related to
expectations, objectives, and goals. In this context, those that are accountable for PSM activities
are answerable to the one person who has the ultimate responsibility for the program. There may
be multiple persons accountable for an activity but only one person with the ultimate responsibility.
Accordingly, it is a powerful element of an effective process safety management system.
Asset integrity: A PSM program element involving work activities that help ensure that equipment
is properly designed, installed in accordance with specifications, and remains fit for purpose over its
life cycle.
Checklist A list of items requiring verification of completion; typically, a procedure format in which
each critical step is marked off (or otherwise acknowledged/verified) as it is performed. Checklists
are often appended to procedures that provide a more detailed description of each step, including
information regarding hazards, and a more complete description of the controls associated with the
hazards. Checklists are also used in conjunction with formal hazard evaluation techniques to ensure
thoroughness.
Consequence: The direct, undesirable result of an incident sequence usually involving a fire,
explosion, or release of toxic material. Consequence descriptions may be qualitative or quantitative
estimates of the effects of an accident in terms of factors such as health impacts, economic loss,
and environmental damage.
Controls: Engineered mechanisms and administrative policies/procedures implemented to prevent
or mitigate incidents.
Competency: A PSM program element associated with efforts to maintain, improve, and broaden
knowledge and expertise.
Determine: To conclude; to reach an opinion consequent to the observation of the fit of sample data
within the limit, range, or area associated with substantial conformance, accuracy, or other
predetermined standard; to obtain firsthand knowledge of.
Effectiveness: The combination of process safety management performance and process safety
management efficiency. An effective process safety management program produces the required
work products of sufficient quality while consuming the minimum amount of resources.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Hazard: Chemical or physical conditions that have the potential of causing harm to people, property,
or the environment. In these Guidelines, hazard refers to the first risk attribute: What can go wrong.
Hazardous chemical: A material that is toxic, reactive, or flammable and is capable of causing a
process safety incident, if released.
Hazard identification and risk assessment (HIRA): A collective term that encompasses all
activities involved in identifying hazards and evaluating risk at facilities, throughout their life cycle,
to make certain that risks to employees, the public, or the environment are consistently controlled
within the organization's risk tolerance.
Incident: An unplanned sequence of events with the potential for undesirable consequences.
Incident investigation: A systematic approach for determining the causes of an incident and
developing recommendations that address the causes to help prevent or mitigate future incidents.
See also Root cause analysis and apparent cause analysis.
ITPM program: A program that develops, maintains, monitors, and manages inspection, testing,
and preventive maintenance activities.
Life cycle: The stages that a physical process or a management system goes through as it
proceeds from birth to death. These stages include conception, design, deployment, acquisition,
operation, maintenance, decommissioning, and disposal.
Operator: An individual responsible for monitoring, controlling, and performing tasks as necessary
to accomplish the productive activities of a system. Operator is also used in a generic sense to
include people who perform a wide range of tasks (e.g., readings, calibration, incidental
maintenance, manage loading/unloading and storage of hazardous materials).
Procedures: Written step-by-step instructions and associated information (cautions, notes,
warnings) that describe how to safely perform a task.
Recognized and generally accepted good engineering practice (RAGAGEP): Legal,
consensus, or recommended practices with respect to design, construction, operations, and
maintenance of equipment. RAGAGEPs can take the form of labor regulation; consensus codes and
standards, recommended practices, and other guidance published and maintained by industry trade
and professional organizations; manufacturer's recommendations for design, installation,
operations, and maintenance; or guidance derived from the operating history of the equipment within
a given facility or the industry as a whole. RAGAGEPs used in the chemical/processing industry are
consensus industry codes, standards, and recommended practices. These codes and standards
define the level of acceptable practice within the industry for various technical and administrative
issues.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Risk: The combination of three attributes: what can go wrong, how bad could it be, and how often
might it happen.
Training: Practical instruction in job and task requirements and methods. Training may be provided
in a classroom or at the workplace, and its objective is to enable workers to meet some minimum
initial performance standards, to maintain their proficiency, or to qualify them for promotion to a more
demanding position.
Written program: A description of a management system that defines important aspects such as
purpose and scope, roles and responsibilities, tasks and procedures, necessary input information,
anticipated results and work products, personnel qualifications and training, activity triggers, desired
schedule and deadlines, necessary resources and tools, continuous improvement, management
review, and auditing.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Objective

The following are the objective of this Disaster management Audit:

Review of capability of the existing contingency/Emergency plan.

Review the existing emergency scenarios/events classification of plant safety

hazards and potential risk which could affect routine and non-routine operations at

plant, results in catastrophic events and activate emergency response.

Review and modify existing onsite emergency management plan and providing list of

improvement points and actions needed considering organizational, resource and

procedures aspects.

Review of emergency classifications

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Background

TSM TheSafetyMasterTM Private Limited


TheSafetyMaster™ is a young organization with a dedicated team of young, innovative, research

driven & experienced professionals, who want to create value for their customers by providing

ingenious services in the field of Safety.

Our Vision is to see TheSafetyMaster™ as a globally recognized Organization, delivering its

Services & Products through talented people and use of latest technologies with Safety, Efficiency,

and Quality & Values for its Customers, Partners & Society at large with the aim of “SAFER INDIA,

BETTER WORLD”.

Our Mission is to deliver Safety Services to our Customers with High Customer Satisfaction & priority

and making safety a priority for everyone

TheSafetyMaster™ Values

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Project Details

Gujarat Alkalies and Chemicals Limited.


Promoted by Govt. of Gujarat
Plot D-II/9, P.O. Tal. - Vagra, Dahej,
Gujarat 392130, India.

Team Details

1. Mr. Gangaram Jansari (Senior Consultant )

2. Mr. Arvind Arya (Senior consultant)

3. Mr. Maruti Patil (Assistant)

GACL Team?

Team detail is not necessary to include

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Assessment Methodology

Preparation-
 Selected Team members of TheSafetyMaster™

 Communicate needed facilities and engagement requirements

 Establish and agree schedule with GACL team

 Collect background information from plant team

Conducting Assessment-

 Opening meeting

 Develop understanding of a facility

 Collecting information

 Evaluating emergency management plan through document verification.

 Evaluating people capability in disaster management through discussions.

 Developing findings & provide risk rating and recommendations.

 Develop understanding of Fire Safety Management program.

 Evaluating fire safety inside the infrastructure through field visits.

Final Report Submission-

 Detailed report

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Section -1

Audit Sheet

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scope Elements Observation Evidence Details Recommendations

1.Emergency preparedness Following scenarios


chart ( Review capability of are not covered in
On Site Emergency Plan the existing contingency/ existing emergency SV1-155970 and SV-2- All the scenarios shall
Emergency plan response plan 155971 (liquid chlorine be covered in disaster
Classification of plant safety a) Catastrophic storage tank no. 24 T 01 management plan.
hazards and potential risk failure of A
chlorine bullet
which could affect routine b) Tonner leakage
and non-routine operations c) Overpressure or
explosion of
in plant) chlorine bullet or
tonner
d) Gasket joint
failure
e) Weld joint failure
f) Chlorine header
charging (filling)
rupture
g) overturning of
truck carrying
chlorine tonners
outside/inside
factory premise
h) Rupture of
tonner due to
non-
122
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM18027072020 Kalpataru Power (Padampur)
compatibility of
material
(chemical like
acetic acid) in
the tonner
i) Fire in amyl
alcohol.

j) Fire/Explosion in
hydrogen
service
k) Fire at HCL
plant
l) Land
contamination
due to HCL
storage tank
failure.
m) Liquid caustic
leakage
n) Dust explosion
in rock
phosphate
handling and
lime handling.
o) Threats due to
any catastrophic
failure in nearby
industry (SRF ,
GFL , Deepak
phenolics )
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
2. Safety valves are
installed on pressure
vessels and being
tested by competent
person but pop-up
and reseat pressure
is not being recorded
on the certificate.

2.Objective ,Scope and A legal register is Legal register is verified To move towards best
Legal Requirement of ERP being maintained during site visit. safety practices
and compliance is following points shall
being done on time be added such as
however there is a 1. The initiation date
Provide us
scope of sample format of concern document
improvement to shall be incorporated
move towards best before the expiry
safety practices. date.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
2.Validity date shall
Already written in
our format be written for each
license
3.Basis of the plan: Hazard QRA and HAZOP List of HAZOP and QRA It shall be ensured
analysis study of different study carried of plant that the
process have been wise is available recommendations of
conducted QRA and HAZOP are
complied
4. Statutory reports and 1. Stack and liquid Compliance status of Good practice to be
compliance for ERP effluent data are external safety audit maintained
online and duly carried in Nov-2019 is
connected to GPCB available.
and CPCB. Any
deviation is
communicated to
authorized person
through SMS alert
2. All other statutory
requirements are
being complied and

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
a legal register has
been maintained.
3. Safety audit is
being conducted
annually as per the
provisions of MSIHC
1989 by competent
person.
4.Recent audit has
been conducted in
the month of October
5. Safety report has
been updated and
submitted to the
concerned authority
in June 2018 as per
MSIHC rule 1989

5.Accident prevention 1. Records have Interaction with HOD


procedure/measures been maintained It shall be ensured
safety
at controller of
central control that periodic checking
room. There are
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
different of functioning of all
interlocks and
layers of protections
some plants are
on DCS like to the intended
H2O2 plant
design.
2. Multiple level of
protections exist
like seven layer
of protection in
chlorine system
and three layer
of protection in
oxidizer in H2O2

6.Accident/ Emergency Schedule for 1. The critical


Records checked during
response Periodic mock drills scenarios mentioned
site visit
procedure/measure is in place and are in the on-site
being conducted emergency plan must
accordingly. be covered in a
closed cycle manner.
2. Frequency of the
Mockdrill should be
defined. Tabulated
chart for the Mockdrill
scenarios and

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
education should be
maintained and
reviewed periodically
3. Scenario of
casualty handling
should be
incorporated
4. Mock drill should
be conducted other
than general shift
timings.

7.Recovery procedure Interaction with the Interaction with HSE Roles and
concerned HOD and team. responsibilities of
authorities was done individual should be
and it was observed ensured through

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
that they are not periodic surveillance
completely aware checking.
about their role as
per ERP in
systematic manner
8. Relevant information Last Off-site Off-site emergency plan Periodic mock drills
furbished to district emergency Mockdrill and Mockdrill conducted shall be ensured as
emergency authority for conducted in 2016 during site visit per guidelines in ERP
preparation of off-site and information has
emergency plan. been shared. On 4th
June 2020 on the
call of district
authority fire tender
was send outside for
help.
9. Site plan Location of Plant layout It shall be ensured
hazardous material that location of
is not mentioned in This is not feasible hazardous material
plant layout inventories ,central
control room

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
(ECC) ,OHC shall be
clearly marked
10. Charts and maps Charts indicating Interaction with HOD Charts and maps
indicating hazardous hazardous safety indicating hazardous
substances and zones substances are substances and
presently not zones shall be
available prepared.
11.Appointment of key Appointment of key Off-site emergency plan It is Good practice
personnel and their specific personnel and their updated in Oct 2019 and it shall be
duties laid out specific duties are updated periodically
well defined in off-
site emergency plan
along with their
address and contact
details

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
12 Emergency personnel’s Appointment of key Off-site emergency plan
responsibility during normal personnel and their update in Oct 2019 It shall be periodically
working hours specific duties during updated as and when
a) Site controller normal working need arises
b)Incident controller hours are well
c) Personnel/Administrative defined in off-site
Manager emergency plan
d) Communication officer along with their
e) Fire and security officer address and contact
f) Telephone operator details.
g)Departmental heads
h) Engineer in-charge and
electricians
I) Fire –pump attendant

13 Emergency personnel’s Appointment of key Off-site emergency plan It is good practice and
responsibility outside normal personnel and their update in Oct 2019 shall be maintained
working hours specific duties are

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
a) Shift executive in-charge well defined in off-
b) Fire and security officer site emergency in off
c) First-Aid
d) Factory fire brigade working
personnel hours/holidays with
their residential
address and contact
details.
14. Testing of emergency Schedule for Mockdrill records have 1. The critical
plan and Types of exercises Periodic mock drills been checked during scenarios mentioned
performed is in place and are visit in the on-site
being conducted emergency plan must
accordingly but the be covered in a
mock drills have closed cycle manner.
been conducted for 2. Frequency of the
fire scenarios only. Mockdrill should be
Other credible defined. Tabulated
scenarios mentioned chart for the Mockdrill
in the on-site scenarios and
emergency plan are education should be
yet to cover for maintained and
Mockdrill. reviewed periodically

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
3. Scenario of
casualty handling
should be
incorporated
4. Mock drill should
be conducted other
than general shift
timings.
5. Mock drills also be
conducted after
general shift hours to
check the emergency
preparedness
15.Responsibility ,frequency Evaluation of On-site emergency plan Good practice and it
and procedure for emergency plan is shall be continued
evaluation of emergency being done once in a
plan year or as and when
required due to some
major change (last
updated on 1st Oct-
2020).

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Responsibility for
evaluation and
updating is assigned
to HOD safety

16. Evacuation procedures Evacuation On-site emergency plan Good practice and
a) Before crisis procedure is being and training records shall be maintained
b)During crisis defined in onsite
c) After crisis emergency plan and
training has been
given for the plant
personnel
accordingly and
record is available.
17. Emergency plan for In warehouse 3 Site visit Secondary
warehouse and tank farm(s) (WH3) it was containment should
observed Iso-amyl be provided in
Alcohol is stored in warehouse.
drums but there is no Height of the sprinkler
should be re-

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
secondary considered to check
containment. the effectiveness of
Automatic water its working.
sprinkler system is Mandatory safety
installed but the signage and safety
height of sprinkler is instructions should be
very high. displayed in Hindi,
The main shutter of Gujarati and English.
the store is gear
operated due to
which emergency
response time may
get delayed.
Mandatory safety
signage and safety
instructions are not
displayed at the
gate.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
19.Emergency notification Emergency As per on-site Additionally for
and termination protocol notification and emergency plan continual
termination protocol (Page no.14) improvement current
has been defined in protection action
onsite emergency criteria like Acute
plan. Site main exposure guideline
controller in levels (AEGL)/
consultation with Emergency response
incident controller is planning guidelines
responsible for (ERPG) may be
notification and considered.
termination of
emergency

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
1. Site plan and Hazard Plant layout Marking should be
Hazardous area
Infrastructure identification chart done as per
classification and
hazardous area
marking of
classification in the
hazardous material
layout plan and
handled in the plant
should be
is not marked on the
communicated to all.
layout plan
Training in this regard
should be arranged.
Other hazards like
chemicals should also
be marked on layout
plan separately and
displayed.

2. Emergency control center CCR with adequate One dedicated landline Periodic checking and
phone with only testing of all
communication mode,
outgoing facility, one communication
CCTV screen,

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
computer, stock of hotline phone connected equipments shall be
PPE and BA set, list to 16 locations of the ensured.
of persons to be plant. One mobile
contacted in case of (ordinary) to connect to
emergency, periodic AMAI and toll free
checking of number 1800-11-1735
communication dedicated exclusively to
equipment and chemical emergency
availability of CCR countrywide are
officer round the clock available. One walkie
has been verified. talkie is also available.
All were verified during
CCR visit.

3. Assembly points Interaction with HOD Good practice and it


There are 14
safety and site visit of shall be continued
assembly points in
assembly points
the plant premises at
various locations. If
any of the assembly
point comes under
hazardous area, they
can go to alternate

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
assembly point and
training has been
given in this regard
and verified during
personal interaction.

4. Operational systems Battery drain test


Captive power
during emergency Interaction with HOD should be conducted
generation plant is
safety to ensure that it
available matching
meets the design time
with plant electrical
duration of backup
load.
power supply
Additionally diesel
Norms at which level
generator sets are
of battery backup
available as standby
duration ,action for
class three power
procurement of
supply to emergency
battery bank and level
electrical equipment.
of battery backup
UPS with battery
backup is available duration at which
battery bank must be
to meet the
replaced should be
requirement of
defined.
control

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
/instrumentation
systems

5. Communication system TSM team has Script of declaring


Siren tones for
a) Different types of alarms Performed observer’s emergency should be
declaring emergency
to differentiate types of
emergency role during emergency mentioned in the site
and calling off of
b) Alarm followed by Mockdrill. emergency plan on
emergency is
announcement over PA
c) Script for announcement similar lines to off-site
mentioned in the site
of emergency
d) Public address system
emergency plan ?? emergency plan

e) Walkie-Talkie indicating cause of


Script of declaration
f) Standby communication emergency and
of emergency is
system in case of failure
of alarm location of
mentioned in the off-
emergency.
site emergency plan
Schedule for periodic
but missing in site
checking of
emergency plan.
effectiveness of the
PA system is
PA system should be
available for
announcing the prepared and
enforced.
incident spot and
scenario

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Eight number of
Walkie-talkie are
available with
fire/safety and
thirteen numbers are
available with
security apart from
one available at
CCR.
Two number of base
unit of walkie talkie
are placed at visitors/
material gate
Portable PA system
is available with
security as well as
fire to communicate
locally at incident site
and same was
verified during

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Mockdrill conducted
on 4th Dec
Announcement on
PA system was not
clearly audible while
declaring
emergency.

6. Public information system Off-site emergency plan Offsite emergency


Periodic awareness
a) Before the crisis exercise may be
program for nearby
b) During the crisis
c) After the crisis considered with the
villagers and industry
scenario of
are being conducted
evacuation of nearby
to educate them
villages and industry
about the hazard and
to ensure
precautionary
preparedness before
measures to be
the crises ,during the
taken by them in
case of release. Also crises and after the
crises
to educate about
requirement of
emergency

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
evacuation and
securing their
immovable
properties during
emergency.

7. Warning system and Existing fire Interaction with HOD Since fire detection
control centers location detection system is safety system provides
very old and job of accurate location and
revamping/ fastest
modernization is in communication of fire
hand at very early stage
thus it must be
implemented on
highest priority

8. Adequate number of One dedicated Verified during site visit Good practice and it
external and internal landline phone with shall be continued
telephone connections
only outgoing facility,
one hotline phone
connected to 16
locations of the plant.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
One mobile
(ordinary) to connect
to AMAI and toll free
number 1800-11-
1735 dedicated
exclusively to
chemical emergency
countrywide are
available. One walkie
talkie is also
available. All were
verified during CCR
visit.

Real time data available


1.Fire-fighting facilities There are 47 trained
on intranet Good practice and it
fire wardens in
Emergency Services shall be maintained
different plants and
periodic training has
been provided.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
OHC document
2. First-Aid and rescue 100 trained first
aiders are available
round the clock and
one CIH doctor along
with male nurse is
present at site.
On-site emergency plan
3. Alternate source of power Five fire water
supply for operating fire and inter action with
pumps are diesel
pumps HSE HOD and team
engine driven pumps
apart from this
electrical motor
driven pumps have
facility to run on
standby power
supply that is diesel
generator (class-III
power supply)
Good practice and it
4.Communication with local
bodies , fire brigade shall be continued

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Mutual aid scheme
Mutual aid scheme is agreement
in place. Hot line
communication
through central
mutual aid control
room

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
1. Written procedure which Mutual-aid group
explains how call for help
exist among eight
will be made
industries within
Good practice and it
distance of 15 km.
shall be continued
Agreement has been
signed by all the
Mutual Aid members of mutual-
Mutual aid agreement
aid scheme on
stamp paper for
acceptance of terms
and conditions.

2. Type of equipment which It is agreed among


would be used and
the members to use
procedure for making
replacement available resources
and return back the
consumables foam,
powder etc. with
same specification
and quality or
reimburse as per
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
purchase order of
helping industries.

3. Quick hot-line method of Good practice and it


Dedicated hot-line
communication shall be continued
communication is
available with the
Verified during site visit
member industries
also contact number
of direct telephone
line at fire station is
shared in the
agreement. Periodic
checking of
communication is
being done and
records are
maintained. Records
have been verified
physically. Dedicated
CCR officer is
available round the
clock at site CCR

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
4. A brief mention of the type Type of hazard in the Off-site emergency plan Good practice and it
of hazard in each plant and shall be continued
plant ,at mutual aid
fire-fighting measures
scheme member
group industries and
nearby industries are
mentioned in the
offsite emergency
plan

5. Orientation and joint Mockdrill observed on Good practice and it


Joint training
training programme for 4th Dec. shall be continued
programs/meetings
staff
are being conducted
regular basis.
Additionally Gujarat
state disaster
management
authority with
infrastructure and
equipment is
available nearby and
it was observed
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
during Mockdrill on
4th Dec that GSDMA
fire tender reached
the incident site in
less than 10 min of
time on getting
intimation.

6. Joint inspections and drills Mutual –aid agreement Good practice and it
Designated team
shall be maintained
with name,
designation of
person and his
alternate are
mentioned in the
mutual –aid
agreement. Periodic
inspections and drills
are carried out and
records are
maintained.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
1. Poison control centers 1. CIH doctor and
2. Poison control program
qualified male nurse
3. Adequate material and
information on preventive Good practice and it
are available round
measures of how to avoid OHC document and visit shall be continued
the clock at OHC
acute poisoning
4. Stocking of anti-dotes and to OHC
2. Stocks of
Medical Facilities special medicines for
necessary
hazardous substances
5. First –aid post emergency
6. Occupational health center
medicines are
7. Base Hospital
8. Specialized training of maintained at OHC.
doctors relating to
3.Schedule for
chemical hazards
9. Blood grouping of all periodic checking of
employees working in plant
stock of medicine
10. Maintenance of list of
blood donors group wise and their expiry date
11. Buffer stock of essential
is in place and
medicines
12. Planning of additional records are
capacity in the base
maintained
hospital for large –scale
victims. 4. Empaneled
13. Training provided
hospitals and other
hospitals are

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
available at Dahej to
meet emergency
situations.
5. Six beds are
available at OHC.
6. Blood group of all
employees working
in the plant is
available and list of
group wise blood
donors is also
available.
7. First –aid box are
placed at designated
location in the plant
and stock of material
kept in the first-aid
box are checked and
maintained
periodically.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
8. Eight number of
ambulances from
mutual-aid group are
available round the
clock.

1. Compliance with existing Interview with Mr. Siraj All necessary check
Drivers of the truck
Emergencies arising during legal provisions like Bhai driver of (GJ 16 Z as per SOP of tonner
transporting chlorine
a) Correct technical name
transportation of hazardous b) Class label, HAZCHEM 5136 ) truck loading shall be
tonners were
goods No. followed religiously
interviewed and it
c) Names and telephone
Nos. of the emergency Interview with Mr. Paul supported by
was observed that
services and the cosigner Rodrigues checklist and record
driver not able to
etc.
shall be maintained.
read the instructions
2 All lifting tools and
given in the TREM
tackles must be
card in any of the
checked periodically
language.
at the beginning of
Instructions on the
shift.
TREM card is
available in
Hindi ,English and
Gujarati
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
2 Fire extinguisher
available in the truck
was found empty
and discharge hose
was damaged
3.First-aid box was
not available in the
truck.
4. Driver has valid
training certificate for
the transportation of
hazardous goods as
per central motor
vehicle rule
5. Driver was not
aware about the
action to be taken in
case of toppling of
the chlorine truck
5.Floor of the tonner
Loading area in the

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
truck was damaged
and there was
opening on the floor
6. Senior operator
responsible for
loading of tonners
has not checked
validity of certificate;
also he was not
aware of what kind of
emergency will occur
in toppling of the
loaded truck outside
the plant.
7. Lifting Hook of
chain sling to lift the
tonner was found
deep undercut at
root area also the
chain link was found
thin to the level of

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
about 50% which
may result in major
accident.

2. Transport emergency plan 1.Transport Off-site emergency plan Good practice and it
available emergency plan is shall be continued
a) Chemicals transported
b) Quantity transported available and
c) Routes on which mentioned in the off-
transported
d) Likely points where site emergency plan
accidents could occur 2.AMAI arrangement
enroute
e) Past accident records with toll free number
and possible cause of to arrange rescue
accidents
team from nearby
available resources
f) Chemicals involved in
accident is available- (1800-
g) Existing safety status 11-1735)
and preparation to
combat an emergency 3. Record of past
h) Notification of accident accident of transport
i) Fire response
j) Level of protection emergency is
k) Health care available at site (one
l) Protective action
m) Spill containment and case of toppling of
monitoring chlorine tonner truck

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
n) Spill recovery and and subsequent fire
clean up
in the diesel of the
o) Waste disposal
truck resulting in
explosion in tonner-
no casualty or effect
to public).Another
incident of fire in
hydrogen batteries in
city area no
human/property
damage as
emergency response
was managed in
time.
4. GACL provides
services to nearby
area for
fire/explosion or
other emergency as
and when

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
sought by district
authorities this
ensures adequate
practical experience
of handling the
actual emergency
5 Arrangement of
standby tractor
trolley, neutralizing
chemicals and
workforce are
available at
warehouse.
6 Fire response team
is available to
contain ,recover and
cleanup and safe
disposal of waste

3. Driver sufficiently aware of Driver is not Interview with Mr. Siraj All the requirement of
the hazards posed by Bhai driver of (GJ 16 Z transporting
sufficiently aware of
goods transported
5136 ) truck hazardous materials
the hazards posed

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
by goods including TREM card
transported. should be verified
during his first entry in
the plant and during
subsequent entry
validity of hazardous
material transport
training should be
verified.
The above
recommendations are
in addition to existing
checklist.

4. All instructions relevant for TREM card is Field visit Good practice and it
safe transportation and shall be continued
available with driver
meeting of situations
arising from any incident and Instructions on
are available in writing.
the TREM card are
available in Hindi,
English and Gujarati.
Detailed description of the 1. Process description IMS documents and on- Good practice and it
Detailed description
plant and activities carried out 2. Routine activities site emergency plan. shall be continued
of the plant and
3. Non-routine activities
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
4. Shut-down activities activities are verified
5. Start-up activities
in IMS and on-site
emergency plan

Education , 1. Training records Valid training Field interview with Mr. Other than person
training and awareness 2. Topics covered certificate are Hardik Patel and Mr. required for
3. Audience covered
4. Frequency of training available with Piyush Patel of emergency help
5. Method(s) to check vehicle/driver while mechanical were should not enter in
effectiveness of training
6. Who conducts training interviewing in the standing as visitor hazardous/
field it was found that during emergency High risk area.
effectiveness of the Mockdrill at incident site. Effectiveness of
training is not to the training program shall
desired level. be ensured periodically
Category wise through one to one
training program are interaction during
being conducted routine safety
periodically through surveillance rounds in
in-house as well as the field.
external faculty.
Training has been
conducted by HR as

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
well by HSE
department. Records
of training are
available on
computer.
Access and Egress 1. Proper Emergency exit Field visit Emergency exit
The emergency exit
2. Emergency lights routes and alternate
routes are marked
3. Exit signage
4. Emergency power emergency exit route
on the site layout
supply must be marked on
plan but not marked
the pathway.
on the walkway path
Separate pathways
may be due to
for vehicle and
construction activity
pedestrian must be
marked on the road.
Inventory of risk in the plant 1. Quantity (Static and Off-site and on-site Good practice and it
Inventory of all the
which may cause emergency. dynamic inventory) emergency plan shall be continued
hazardous material
2. Storage
3. Transportation which can cause
4. Handling
emergency are
mentioned in the
site/ off-site
emergency plan

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
ERP safety audits and 1. Frequency of audits Compliance status of Good practice and it
External safety audit
reviews 2. Scope of Audit external audit has been shall be continued
is carried out yearly
3. Audits carried internally or
externally shared.
by competent
4. Action points implemented
person.

1. Public transportation network Interaction with HOD Details of pipeline


Responsibility for
2. Traffic load and connecting safety. network carrying toxic
monitoring upcoming
road with industries and rail
Geographic information network and flammable
hazardous industries
3. Details of pipeline network material and their
in close vicinity has
carrying flammable and toxic
material storage inventory
not been assigned
4. Land use plan in the vicinity must be marked on
at present. Details of
of hazardous industry
5. Water supply layout plan.
pipeline network
6. Hazards of nearby industries System to
carrying flammable
if any
You are requested to communicate all the
and toxic material guide us for recommendation
industries in SEZ area
are not marked in
needs to be
plant layout.
developed for any
Data of public
change in existing
transport network
plant hazards or
traffic load are not
available with the hazard due to any
upcoming plant in
plant.
similar lines like

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
environmental
clearance and public
hearing to understand
any new hazard
coming in the area
and which require
preparation to meet in
any emergency
situation due to their
new hazard.
Responsible person
to make
communication in this
regard should be
identified and
assigned the
responsibility.
Data of public
transport network
traffic load should be
obtained periodically

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
from state
government transport
department to
understand the kind
of preparation
required during
emergency.

Review of emergency Level I Emergency Emergencies are On-site emergency plan. The basis of declaring
classifications Level II Emergency classified based on emergency should be
Level III Emergency affected area but not based on quantified
quantified for toxic values and in case of
releases. You have to identify and give GACL it should be for
us details qty for the same based on
our process data. chlorine accordingly
concentration of
chlorine ppm at which
emergency should be
declared needs to be
fixed for all the
scenarios of Level

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
I/II/III and basis can
be AEGL -1/2/3.

Other emergencies 1. Storm Periodic mock drills Schedule for periodic


All the emergencies
2. Earthquake have been conducted Mockdrill for other
mentioned are
3. Lightning
4. Terrorism for other scenarios. emergencies should
covered in onsite as
5. Sabotage be prepared and
well off-site
6. Air attack
enforced.
emergency plan
Maintenance and review Verified during field visit Good practice and
- A maintenance
programs for resources shall be continued.
arrangement for
(emergency control center) emergency is being
used to handle emergencies done through
and other strategic or schedule periodic
essential services. checking and
records are
maintained in
computer.
Integration of the ERP with Both documents Good practice and
IMS procedures. were reviewed in shall be continued.
view of IMS section
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Both documents will be 7.4 (communication). IMS documents and on-
reviewed and checked that Section 8.2 site emergency plan
all points have been (emergency
covered. preparedness )are
found in order

Business continuity aspect 1.Public liability insurance PLI policy is Policy number- Adequacy of total
2. Rehabilitation program available and it is 160132027120000002 insured amount (15
valid up to 31st crore) needs to be

Crore spell
March 2021.The Off-site emergency plan. verified/
correction value covered is 5 reviewed
core for one accident
and 15 core in a
year
Post emergency
restoration is

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
mentioned at page
no. 95 of off-site
emergency plan.
Integrated incident command - Integrated incident Onsite /off-site Integrated incident
structure and communication command structure emergency plan command structure
flow with communication and communication and communication
facility. flow with flow with
communication communication facility
facility are well should be ensured
defined in the on- during Mockdrill in the
site/off-site same chronological
emergency plan order as mentioned in
the plan.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Coordination of the plant - Coordination of the On-site/ off-site Training/periodic
emergency plan with the plant plant emergency emergency plan retraining should be
security plan plan with the plant arranged for security
security plan is well department with
defined in respect to the roles
emergency plan. and responsibilities
During field visit at during emergency as
material gate on 4th defined in the on-site
Dec at 15:45 pm the Field interview emergency plan.
Particular
name avoided. on duty security Effectiveness of the
officer Mr. L.M. training should be
Rosewal. It was ensured through
observed that he is periodic surveillance
not aware of his rounds/internal safety
roles and audit
responsibilities
during emergency
also any document
(on-site emergency
plan) available in this
regard. He was also

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
not aware of actions
to be taken in event
of receiving inputs
from intelligence
department.
Examples of possible - -
- Scenarios which can
emergency scenario which lead to disaster and
can lead to disaster not covered in the
existing disaster
a)Emergency arising from plan. are being
accident to any personnel covered separately
within plant area in detail in
b)Personnel entrapment or consultation with
rescue HSE HOD and team.
c)Emergency due to fire (plant
building ,offices ,
warehouse ,loading/unloading
bay ,stored or stacked
dangerous goods ,electrical
substation)

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
d)Vehicle accidents in plant
area and road during
transportation of hazardous
goods
e)Loss of containments of
dangerous goods
(fire ,explosion ,leakage ,gas
release ,flammable or toxic
cloud)
f)Emergencies from severe
weather conditions and
geological hazards
g)Emergencies from mass
casualty incident
h)Emergencies from health
epidemic
i)Other emergencies

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Section-2

Disaster management scenario

122
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM18027072020 Kalpataru Power (Padampur)
Scenarios which can lead to disaster and not covered in the existing disaster plan are being
covered in detail in consultation with HSE HOD
Scenario: Fire in amyl alcohol

Location 1. Phosphoric acid plant


2. Dedicated Storage amyl alcohol in drums
When It can happen any time but the probability of the incident is more in
odd hours. (After general shift)
Why  Due to short circuit
 Accumulation of static charge
 Incompatibility of material stored along with it
 Mishandling of drum due to which rupture or leak of the drum
may occur
 Storage condition (temperature)
 Hot work in nearby area
 Material handling by unskilled person
Likelihood 2
Severity 4.5
Risk (Likelihood * 9
Severity )
Risk Level Medium
Emergency Level Level I
Consequence In event of fall of four drum loaded pallet the leaked/escaped iso-
amyl alcohol may form pool and on getting ignition source there
can be explosion in the vapors and pool fire in the liquid. The pool
fire may further lead to heating of nearby drums (24 KL stored in
the area) and can lead to BLEVE. The impact of explosion may
injure persons in the nearby vicinity of store. In case of leak from
flange or weld joint in the plant area a pool of iso-amyl alcohol will
be formed ,since the flash point is 32.7 0C and in summer when
ambient temperature is crossing 40 0C (which is likely in the area)
it may form vapor cloud and can result in explosion on getting
ignition source which can injure workforce in the nearby area.
 Dedicated storage is available for amyl alcohol
 Entry is restricted in the store
Site Preparedness  Electrical fittings inside the storage are flameproof
level  Fire deluge system is in place and revamping work of the same
is in hand
 Spark arrestors are installed on the vehicles moving in this
area
 Internal audit by company and external audit by competent
person are being done by periodically
 Double Earthing is being used while transferring the material
from the drum
 Foam type fire-extinguishers are available
 Foam solution is also available in 20 lit containers along with
portable foam monitor in nearby area
 Storage area is well ventilated
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
 Provision to pour fire water from outside without opening the
main shutter is also available in the form of glass windows
 Spill collection pit is also available inside the storage

Adequacy of  Surveillance round the clock


firefighting  CCTV camera is installed outside the storage area
equipment  Two fire tenders are available
 Fire hydrant network is available with two set of fire water
storage tanks and fire water pump house which ensures
availability of complete unit as standby. Each pump house
have jockey pumps and two diesel engine driven and two
electrical motor driven pumps (273 m3/hr. at 8.8 kg/cm2
pressure). Electrical motor driven fire pumps have alternate
standby power supply from DG sets.
 Dedicated fire water storage of 6700 m3 and connected with
GIDC inlet water supply

Team  47 trained fire wardens are available other than fire staff.
preparedness  100 trained first-aiders are available at site.
 Data of first-aiders and fire wardens is available on intranet.
 Refresher training for first-aiders and fire fighters is being
carried out periodically.
 Fire team (regular staff) is available round the clock.
Ways to mitigate  On detection of fire communication is to be made to central
the scenario control room (CCR) which further communicates to site in-
charge and resources are mobilized based on the situation
from the existing resources mentioned above. This includes
use of siren if needed.
 Help from mutual-aid can also be sought

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Fire at HCL Plant

Location HCL synthesis

When Lightning during thunderstorm


Why Hydrogen is put at slightly higher quantity to ensure complete
combustion of chlorine gas and this excess (very less) is getting
released through stack.
Likelihood 4
Severity 3
Risk (Likelihood * 12
Severity )
Risk Level Medium
Emergency Level Level I
Consequence  Explosion may occur resulting in human injuries/fatality,
damage to nearby equipment in the blast zone.
 Provision of nitrogen and steam purging is made to minimize
Site Preparedness the probability of fire.
level  SOP is in place.
 Detector is installed at stack which is integrated with alarm
and action to stop hydrogen on appearance of alarm is in
place.
Adequacy of  To limit the metal temperature of the flame affected area fire
firefighting hydrant system can be used and fire staff is trained to deal with
equipment hydrogen fire accordingly.
Team •47 trained fire wardens are available other than fire staff.
preparedness •100 trained first-aiders are available at site.
•Data of first-aiders and fire wardens is available on intranet.
•Refresher training for first-aiders and fire fighters is being carried
out periodically.
•Fire team (regular staff) is available round the clock.
Ways to mitigate  Provision has been made for steam and nitrogen purging
the scenario  Flow of hydrogen will be stopped upon getting alarm
 Fire hydrant system can be used to limit the metal temperature
of flame affected area.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Land contamination due to escape of corrosive substance from system and
spilled on floor/soil
Me
ntion name
Location Tank farm area and plant area ( in different plants) of chemicals
eg HCl, NaOH,
When  In the event of failure of gasket and puncture in the pipeline
H2SO4
 Catastrophic failure of storage tank (100 KL )
 Leakage from road tanker/toppling of tanker (within plant or
outside plant)
Why  Aging of gasket
More reason
 Corrosion/ aging in pipeline to be updated
Likelihood 3
Severity 3
Risk (Likelihood * 9
Severity )
Risk Level Medium Level II only
Emergency Level Level II or Level III
Consequence  Spillage on floor will make the surface slippery and the
situation will not only lead to injury but also chemical burns,
HCL fumes liberated in the atmosphere and will move in
downwind direction making situation uncomfortable to breath.
Apart from this soil contamination may affect the ecosystem
and ground water of surrounding area. In case of catastrophic
failure of storage tank the corrosive substance may spill in the
area beyond dyke and may lead to burn injuries workforce
passing/working in nearby area.
 In case of spillage on road (beyond plant boundary it may lead
to chemical exposure/burn to the people within vicinity )

 Adequate quantity of neutralizing agents is available at plant


Site Preparedness  Dyke wall with collection pits are provided around the storage
level tanks and from pit through pump it can be transferred to ETP.
 Spill control system is in place with alternate contingency
arrangement.
 Arrangement of standby tractor trolley, neutralizing chemicals
and workforce are available at warehouse.
Adequacy of  Fire staff services are available for mitigation round the clock
firefighting and plant personnel are also trained for the same.
equipment
Team •47 trained fire wardens are available other than fire staff.
preparedness •100 trained first-aiders are available at site.
•Data of first-aiders and fire wardens is available on intranet (real
time)
•Refresher training for first-aiders and fire fighters is being carried
out periodically.
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
•Fire team (regular staff) is available round the clock.
 GACL provides services to nearby area for chemical spillage or
other emergency as and when sought by district authorities this
ensures adequate practical experience of handling the
emergency
 Arrangement of transfer pump and spare tanker is also listed
and can be arranged on short notice.
Ways to mitigate  Neutralizing agents will be used and services of fire staff will be
the scenario taken for mitigation if needed.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Liquid caustic leakage

Location  Plant area (CSP)


 Tank farm area
 Tanker loading area
 Outside the plant (tanker toppling)
When •In the event of failure of gasket and puncture in the pipeline
•Catastrophic failure of storage tank (1000 m3 )
•Leakage from road tanker/toppling of tanker (within plant or
outside plant)
Why •Aging of gasket
•Corrosion/ aging in pipeline
Likelihood 2
Severity 4.5
Risk (Likelihood * 9
Severity ) Level II only
Risk Level Medium
Emergency Level Level II or Level III
Consequence • Spillage on floor will make the surface slippery and the
situation will not only lead to injury but also chemical burns.
Apart from this soil contamination may affect the ecosystem
and ground water of surrounding area. In case of catastrophic
failure of storage tank the corrosive substance may spill in the
area beyond dyke and may lead to burn injuries workforce
passing/working in nearby area.
• In case of spillage on road (beyond plant boundary it may
lead to chemical exposure/burn to the people within vicinity
• Adequate quantity of neutralizing agents is available at
Site Preparedness plant
level • Dyke wall with collection pits are provided around the
storage tanks and from pit through pump it can be transferred
to ETP.
• Spill control system is in place with alternate contingency
arrangement.
• Arrangement of standby tractor trolley, neutralizing
chemicals and workforce are available at warehouse.
Adequacy of •Fire staff services are available for mitigation round the clock and
firefighting plant personnel are also trained for the same.
equipment
Team •47 trained fire wardens are available other than fire staff.
preparedness •100 trained first-aiders are available at site.
•Data of first-aiders and fire wardens is available on intranet (real
time)
•Refresher training for first-aiders and fire fighters is being carried
out periodically.
 Fire team (regular staff) is available round the clock.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
•GACL provides services to nearby area for chemical spillage or
other emergency as and when sought by district authorities this
ensures adequate practical experience of handling the emergency

•Arrangement of transfer pump and spare tanker is also listed and


can be arranged on short notice.

Ways to mitigate •Neutralizing agents will be used and services of fire staff will be
the scenario taken for mitigation if needed.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Dust explosion in rock phosphate and lime handling unit
Bullets
Location  Unloading and charging area to be removed
When •During charging or unloading operation from all single
points
Why • Bulk storage of rock phosphate and frequent handling of lime

Likelihood 3
Severity 4
Risk (Likelihood * 12
Shock wave
Severity ) to be
Risk Level Medium discussed
Emergency Level Level II
Consequence  Shock wave generated during dust explosion will severely
damage equipments, structure, within the blast radius. This
may further escalate the situation because of secondary effects
such as fire ,severe human injury/fatalities
 Identification of potential dust explosion risk are assessed in
Site Preparedness QRA study and mitigations, measures have been planned and
level are in place in on-site emergency plan.
Adequacy of •Fire staff services are available for mitigation of secondary effect
firefighting of dust explosion round the clock and plant personnel are also
equipment trained for the same.
 Two fire tenders are available
 Fire hydrant network is available with two set of fire water
storage tanks and fire water pump house which ensures
availability of complete unit as standby. Each pump house
have jockey pumps and two diesel engine driven and two
electrical motor driven pumps (273 m3/hr. at 8.8 kg/cm2
pressure ). Electrical motor driven fire pumps have alternate
standby power supply from DG sets.
 Dedicated fire water storage of 6700 m3 and connected with
GIDC inlet water supply

Team  One CIH doctor along with male nurse ,Five beds, adequate
preparedness emergency medicines/equipment and One ambulance are
available at OHC
 Eight numbers of ambulances apart from GACL are available
within mutual aid group.
 Services of emergency ambulance is available at 108 phone
number
•47 trained fire wardens are available other than fire staff.
•100 trained first-aiders are available at site.
•Data of first-aiders and fire wardens is available on intranet (real
time)
•Refresher training for first-aiders and fire fighters is being carried
out periodically.
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
 Adequate numbers of hospitals including empaneled hospitals
are available as tabulated at table 22: Medical aid information
at page no. 57 of off-site emergency plan.
 Transport and evacuation arrangement exist at annexure-22 at
page no. 105 of on-site emergency plan.
 GACL provides services to nearby area for fire/explosion or
other emergency as and when sought by district authorities this
ensures adequate practical experience of handling the actual
emergency

Ways to mitigate •Apart from availability of resources mentioned in the team


the scenario preparedness column other rescue/recovery resources like heavy
vehicles ,earth moving equipments like hydra ,crane, forklifts are
available at site as mentioned in Annexure -24 on page no. 111 in
the on-site emergency plan.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Natural Calamity – Flood/cyclone/earthquake

Location  Anywhere in entire Plant Area


When •Extreme weather conditions for flood/cyclone but earthquake is
not predictable

Why •The intensity of flood/cyclone has crossed the base parameters of


facility siting and designed parameters.

Likelihood 4 - Not exactly predictable but pre warning provision exist through
meteorological department in their periodic forecast but again
cannot be predicted for earthquake
Severity 4
Risk (Likelihood * 16 Level II also
Severity ) tobe added
Risk Level High
Emergency Level Level III
Consequence Mass casualty /fatality, damage to plant
equipment/building/structure linked with secondary effect of
release of hazardous chemicals (liquid/gaseous) and effect may
go beyond plant boundaries.

 Necessary precautionary arrangements are made on receipt of


Site Preparedness forecast warning issued by meteorological department to
level manage the situation of flood/cyclone
 Provision of plant emergency shutdown in case of extreme
condition is in place with consultation of plant head.
 Pool of emergency manpower is made available on receiving
pre warning from meteorological department.

Adequacy of •Fire staff services are available for mitigation of secondary effect
firefighting/rescue of earthquake round the clock and plant personnel are also trained
equipment for the same.
Team •47 trained fire wardens are available other than fire staff.
preparedness •100 trained first-aiders are available at site.
•Data of first-aiders and fire wardens is available on intranet (real
time)
•Refresher training for first-aiders and fire fighters is being carried
out periodically.
 Fire team (regular staff) is available round the clock.
 Pre -monsoon checks are in place.
 Highest flood level of past history is marked on the plant
location
 Off-site emergency plan is in place and preparedness is
assessed periodically through mock drills.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
 Public awareness program to nearby industries and villages
are conducted. (14 villages already covered and others are in
pipeline)
 Mutual-aid scheme is in place
•Adequate numbers of hospitals including empaneled hospitals
are available as tabulated at table 22: Medical aid information at
page no. 57 of off-site emergency plan.
•Transport and evacuation arrangement exist at annexure-22 at
page no. 105 of on-site emergency plan.

Ways to mitigate •Adequate number of de-watering pumps are available for flood
the scenario like situation.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Fire and explosion in hydrogen service

Location  Cell house


 HCL synthesis
 Storage (deoxo)
 Hydrogen filling/dispatch
 Toppling of truck during transportation within plant or beyond
plant boundary
When • In case of leakage from piping/tubing joints ,battery of cylinders
of hydrogen
 On getting ignition source including hot surface

Why • Due to accumulation of static charge


• Inter connected tube leakage of battery of cylinder
• Due to road accident
Likelihood 3
Severity 4
Risk (Likelihood * 12 Level III to be
Severity ) added in case of
Toppling of truck Risk level
Emergency Level Level II medium and
Risk Level Medium high

Consequence • Fire /explosion


• Shock wave generated during explosion will severely damage
equipments, structure, within the blast radius. This may further
escalate the situation because of secondary effects such as
fire ,severe human injury/fatalities
 Hydrogen detectors are in place
Site Preparedness  SOP is in place
level  Fogging system of water is in place at hydrogen battery filling
area
 Alarm and interlock to trip to bring the plant in safe condition is
in place
 Specific training to handle hydrogen fire is arranged
periodically
 TREM card is in place for road transportation

Adequacy of • Fire staff services are available for mitigation of explosion round
firefighting/rescue the clock and plant personnel are also trained for the same.
equipment •Two fire tenders are available
•Fire hydrant network is available with two set of fire water storage
tanks and fire water pump house which ensures availability of
complete unit as standby. Each pump house have jockey pumps
and two diesel engine driven and two electrical motor driven
pumps (273 m3/hr. at 8.8 kg/cm2 pressure). Electrical motor
driven fire pumps have alternate standby power supply from DG
sets.
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
•Dedicated fire water storage of 6700 m3 and connected with
GIDC inlet water supply
Team •47 trained fire wardens are available other than fire staff.
preparedness •100 trained first-aiders are available at site.
•Data of first-aiders and fire wardens is available on intranet (real
time)
•Refresher training for first-aiders and fire fighters is being carried
out periodically.
•Fire team (regular staff) is available round the clock

Ways to mitigate •Periodic mock drills on various fire scenario are being conducted
the scenario periodically

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Accident of bus on the way from plant to colony

Location  Anywhere between Dahej plant and Bharuch


When • while transporting employees from Dahej plant to Bharuch or vice
versa

Why  Mistake of other vehicle running on the road


 Unsafe driving of the driver
 Unfavorable weather conditions (raining ,fogging ,night hours)
 Defective vehicle
 Intoxication (Alcohol)
 Poor road condition
Likelihood 3
Severity 4
Risk (Likelihood * 12
Severity )
Emergency Level Level II
Risk Level Medium
Consequence Mass casualties/fatality

 Instructions to drive safely during adverse weather conditions


Site Preparedness are in place.
level  Alcohol breath testing equipment is available at site
 Periodic inspection of vehicle ensuring safety aspect in the bus
operation control is incorporated
Adequacy of •In case of fire in the vehicle ,plant fire tender is available to
firefighting/rescue mitigate the situation
equipment
Team •Adequate numbers of hospitals including empaneled hospitals are
preparedness available as tabulated at table 22: Medical aid information at page
no. 57 of off-site emergency plan.
•Transport and evacuation arrangement exist at annexure-22 at
page no. 105 of on-site emergency plan.
 A service of ambulance at 108 numbers is available.

Ways to mitigate  CCR is available round the clock to receive information in such
the scenario case and contact number of CCR is available with employees.
 A service of ambulance at 108 number is available.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Overturning of truck filled with chlorine tonner

Location  Anywhere within plant or on public road while transportation


When • while transporting tonner within plant or on public road

Why  Mistake of other vehicle running on the road


 Poor road condition
 Unsafe driving of the driver
 Unfavorable weather conditions (raining ,fogging ,night hours)
 Defective vehicle
 Intoxication (Alcohol)

Likelihood 3
Severity 4
Risk (Likelihood * 12
Severity )
Emergency Level Level III
Risk Level Medium
Consequence  On toppling of vehicle fire may take place due to leakage in
fuel (diesel line of vehicle) and heat of fire may lead to over
pressurization/rupture of tonners. In case of rupture of tonner
chlorine will escape to local area and effect local public.
 Tonner valve can also get damage and can result in leakage of
chlorine to local area and effect the local population.

 Instructions to drive safely during adverse weather conditions


Site Preparedness are in place.
level  TREM card is provided
 Driver’s training as per motor vehicle act and checking of
license at site is being done through SOP
 Emergency response team is available at site.
 AMAI arrangement with toll free number to arrange rescue
team from nearby available resources is available- (1800-11-
1735)
 Alcohol breath testing equipment is available at site

Adequacy of •In case of fire in the vehicle ,plant fire tender is available to
firefighting/rescue mitigate the situation
equipment
Team •Resources like heavy vehicles ,earth moving equipments like
preparedness hydra ,crane, forklifts are available at site as mentioned in
Annexure -24 on page no. 111 in the on-site emergency plan.
•Services of ambulance at 108 number is available
 Emergency contact details are available in TREM card

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Ways to mitigate  CCR is available round the clock to receive information in such
the scenario case and contact number of CCR is available with employees.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Leakage of chlorine and hydrogen outside the plant

Location  Anywhere from plant to Shivapharmachem beyond plant instead of


premises company name
When  When any vehicle hit the pipe supporting structure use receiving
 Mischief by outsiders company

Why Accidental failure


Likelihood 3
Severity 4
Risk (Likelihood * 12 and hydrogen
Severity )
Emergency Level Level III
Risk Level Medium
Consequence  Escape of chlorine to the public domain area affecting the
general public /and nearby industries and can lead to mass
casualty/fatality. There could be large number of affected
people especially if leakage happens during shift change.
 Emergency shut-down valves and procedure are in place ‘
Site Preparedness  Evacuation of residual gas in the pipeline through hypo
level scrubber is in place
 Rescue arrangements are in place
Adequacy of •Plant fire tender is available to mitigate the situation
firefighting/rescue
equipment
Team •Experienced persons team is identified and trained to respond in
preparedness this kind of situations.

Ways to mitigate  CCR is available round the clock to receive information in such
the scenario case and contact number of CCR is available with employees.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Health pandemic – COVID -19

Location  Anywhere inside plant or outside plant premises


When  When COVID-19 positive person comes in contact with other
person.

Why Accidental failure


Likelihood 3
Severity 4
Risk (Likelihood * 12
Severity )
Emergency Level Level II
Risk Level Medium
Consequence  This may affect health of workforce and it could be serious
concern for employees who have pre-medical conditions such
as diabetes, high or low blood pressure, condition related to
lungs etc.
 Eight numbers of ambulances apart from GACL are available
Site Preparedness within mutual aid group.
level  A service of emergency ambulance is available at 108 phone
number.
 Submission of RT PCR report is compulsory for visitors coming
from other state.
 Temperature check of employees is being done regularly
 Temperature check (thermal) of employees is being done
through thermal image camera installed at entry point (security
gate).
 Covid-19 guide lines issued by Government including Social
distancing norms are followed in canteens, offices and in the
entire plant area
 Areas such as washroom and canteen are provided with leg
operated stand to use hand-wash and sanitizer.
Team •One CIH doctor along with male nurse, Five beds, adequate
preparedness emergency medicines/equipment and One ambulance are
available at OHC.
 Training and instructions have been given to employees on
maintain hand hygiene, social distancing, use of sanitizer/soap
and use of mask inside plant and beyond plant premises.

Ways to mitigate  Person showing symptoms of COVID-19 are checked.


the scenario

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario: Manmade disaster – Mob attack, Terrorist attack, Sabotage, Air-attack

Location  Anywhere inside plant or outside plant premises


When  Stealing of sensitive and confidential information.
 Social unrest
 During war
 Terrorist threat

Why  Brain washing


 Personal conflict
 Anti-national element
Likelihood range to
 Malafied intention of enemy country be discussed and
modified as per
Likelihood 4
Severity 4
Risk (Likelihood * 16
Severity )
Emergency Level L –II or L-III
Risk Level High
Consequence  Stealing of sensitive information may lead to illegal trading of it
.which can be the biggest threat to the plant process. In case of
air attack / terrorist attack critical equipment/ storages
containing flammable /toxic material may get destroyed which
could lead to release of toxic chemicals in huge quantity
resulting into mass casualty. Fire/explosion from flammable
substances such as hydrogen could affect nearby industries
and villages. A secondary effect in terms of fire, explosion,
toxic release and collapse of structures might be felt due to
damage to nearby industries which can further escalate the
situation. Stalling plant process or making vital safety interlocks
ineffective.
 Site designated authority is liasoning with IB for getting inputs
Site Preparedness R- Persons for vigilance within the plant should be identified,
level trained and assign duties of vigilance on receipt of input from
IB.

Team • Trained and experienced security personnel are deployed for


preparedness the job
 CCTV cameras are placed at all key locations and are
being monitored continuously round the clock
 Vehicle entering the plant are being checked as per security
guideline
 Periodic round of the plant are taken by security staff.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Ways to mitigate  Ways to mitigate the scenario are mentioned in off-site
the scenario emergency plan and responsibility of individual are specified
and communicated.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Scenario : Collapse of tall structure

Location  Anywhere in the plant


When  During extreme weather conditions such as rain or high wind
 Overloading of structure beyond its design value due to
addition of any equipment as a part of modification.

Why  Aging of structure


 Corrosion and rusting
 Excess vibration/load /stress
Likelihood 4
Severity 4
Risk (Likelihood * 16
Severity )
Emergency Level L –II or L-III
Risk Level High
Consequence  Collapse of the tall structure can severely damage the nearby
structure /equipment and can also lead to entrapment of
persons working in nearby area, resulting into mass casualty.
Damage to the critical equipment can release toxic gas,
corrosive liquid which can generate fumes leading to
uncomfortable breathing environment. Release of toxic gas
may spread in the other areas of the plant and in nearby areas
of the plant and can lead to mass casualty. It can also lead to
fire/explosion.
 Resources like heavy vehicles, earth moving equipments
Site Preparedness like hydra, crane, and forklifts are available at site as
level mentioned in Annexure -24 on page no. 111 in the on-site
emergency plan.
 Eight numbers of ambulances apart from GACL are
available within mutual aid group.
•Services of ambulance at 108 number is available.
Team • 47 trained fire wardens are available other than fire staff.
preparedness •100 trained first-aiders are available at site.

Ways to mitigate  Structure stability is obtained periodically from competent


the scenario person.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Risk Matrix

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Section-3

Disaster management Team

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Disaster Management team and their role

He will himself try to control the same and if


the incident is beyond his control,
immediately evacuate all the workers of
down wind direction at safe place and
inform to concerned plant Control Room
person & CCR.
ROLE OF PERSON NOTICING
If noticing person is more than one, another
person has to immediately inform to
concerned plant Control room person &
CCR. Concerned plant Control Room
person will immediately inform to Shift In
charge.

On receiving the message, IC will rush to


the site of incidence and he himself will
assess the scale of emergency and decide
that the incidence is under his control or is
likely to go beyond his control, then
immediately inform to SMC & CCR.

•Act as SMC till arrival of SMC

•Direct for shutting down of plant, if


ROLE OF INCIDENT CONTROLLER required.
(AGM/DGM/CM/SM/Mgrs./Shift I/C) •Direct for calling the key personnel and
mutual aider through CCR.

•Direct for evacuation, search, traffic


control and rescue with the help of the
security.

•Direct for firefighting with the help of Fire


Department.

•Direct for first aid / medical help


arrangement with the help of HR and
Admin.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
•Inform SMC about progressive
development.\

 Preserve evidence for the cause of


emergency.

•To find out toxicant and their effect of the


area / environment through process /
QCD.

In case of outside Road Accident, IC shall


make following arrangement:

•Send a team of Process Department.


More To
Morereason
reason
totobe
check and arrest of leakage. beupdated
He can also
updated
put in service of ES Department, if
required.

•Neutralize the spilled material and waste


to be collected and shift to our ETP for
further treatment before final disposal.

•Co-ordinate through Marketing


Department for making situation normal
site with the help of transporter.

•Inform to Stores Department, for the


arrangement of crane / Hydra / Forklift if
required.

•In case of the Chlorine leakage, follow as


per the AMAI Manual. (Chlorine
Emergency Response Network).

Complex Head

Any major loss and/or major injury likely


to result to fatality or not, communicate
ROLE OF SITE MAIN CONTROLLER: - GM (O&ES) immediately to Dahej Eco-friendly
Society, Dahej for coordinating.

- Immediate required help

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
- Information to various authorities
concerned with Disaster Management in
the District.

- Support, if needed in the


Management of incidence at the site,
under the direction of available senior
most executive.

•After getting message he will


immediately go to respective process
control room/incident place.

•Relieve the Incident controller from


respective plant and act as an overall Site
Main Controller.

•In consultation with the incident


controller, decide to declare major
emergency.

•Ensure that the key personnel – senior


most people available in respective
department – are called in.

•To inform senior executives, MD about


the incident.

•Constantly review and assess possible


developments to determine the most
probable cause of events.

•Direct the safe shut down of the plant if


required, and evacuation of plant
personnel in consultation with the incident
controller and key personnel. Arrange for
evacuation of surrounding population in
accordance with evacuation arrangement,
with the help of Security, if necessary.

•Ensure for control of traffic movement


within the factory through Security.

•Ensure for a chronological record of the


emergency events through Incident
Controller.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
•If the emergency gets prolonged,
arrange for the relief of personnel and the
provision of catering facilities.

•Issue authorized statements to the news


media, where necessary.

•Ensure for preservation of all possible


evidence arrange for photograph/video.

•Ensure that casualties are receiving


adequate attention and their relatives are
informed.

•Receive information about casualty /


accident.

•Do not restart the plant unless it is


ensured that it is safe to start and cleared
by the statutory authorities

Ensure that information and liaison is


being done with the concerned authorities
through concerned Department Of
company, as per the applicable incidence.

(A) I/C (HR&A) will informPortion


and liaise
to be
with – shifted

1. Director (Industrial Safety & Health),


Gujarat State, Ahmedabad

2. Dy. Director (Industrial Safety &


Health), Bharuch

3. District Collector, Bharuch

4. Dy. Collector, Bharuch (Local Crisis


Group, Vagara)

5. Mamlatdar, Vagara

6. Primary Health Centre, Dahej

7. Bharuch Hospital, (Jambusar


Chowkdi) Bharuch

8. Civil Hospital, Bharuch

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
9. Sun Shine Global Hospital,
Bharuch.

10. Bhailal Amin Hospital, Vadodara

11. Baroda Heart Institute, Vadodara

12. Sterling Hospital, Vadodara

13. Shri Narahari Arogya Kendra


hospital, Vadodara

14. Doctors of surrounding industries,


Dahej

15. Ensure the availability of personal


protective equipments

(B) I/C (S, E & F) will inform and liaise


Portion to be
with shifted

1. Gujarat Pollution Control Board,


Bharuch / Gandhinagar

2. Controller of Explosives (Petroleum &


Explosive Safety Organization), Baroda.

3. Chief Controller of Explosives,


(Petroleum & Explosive Safety
Organization), Nagpur.

4. Dahej Eco Friendly Society

Portion to
The following personnel will inform and
liaise with - be shifted and
formated in
continuation
1. I/C (ES) for PA Plant / I/C (CCP) for
of above
CCP Plant in connection of Boiler

• Chief Inspector of Boiler, Bharuch /


Baroda /Ahmedabad.

2. I/C (CCP) for CCP Plant / I/C (ES) &


I/C (E) for PAP / CSP / H2O2 / AAC /
PAC / SBP / SCP / ASS in connection of
electrocution –

• GEB, Haldarva / Jambuva.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
• Electrical Inspector, Bharuch.

(D) I/C (Mktg.) will inform and liaise with


Portion to be
– shifted

1. Supdt. Central Excise & Custom,


Bharuch Range, Bharuch

2.Concerned Transporters / Consumers /


Dealers

(E) I/C (Store & Purchase) will inform


Portion to be
and liaise with – shifted

Concerned Transporters / Vendors /


Suppliers

(F) I/C (Finance) will inform and liaise


with –Concerned insurance company.
Portion to be
shifted

1. In the Emergency period, he should not


leave the Central Control Room and act
ROLE OF CONTROLLER OF CENTRAL as Communicator Cum Co-coordinator
CONTROL ROOM (CCR) and follow the Emergency Response
Plan/On Site Emergency Plan.

2. In Normal course, he should render the


Header to duties of CCR officer
be added as
Role of Key •Ensure availability of required PPEs in
Personnel
case of emergency.

•To find out toxicant – along with


PROCESS/QC personnel.
Safety, Environment & Fire Department •To inform office of
PESO/GPCB/CPCB/Dahej Eco Friendly
Society /Mutual Aiders.

•To facilitate CCR by additional man


power.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
•To deploy fire personnel with all
necessary rescue setup.

To deploy security personnel.

• To control traffic and vehicle


movement.

• To arrange for search & evacuation


Security Department
of people to assembly points / designated
placed.

• To inform police authority.

To ensure medical help including drugs,


medicines and first aider to the victims in
consultation with I/c Dr. OHC.

•To arrange for sending message to the


relatives of victims.

•To arrange for all administrative help to


HR & Administration Department the casualties and their relatives at the
hospital.

•To inform / brief press, DISH, District


Collector and Local Authorities.

•Head count will be taking care by HR


department.

 To Provide First Aid / Medical


treatment.
I/C Doctor-OHC-Role
 Ensure medicine availability,
Antidotes etc.

Engineering and Technical Services Ensure that Essential staff of Eng. dept.
shall carry out all engineering job.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
• To inform Boiler inspector by I/C (ES) for
PA Plant.

•To inform Boiler inspector by I/C (CCP)


for CCP Plant.

•To inform Electrical inspector by I/C


(CCP) for CCP Plant.

•To inform Electrical inspector by I/C (ES) /


I/C (E) for PAP / CSP / H2O2 / AAC / PAC /
SBP / SCP

Quality Control Department


To carry out all required testing.

Essential Staff Carry out all the emergency jobs as per


direction of IC.

 To ensure that provision for


material/spares of Equipment and
arrange for Hydra / Crane etc.
Stores & Purchase Department
 •To inform Transporters / Vendors /
Suppliers

 To inform Central Excise & Custom


Marketing Department Dept.

 To inform Transporters / Vendors /


Suppliers

 To ensure Mobilization of equipment.


Civil Department
i.e. Excavators, Bulldozers etc.

FINANCE Department  To inform Insurance Dept. / Surveyor

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
CIRP
tobe added
before this
page

DAHEJ COMPLEX EXECUTIVES / OFFICERS


RESIDENTIAL ADDRESS & TELEPHONE Nos.
Resi.
Sr. Name
Residence Address Phone Mobile No.
No. S/S
No.
(A) General
B/4, GACl Colony, Dahej Bypass Road,
1 D C Thakur -- 9909021823
Bharuch
45, Revaba Township, Behind College, 99090
2 T N Trivedi 2266 81
Old N.H. No. 8, Bharuch 21826
B/100, Mangla Park, Dahej By-pass 99090
3 H H Salot 238 648
Road, Bharuch 21824
MK B/3, GACL Colony, Dahej By-pass Road, 99090
4 223 892
Dewangan Bharuch 29670
B/5, GACL Colony, Dahej By-pass Road,
5 H D Parekh -- 9909070333
Bharuch
C/404, Laxminarayan tower, Shreeji
6 R S Patil sadan villa, opp. Narmada college, -- 8238003430
Zadeshwar, Bharuch
A/27, Laxminarayan, Nr. Narayan School, 99090
7 J B Chauhan 2532577
Bharuch 29647
21, Dayanand Park, Nr. GNFC Town 98796
8 K J Bhatt 230483
Ship, Bharuch 60787
99090
9 M B Patel 19, Arbuda Nagar, Link Road, Bharuch 239967
29646
C-2/1, Gokuldham Flats, Dahej Bypass
10 R P Pandey Road, - 9099921249
Bharuch-392001G
(B) PAP
B/6, GACL Colony, Dahej By-pass Road, 99090
1 S K Jain --
Bharuch 29654
C/12, GACL Colony, Opp Amity School,
2 D K Parmar -- 9724332566
Bharuch
A – 82, Samruddhi bunglow, Zadeshwar
3 Rahul Patel -- 9925756638
chokdi, Bharuch
D/7, GACL Colony, Dahej Bypass Road,
4 Hiren Mehta -- 8238003474
Bharuch
(C) CS Plant
B/141, Mangla Park, Dahej By-pass
1 M J Patel -- 9979891834
Road, Bharuch

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
A/504, Narayan Square, Link Road,
2 Anjan Kundu 221059 9979890125
Bharuch
B-304, Satsang park, opposite jain
3 Amit Mehta -- 9979849112
derasar, GIDC,Ankeshwar
Nilesh A/4, V.D. Township, Opp.: IOC petrol
4 _ 9662532983
Jethwa pump, Dahej bypass road, Bharuch.
A/28, V.D. Township, Opp.: IOC petrol
5 D P Tiwari -- 9909029672
pump, Dahej bypass road, Bharuch.
31, VD Township, Dahej – Bypass Road,
6 R V Singh -- 9909029677
Bharuch

(D) Power Plant


DK B/26, Mangla Park, Dahej By-pass
1 238377 99090 29642
Hingrajia Road, Bharuch
C/8, GACL Colony, Dahej By-pass Road,
2 Nirmal Jain -- 99090 29765
Bharuch
C/1, GACL Colony, Dahej By-pass Road,
3 M G Darji - 9909029763
Bharuch
47, Patel Society, Opp. “Shital Guest
4 K V Patel -- 9099029731
House” Railway Staition, Bharuch.
C/9 GACL Colony, Dahej By-pass Road,
5 J J Dasani -- 9979892061
Bharuch
(E) H2O2
MK B/3, GACL Colony, Dahej By-pass Road,
1 223 892 99090 29670
Dewangan Bharuch
C/404, Laxminarayan tower, Shreeji
2 R S Patil sadan villa, opp. Narmada college, -- 8238003430
Zadeshwar, Bharuch
C/12, GACL Colony, Dahej By-pass
3 S K Jain -- 99090 29654
Road, Bharuch
C/10, GACL Colony, Dahej Bypass
4 Jay Hathi -- 9979891869
Road, Bharuch
C/9, GACL Colony, Dahej Bypass Road,
Ashish Bharuch
5 9724323057
Pomal

(F) PAC
A/106, Rang Krishna residency, opp.
Tapan
1 Pramukh park, GNFC by pass road, - 9898207088
Jiwani
Zadeshwar, Bharuch
(G) SBP
BD C/103, Smarajya society, Nr. CNG pump,
1 -- 9687603621
Chaudhary Gadkhol patia, Ankleshwar
(H) AAC
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Mukesh J C/11 GACL colony, Dahej bypass road,
1 8238003443
Patel Bharuch
(I) SCP
Sandeep B. B/47, Mangla Park society, Dahej By-
1 -- 9909029726
Suthar pass Road , Bharuch
C/7, GACL Colony, Dahej By-pass Road,
KH Bharuch
2 -- 9979892138
Vadgama

(J) ASS

Sandeep B. B/47, Mangla Park society, Dahej By-


1 -- 9909029726
Suthar pass Road, Bharuch

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
District contact details
Sr. Authority Address Telephone Email
1 District Collector (Or (O) District (O) 02642 240500, collector-
DEA) Collector 240600 bha@gujarat.gov.in
Office, Bharuch (R) 02642- 223701
(R) Civil Lines (M) 99784 06205
Edgah Road,
Bharuch
2 Alternate Additional District (O) 02642-222332
Collector Collector (R) 99784 51077
Office, Bharuch
3 Superintendent Of Civil Lions, Kali (O) (02642) 223633
Police Talavadi, (M) 99784 05066
Bamba Khana
Road, Bharuch
4 Alternate Dy Sp Civil Lions, Kali (O) 02642 – 223433
Talavadi, (M) 8980044474
Bamba Khana
Road, Bharuch
5 District Development District (O) 02642 - 240603
Officer, Bharuch Development
Office, District
Panchayat,
Bharuch
6 Fire Department Chief- DPMC, (O) (02642) 220229
Ankleshwar Ankleshwar
7. Alternate- Fire DPMC, (O) (02642) 220229
Department Chief- Ankleshwar
Ankleshwar
8 Fire Officer - Fire Bharuch (O) (02642)
Department Chief- Nagarpalika 220151,220143,101,
Bharuch Nagarpalika 102, 108
9. Dist. Health Officer Maktampur, (O) 02642243660 cdmo-
Bharuch (R) 02642243660 bur@jujarat.gov.in
10. Civil Surgeon Civil Hospital, (O) 02642- 243515,
Station Road, 241759
Bharuch.
11 Inspector Of Factories Jilla Seva (O) 02642 -240421 dydishbh@gmail.com
Dy. D I S H, Bharuch Sadan – 2, Nr. (M) 9825627085
Court Bldg.
Bharuch
12 Pollution Control Board Plot No. 1501, (O) 02646 - 222933 ee-brch-
(Regional Officer) GIDC, (R) 02646 – 248665 gpcb@gujarat.gov.in
Estate Phase-
2, Ankleshwar
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
13 Red Cross Blood Bank Panchbati, (O) (02642)243603
Bharuch (R) (02642) 240232
(M) 9377410614
14 Indian Medical Rajpipla (O) (02646)223117
Association Chokdi, (M)9228168461
Ankleshwar
15 Regional Transport Arto Office, (O) (02642) 240653
Officer Bholav, (M) 94284 73322
Bharuch
16 Petroleum And 8th Floor, (O)
Explosive Safety Yashkamal (0265)2361035,
Organization Building. 2225159
Vadodara
17 Disaster Prevention & Fire Station, (O)
Management Centre, Notified Area, (02646) 220229
Ankleshwar GIDC ,
Ankleshwar
18 Disaster Prevention & Dahej Eco (M) 98244-75576
Management Centre, Friendly
Dahej Society – Dahej
19 Railways Railway (O) 02642-240969
Superintendent Station, (R) 02642-240969
Bharuch
20 District Information Bahumanli (O) 02642- 240603
Officer Building
Bharuch

21 Chairman-Local Crisis District (O) (02642) 241400,


Group, And Sdm & Dy. Collector 241980
Collector Office, Bharuch (R) (02642) 240162,
Bharuch &Dahej (M) 9427305256
(Vagra)
22 Chairman-Local Crisis Sdm & Dy. (O) (02646) 242648
Group, and Sdm & Dy. Collector Office (M) 9978405356
Collector, Ankleshwar Ankleshwar
& Hansot
23 Chairman-Local Crisis Sdm & Dy. (O) (02645) 220039
Group, and Sdm & Dy. Collector Office (M) 9426843973
Collector Jhagadia
Jhagadia & Valia
24 Manager-GIDC GIDC (O)02646-223561
Bharuch District Ankleshwar
25 Sdm & Dy. Collector Sdm & Dy. (O) (02644) 220191
Jambusar & Amod Collector Office
Jambusar
26 Secretary-Local Crisis 2nd Floor, Multi (O) 02646 -240421
Group- Story Bldg.,
Bharuch Opp. Gayatri
Nagar, Bharuch
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
27 Secretary-Local Crisis 2nd Floor, Multi (O) 02646 -240421
Group, Dahej (Vagra) Story Bldg.,
Opp. Gayatri
Nagar, Bharuch
28 Secretary-Local Crisis 2nd Floor, Multi (O) 02646 -240421
Group -Ankleshwar Story Bldg.,
Opp. Gayatri
Nagar, Bharuch
29 Secretary-Local Crisis 2nd Floor, Multi (O) 02646 -240421
Group -Jhagadia Story Bldg.,
Opp. Gayatri
Nagar, Bharuch
30 Coast Guard – Daman Daman (O) 0260 – 2260665

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Safe Assembly Points
At the time of emergency

Identifi- Person In charge


cation
Sr. No. of Accommodation Nearest Personal Protective
Location
the Capacity Name & Place of Phone Number Phone Equipment that
Assembly Designation availability number may be required
Point
Resid- In the Resid-
In the factory
ence factory ence
1 2 3 4 5 6 7 8 9 10
1 PA Plant Aprox. 200 Direct Self contained
weigh 282204 breathing
bridge Shift I/C Control room 282243 apparatus are
(PAP) PA Plant. placed in Central
Duty is round --- P.A. Control Room &
2. Near Appox.1200
the clock, Mob. System other locations
Cooling Shift I/C
Shift I/C is 9979890123 much away from
Tower of PA
available at the source of
Plant and
any given 204, 243 emergency. Other
for SBP
Time personal protective
Plant also
equipments are
also placed at
various locations in
the Plants.
3 Tank Farm Approx. 300 Control room -- Direct.
Area CS Plant. Mob. 256130,
Duty is round 9979890124 282304, ---Do---
4 Near AAC Approx. 300 the clock, 304, 343 282343.
Plant - front Shift I/C is

122
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM18027072020 Kalpataru Power (Padampur)
of Cl2 Shift I/C available at P.A
bottling (CSP) any given System
plant Time
5 Near Di-oxo Approx. 100
Plant
6 Near Salt Approx. 100
operator
Cabin
7 Near GTG # Aprox. 100 Control room Direct.
1 CS Plant. 282404,
220 KV Aprox. 200 Shift I/C Duty is round 282443.
8 switch yard (Power the clock, Mob.
(east side) plant) Shift I/C is 9979890122 P.A ---Do---
Near DM Aprox. 100 available at 404, 443 System
plant any given
9
Time

Plant entry Approx. 200


towards Control room
10
substation H2O2 Plant.
Shift I/C Duty is round
Utility Aprox. 200 (H2O2) the clock, P.A
Mob.
Operator Shift I/C is System
11 9909021547 ---Do---
Cabin available at
555, 585
any given
East side of Aprox. 100 Time
H2O2
12
Control
Room
Between Mob. Direct.
Control room
13 sodium 9909021 257077 ---Do---
SC Plant.
chlorate Aprox. 100 460, 461
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Plant & Salt Shift I/C Duty is round P.A
Storage of (SCP) the clock, System
Caustic Shift I/C is
Plant available at
any given
Time

Duty is round
the clock, at Direct.
Nr. Aprox. 400 Shift security 309, 316 282309
Entrance of inspector main gate, 282316
14 marketing (Main gate) Shift security ---Do---
office inspector is
available at
any given
Time

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
SIREN CODE

(a) Actuation of Emergency


- Warbling sound for 2 minutes.

- (pause of 5 second after every 25 seconds)

(b) Emergency Over:


- Continuous blow for 2 minutes.

(c) Siren Testing:


- All the electrical sirens of Dahej complex is tested simultaneously on every Wednesday at 10:00 am for ½ min. with
continuous blow from all the concerned control rooms or respective plant and security gate.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Details of Communication Facilities Available During Emergency
And Those Required For An Off - Site Emergency.

Plant Wise Alarm Points


Plant / Department / Location
Sr. No. The Alarm
Sr. No. Area Location With Type Of
of The It Period of [ Single] Is Type of
Name & Numbers of Floors Alarm or
Alarm Checking Heard Emergency
Location of Floors Each Number Siren
Point [Seen] at
Floor
Fire, Explosion
/ Heavy
Control Electrically 30 Second on Leakages of
In The
1 Room of 1st Floor NA 1 ETP 4th Floor Operated Every Liquids or
Premises
PAP Plant Siren Wednesday Gases,
Natural
Calamities
Fire, Explosion
/ Heavy
Security Electrically 30 Second on Leakages of
Ground Top of ADM In The
2 Gate of NA 2 Operated Every Liquids or
Floor Building Premises
PAP Plant Siren Wednesday Gases,
Natural
Calamities
Fire, Explosion
Control Electrically 30 Second on
Top of 2nd In The / Heavy
3 Room of 1st Floor NA 3 Operated Every
Brine Premises Leakages of
CSP Siren Wednesday
Liquids or
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Gases,
Natural
Calamities
Fire, Explosion
/ Heavy
Top of
Control Electrically 30 Second on Leakages of
Chlorine In The
4 Room of 1st Floor NA 4 Operated Every Liquids or
Liquefaction - Premises
CSP Siren Wednesday Gases,
PGW
Natural
Calamities
Fire, Explosion
/ Heavy
Control
On Pipe Rack Electrically 30 Second on Leakages of
Room of In The
5 2nd Floor NA 5 Near STG Operated Every Liquids or
Power Premises
Building Entry Siren Wednesday Gases,
Plant
Natural
Calamities
A - 02 Minutes & Pause of 05 Seconds Each at Intervals of 30 Seconds.
E.G. [On 25 Sec.] ….. [OFF 05 Sec.]…. [ON 25 Sec.]… .[OFF 05 Sec.]... [On 25 Sec.].... [OFF 05 Sec.]... [ON 25 Sec.]….
NOTE:- [OFF 05 Sec.] In Case Of Emergency
B - Continuous Tone for 02 Minutes After Completion of Emergency.
C - Testing On Wednesday at 10:00 AM By Blowing for 30 Sec.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Details of Communication Facilities Available During Emergency
And Those Required For An Off - Site Emergency.

Plant Wise Alarm Points

Plant / Department / Location


Sr. No. Location Type of The Alarm [
Sr. No.
of The With The It Period of Single] Is Type of
Area of Alarm Floors Alarm or Checking Heard [Seen] Emergency
Name & Numbers
Each Point Number Siren at
Location of Floors
Floor
Fire, Explosion /
Control Electrically 30 Second on
On Top In The Heavy Leakages of
6 Room of 1st Floor NA 6 Operated Every
Floor Premises Liquids or Gases,
AAC Siren Wednesday
Natural Calamities
On Top Fire, Explosion /
Control Electrically 30 Second on
Floor In The Heavy Leakages of
7 Room of 1st Floor NA 7 Operated Every
Control Premises Liquids or Gases,
SBP Plant Siren Wednesday
Room Natural Calamities
Control On Top Fire, Explosion /
Electrically 30 Second on
Room of Floor In The Heavy Leakages of
8 1st Floor NA 8 Operated Every
H2O2 Control Premises Liquids or Gases,
Siren Wednesday
Plant Room Natural Calamities
Fire, Explosion /
On Top Heavy Leakages of
Control Electrically 30 Second on
Floor In The Liquids
9 Room of 1st Floor NA 9 Operated Every
Control Premises
PAC Plant Siren Wednesday
Room or Gases, Natural
Calamities

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
A - 02 Minutes & Pause of 05 Seconds Each at Intervals of 30 Seconds.
E.G. [On 25 Sec.] ….. [OFF 05 Sec.]…. [ON 25 Sec.]… .[OFF 05 Sec.]... [On 25 Sec.].... [OFF 05 Sec.]... [ON 25 Sec.]…. [OFF
NOTE:- 05 Sec.] In Case Of Emergency
B - Continuous Tone for 02 Minutes After Completion of Emergency.
C - Testing On Wednesday at 10:00 AM By Blowing for 30 Sec.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Medical Aid information– As per On-site emergency plan
Ambulance van or alternate
First Aid centers / Ambulance room / OHC / Hospital
arrangement
In charge Persons First Driver’s
Sr Antido Place Faciliti
Telepho Residence aider name
. Name & Name Facilities & tes Accommod of Capa es in
ne-one s &
N location & equipments availa ation availab city the
No. Phone Add. availa Addres
o. Add. ble ility van
ble s
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 Occupati Direct: Three Our Yes One Five Beds At first 5 First We
onal 282211 CIH OHC is 5 beds OHC Availa MBB aid Beds Aid have
Health doctor running with 24 hrs. ble. S center box, total 4
Centre M: s on available CIH/ near Stretc drivers
Dahej 9099915 workin contract staffs with DIH Admin her, for
Complex 266 g in 9904023 agreem require Docto office Oxyge Ambula
, GACL Shift , 878 ent medicines. r is in n nce
Ext.: 211 Dr. done round Cylind and
J.H. with Equipments: the er one
Ghadi 9427873 Baroda Glucometer clock driver
ya 387 Heart Pulse duty availabl
(CIH) and Oxymeter e round
Dr. Multi Digital weight the
Ajitsin Specialt machine clock
h y Sphygmoman
Borasi Hospital ometer
ya , Digital -
(CIH), Bharuc Sphygmoman
Three h, ometer
(3)
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Male Addres Peak Flow
Nurse s: meter
s in Capital Nebulizer
shift, Busines Oxygen
One s Cylinders
(1) Centre, Near-Far and
Attend Panchb Color vision
ant atti, book and
Station chart
Road,
Bharuc
h
02642-
260551/
552

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Medical Aid information – On-site emergency plan
Ambulance van or alternate
First Aid centers / Ambulance room / OHC / Hospital
arrangement
In charge Persons First Driver’s
Sr Antido Place Faciliti
Telepho Residence aider name
. Name & Name Facilities & tes Accommod of Capa es in
ne-one s &
N location & equipments availa ation availab city the
No. Phone Add. availa Addres
o. Add. ble ility van
ble s
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 Occupati Direct: Three Our Yes One Five Beds At first 5 First We
onal 282211 CIH OHC is 5 beds OHC Availa MBB aid Beds Aid have
Health doctor running with 24 hrs. ble. S center box, total 4
Centre M: s on available CIH/ near Stretc drivers
Dahej 9099915 workin contract staffs with DIH Admin her, for
Complex 266 g in 9904023 agreem require Docto office Oxyge Ambula
, GACL Shift , 878 ent medicines. r is in n nce
Ext.: 211 Dr. done round Cylind and
J.H. with Equipments: the er one
Ghadi 9427873 Baroda Glucometer clock driver
ya 387 Heart Pulse duty availabl
(CIH) and Oxymeter e round
Dr. Multi Digital weight the
Ajitsin Specialt machine clock
h y Sphygmoman
Borasi Hospital ometer
ya , Digital -
(CIH), Bharuc Sphygmoman
Three h, ometer
(3)
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Male Addres Peak Flow
Nurse s: meter
s in Capital Nebulizer
shift, Busines Oxygen
One s Cylinders
(1) Centre, Near-Far and
Attend Panchb Color vision
ant atti, book and
Station chart
Road,
Bharuc
h
02642-
260551/
552

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Medical Aid information – Off-site emergency plan

Designated Contact
Sr. Hospital Name With Address Persons With Address (O, Number Of Number Of No. Of Burn
No And Phone Number and Phone:- Numbers Beds Doctors, Ward No Of Ambulance
(O, R, M) Number, Staff
Total
1 2 3 4 5 6 7
1)
Baroda Heart & Multispiciality Mrs. Jagruti Macwan 40 BEDS Doctors – 09
Hospital (O) 02642- Nursing Staff-
71-91, 260551/52/53
(M) 97277 63845 &(O) 52
Capital Business 2 + 1 MOBILE
Center, 02642-260551/52/53 Other Staff –
ICCU
Panchbatti, Station Road, Bharuch Ms.Jinal Rana 84
AMBULANCE BIG
- 392 001. Phone No. 02642- (M) 9727763857 Total - 145 Nos.
260551/52/53
Civil Hospital,Bharuch. Dr.Mansukh K Mavani. 210 Beds Available
Civil Hospital, Station Doctor – 18
Road, Other Staff - 50
Bharuch. 4+1 I.C.U.
(O) 02642- 243515 Ambulance Medium
,241759
(R) 02642- 246200
3) Cjst-Arogya Hospital- Birla Copper Dr .Arvind Raval- 10 Beds Doctors – 5
Township – Dahej Tel-No- Nurses – 7
Tel-No,-02641664097 02641664097 Ambulance 1 2
Drivers – 6
Other Staff - 6

4) Grasim Janseva Trust Dr. Manju Ramnani, 20 Doctors OnRoll


Jankalyan Hospital, C-3, Narmada : 04,
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
C/O Birlacellulosic, Colony, Birladham, Doctors On
Birladham-Kharach, Ta: Kharach. Ta: Contract: 02 ,
Hansot, Dist. Bharuch- Hansot, Dist.: Visiting
394120,Phone Bharuch - 394120 Doctors : 04,
No. : 02646 270001-5 Phone No.: (O) Staff 1 (One) 2 (Two)
02646 271772 (R) Nurse(Male &
02646 271526 (M) Female): 07
9904236100 Lab Technician
: 01 ,

X-Ray
Technician
01 Clerical
Staff : 01 Total
Staff : 20
5) Jayaben Modi Hospital Dr Santosh 100 Consultants – 9,
G.I.D.C Ankleshwar Zacharias, Director, Medical Officers 06 Nos.
Ph No.-222220 (R) Jayben Modi – 6, 05nos.
Hospital Staff Nurses – 40
Quarters Other Staff - 60
(O) 222 220
{R} 224 550
Dr. Nirav Patel
(M) 99132 02862
Narmadanagar Hospital Dr.(Mrs.) A D 32 Beds. Doctor – 5 Other -
6)
Extn – 5290 ,3302 Thakker,Manager Staff - 9
O.N.G.C. Hospital. Dr. Brijesh Prasad 5/C- 5 Beds Doctor – 5 Other - 3
7)
Ankleshwar. 11, T/S, Staff - 9
Bharuch. 5700, 3303
5218, 232625
Patel Surgical Dr.Arvind K Patel (O) 25 Beds Doctors – 1 Nil 1
8)
Hospital,Near S T 02646 - 246535 Mo- Nurse - 3 Staff
Depot,Station 9898595681 – 5 Total - 10
Road,Ankleshwar-
393001
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Welcare Hospital , N.H Mr. Mustaq Shaikh 34 Beds Doctor – 07 Burn Ward 1 + 1 (108)
10
No.08,Kharod Ll Office Admistrator (M) + 6 ICU MBBS - 03 (Proposed)
:02646-650656 99747 39526 Beds BHMS – 02
Dr. Anarwala BAMS - 01
Seva Rural Hospital, (O) 02645- 220021, Enough Enough Staff Available Available
11
Jhagadiatower -Road 220006 Beds

Emergency Response Facility details

Type of Siren. If any, for evacuation. Electrical


Name & Phone In charge Person Own Vehicles
Location No.
No. & Type
Name & Sr.
Phone. No. Address. Type & No. of Public Capacity Driver’s Availability
Address. No.
Warning
1 2 3 4 5 6 7 8 9 10
GACL 02641- TN Trivedi 261 45, Revaba 1 Ambulance Siren with 2 one in each shift
Plant 256315 GM(TS) 9909021826 Township, GJ-6 Z 4032 flashing light
P.O. to17 Behind
Dahej, 256235 College, Old Bolero
TaL: 253335 N.H. No. 8, 2 GJ-16 BG- --- 6
vagra, Bharuch 4828
Dist: SK Rozia
Bharuch. CM (Sec. 253 34, Ganesh
&Tra.) 9909029651 Vihar Soc.
Opp.
Zadeshwar bus
stand
Bharuch

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Mutual Aid Agreement- Outside shelter for Evacuated persons
Incharge Person
Sr. Name, Address & Phone Accommodation
Name & Residence Facilities available
No. Distance Number / Capacity
Designation Ph. No. Address
11 12 13 14 15 16 17 18
1 PJ Chheda high 02641 Harendra Sindha 1500 Public Health Centre,
School, Dahej 256236 (Principal) Post office, STD/PCO
9427115252
Village. 2 K.M. are nearby.
2 GACL Colony, Ajay J. Sharma 1000 Situated on High Way
02642
Dahej by pass road, 9925453199 No. 8
238577
Bharuch

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Mutual Aid emergency response
Name & Address In charge Person Vehicle available
of the factories & Residence
Sr Public Driver’s
outside Transport Distance Ph. No. Name & Sr.
No. Type Capacity Warning Name &
Centers including Designation Ph. No.
Address Instruction Address
Railway Station. No.
19 20 21 22 23 24 25 26 27 28 29 30
2 2+2
Ambulance 6+6
S/ I is Three
02641- 2 Fire Jeep 4 with Audio
Reliance Industries 4.0 to Shift In available driver in
1 282400/282431 --- 1 1 Visual
limited, Dahej 5.0 km. charge round each
Emergency Siren
the clock shift
rescue
tender
2 Three
2+2 with Audio
Hindalco Industries 6.0 to 02641-256004 Shift In Ambulance driver in
2 --- ” 2 6 Visual
Limited 7.0 km 662980 charge 1 Fire Jeep each
Siren
shift
One
Gujarat Chemical Security / 1 with Audio
6.0 to driver in
3 Port Terminal 02641-261036 Shift In --- ” 3 Ambulance 2 Visual
7.0 km each
Company Limited charge Siren
shift
1 Two
Security / with Audio
Petronet LNG 6.0 to 02641- Ambulance 2 driver in
4 Shift In --- ” 4 Visual
Limited 7.0 km 300444/300445 1 Fire Jeep 6 each
charge Siren
shift

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
1 Three
ONGC petro Security / with Audio
7.0 to 9099901600 Ambulance 2 driver in
5 addition limited Shift In --- ” 5 Visual
8.0 km 02641-666108 2 Fire Jeep 6 each
(OPAL) charge Siren
shift
1 Two
Security / with Audio
10 to Ambulance 2 driver in
6 ONGC (C2 – C3) 02641264111 Shift In --- ” 6 Visual
11 km. 1 Fire Jeep 6 each
charge Siren
shift
One
Security / 1 with Audio
2 driver in
7 Torrent Energy Ltd. 1.0 km 02641202500 Shift In --- ” 7 Ambulance Visual
each
charge Siren
shift

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Details of equipment in emergency/central control room

Location of the Centre : (1) Central Control Room (2) Off Site Industrial Emergency Control room :
Dahej Eco-Friendly Society ( 02641-256670 & 9824937101)
Telephone Nos. of the Centre : (1) External – 02641-256133
(2) External – 02641-256315-17
(3) M – 9879604102
(4) Cl2 Helpline No. 1800111735
Internal Ph. No. - 232, 293
Person who
Sr. Numbers or will handle /
Items kept in the Center Its Period of Operation
No. Quantity operate this Notes
item
Last Present
1 2 3 4 5 6 7
1 Internal Phone Two - 232, 293 I/C CCR Daily --
2 External Phone One - 256133 --do-- Daily --
3 Mobile No. 9879604102
4 Wireless Set -- -- -- --
5 PA System -- -- -- --
Key Plan of the factory
6 showing Hazardous area One -- -- --
Classification
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
(a) Inventories Process --
-- --
(b) Location of Eight Instrument
radioactive source Eng.
(c) Sources of siren, Nine (Siren) & Process & Siren resting every --
PPE PPE is in Security Dept. Wednesday at 10:00 --
Every Control hrs. from all plant
room and Egg. concern. The gadgets
Work Shop. mention here in are
regularly tested/
checked

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Section-4

Key Recommendations

122
This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM18027072020 Kalpataru Power (Padampur)
1. All the above scenarios mentioned in section 3 of the report should be included in Disaster
Management Plan.

2. Schedule for periodic mockdrill covering these senarios should be prepared & enforced to
ensure / understand preparedness to mitigate in these conditions in best possible manner.

3. For cyclone / Thundersrome conditions, Online wind velocity monitoring with alarm at
structure designed wind velocity should be installed .

4. Historical maximum flood level in the area should be marked on all the plants structures &
equipments which may submerge at this flood level should be identified , their criticality with
respect to plant safe shutdown must be studied and accordingly contegency plan should be
prepared & enforced.

5. Schedule for periodic checking of foundation integrity (hammer rebound / eco test) and
verticality should be prepared & implemented.

6. Schedule for periodic checking of thickness of structure members / weld joints should be
prepared & enfored. The thickness measured should be compared with minimum acceptable
limits, recorded & reviewed.

7. Training on Mechanical / Engineering integrity should be arranged.

8. Schedule for periodic checking of soil charectstics & comparing with original values at the
time design should be prepared & implemented.Corrective measures. For any change in soil
charectstics obseved during these tests, opinion of expert in this field should be sought.

9. For senario of bus accident, - Periodic training for defensive driving of drivers and Speed limit
on buses / vehicles should be incorporated; it must be ensured that vehicles are fitted with
ABS (Anti brake locking system). Availability of Fire extinguisher must be ensured in all
vehicles.

10. Apart from Level-1,2,3 of emergencies , Plant alert level emergency which should lower most
should be incorporated & its basis should be apperance of alarm with comfirmation with
portable monitor & STEL value.

11. Similarly for for toxic chemical (Chlorine) release, the PPM level in plant at which Plant
emergency (Level-I) & PPM level at plant boundry at which on site emergency (Level-II)
should be declered must be defined / fixed. For this AEGL/EPRGs criteria can be considered.

This document is confidential. For internal use only. Copyrights reserved with TheSafetyMaster™
Doc. No. TSM22002122020 GACL (Dahej)
123
Disclaimer

All rights are reserved with TheSafetyMasterTM 2020. The information and statements contained in
this document are opinions only and reflect TheSafetyMaster™ Team’s judgment based on the
available information.
The Safety Master or any of its employees shall not be responsible for any kind of loss or damage
whatsoever (including, without limitation, loss of profits or any indirect loss), if any, suffered by any
party as a result of decisions made or actions taken in reliance upon or in connection with the
information contained in this report. TheSafetyMasterTM recommends its customer to refer