Professional Documents
Culture Documents
data recorded
Started phase ABC
Tripped phase ABC
Gen. Diff Trip ABC
System Backup start Volt Dept overcurrent start
U/V start V<1 AB BC CA
U/F start f<12
Date and Time 23.08.2016 20:24:43:846
Active group 1
System Frequency 47.52
Relay Trip Time 489 msec
IA‐1 4.787 KA CT at
IB‐1 4.044 KA generator
IC‐1 3.927 KA side
VAB 1.027 KV
VBC 2.649 KV
VCA 3.316 KV
VAN 1.097 KV
VBN 367.5 V
VCN 2.347 KV
IA‐2 9.298 KA CT at
IB‐2 9.734 KA substation
IC‐2 9.332 KA side
IA Diff. 5.248 KA
IB Diff. 5.818 KA
IC Diff. 6.515 KA
VN 0
VN Derived 1.142 KV
IN Measured 2.831 A
IN sensitive 0
I2 182.7 A
3 Phase watt ‐768.4 KW
3 Phase VAR ‐15.04 MVAR
3 Phase p.f. ‐0.048
Null Balance ‐8.786
Field Current 2.73
Field Voltage 24.24
Bus Bar voltage 11.13 KV