SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
35-SDMS-01
SPECIFICATIONS
FOR
TABLE OF CONTENTS
1 – SCOPE 3
2 – CROSS REFERENCES 3
4 – SERVICE CONDITIONS 4
5 – SYSTEM CONDITIONS 4
7 – MARKING 7
10 – GUARANTEE 10
Page 2 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
1.0 SCOPE
This material standard specification shall be read in conjunction with the SEC
general specification No. 01-SDMS-01 (Latest Revision) for general requirements
for all equipment/materials as integral parts of this SDMS.
This SDMS shall also be read in conjunction with SEC Purchase order or contract
schedules.
The latest revision of the following codes and standards shall be applicable for the
equipment/material covered in this specification. In case of any deviation, the
vendor/manufacture may propose equipment/material conforming to an alternate
code or standard. However, the provisions of SEC standard shall supersede the
provisions of these standards in case of any difference.
3.1 ANSI C62.1 Standard specification for surge arrester for AC power
circuit.
3.3 IEC 60099-4 Standard specification for non-linear resistor type arrester
for A.C. system.
3.4 IEC TC37- Standard specification for metal oxide type arrester with
Part-3(wg-4) out spark gaps.
Page 3 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
In case of any deviation from the listed standards, it should be indicated in the list
of deviations submitted by the supplier.
4.1 Surge arrester shall be suitable for operation under the service conditions as per
SEC latest revision of General Specification No. 01-SDMS-01.
4.2 The surge arresters and its fittings shall withstand the effect of direct solar
radiation at their installed locations. The temperature of exposed surfaces shall
be regarded as 75ºC plus the effect of internal heating.
4.3 All locations are subject to sand storms and arresters shall therefore be designed
to prevent ingress/deposit of sand over the outer and inner surface of surge
arresters.
The surge arresters shall be suitable for installation in a system of the given
characteristics in Table No. 1.
However for detailed system conditions refer to the latest revisions of the SEC
general specification No. 01-SDMS-01.
Page 4 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
TABLE NO. 1
SYSTEM
SYSTEM PARAMETER 13.8KV 33KV
Frequency 60HZ 60HZ
Configuration 3W 3W
Effectively Effectively
Neutral Arrangement earthed and/or earthed and/or
low resistance low resistance
Nominal Voltage 13.8KV 33KV
Highest System Voltage 15.2KV 36KV
Short Circuit Levels 21KA 25KA
Power Frequency withstand voltage
(Dry/Wet) 50/45 80/75
Creepage Distance 25/40mm/KV 25/40mm/KV
Nominal discharge current based on
8/20 microsecond wave form 5KA 10 KA
Maximum residual voltage (KV peak
for 8/20 micro second discharge 54KV 130 KV
current wave form having peak of
10KA)
6.1 This SDMS covers one type surge arrester namely Metal oxide non-
linear resistor type gapless, designed for outdoor service and shall be
housed in sealed casing to prevent ingress of moisture and dust.
6.2 Metal oxide non-linear resistor type gapless: An arrester having one
or more non-linear metal oxide resistors, connected in series and/or
parallel but having no integrated series or parallel spark gaps.
Page 5 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
Page 6 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
6.10 Terminals:
Terminals shall be clamp type and shall be constructed for conductor
either copper or ACSR and continuous work shall be guaranteed
without any deterioration. Full details of the design of terminals
must be submitted at the time of tendering and must receive SEC
approval.
Terminals shall accommodate conductor standard sizes used by
SEC.
7.0 MARKINGS:
Each arrester shall be provided with a name plate, bearing the following
information as a minimum, in English and/or Arabic:
7.1 Rated voltage.
7.2 Nominal discharge current.
7.3 Short circuit level.
7.4 Maximum continuous operating voltage (MCOV).
7.5 Manufacturer’s name or trademark.
7.6 Year of manufacture.
7.7 Country of origin.
7.8 Manufacturer serial number.
Page 7 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
8.1 General:
All equipments shall be tested in accordance with the latest standards
and as specified herein.
The supplier shall provide acceptable type test certificates for his
offered equipment. SEC at his discretion may wish to have
additional or repeat type test carried out. After completion of the
type tests, two certified copies of the test reports shall be submitted
for approval. No equipment shall be shipped untill approval of the
test report has been given by SEC.
Page 8 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
8.2 Inspection:
SEC may wish to witness tests or to visit the factory during manufacture
of any or all items covered by this specification. Accordingly, the
supplier should give adequate notice of manufacturing and test
schedules.
9.1 Each arrester shall be unit packed, complete with line and ground
lead attachment and mounting accessories in such manner to prevent
damage to them during transportation and handling up to installation
site.
9.5 Packing note in Arabic and English shall be included in each case
giving description of goods packed.
10.0 GUARANTEE
10.1 Vendor shall guarantee the surge arresters against all the defects
arising out of faulty design, workmanship or defective material for
Page 9 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
a period of one (1) year from the date of installation or two (2)
years from the date of delivery, unless and otherwise specified in
tender documents. SEC certification for the date of installation
shall be accepted by the vendor.
11.1 The vendor shall complete and return one copy of the attached Data
Schedule with quotation. In addition to Data Schedule, clause-by-
clause compliance to this Specification shall also be
confirmed/submitted.
b- Test reports.
Page 10 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
SEC VENDOR
SR. DESCRIPTION SPECIFIED PROPOSED
NO. VALUES VALUES
1 Standard to which the arrester is made IEC 60099-4
2 System voltage 13.8/33KV
3 Rated voltage 15/36KV
4 Nominal discharge current 5 & 10KA
5 Pressure relief class Required
6 Power frequency withstand voltage
7 Creepage distance 25/40mm/KV
8 Short circuit levels 21/25KA
9 BIL
10 Max. continuous operating voltage (MCOV) 12.7KV/29KV
11 Maximum residual voltage, KV
12 Net weight, Kg
13 Safe cantilever strength at line terminal, KN
14 Insulator type
15 Color of glazed porcelain/polymer Brown/Grey
16 No. per standard packing
17 Dimentional drawings and data submitted
with proposal
18 Method of operation of disconnector
19 Moisture sealing system
20 Mounting arrangement Vertical or
horizontal
21 Marking Required
22 Nameplate with complete information Required
Page 11 of 12
Saudi Electricity Company اﻟﺸﺮآﺔ اﻟﺴﻌﻮدﻳﺔ ﻟﻠﻜﻬﺮﺑﺎء
35-SDMS-01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 28-12-1422 H
D. List of the deviations and clauses to which exceptions are taken by the
bidder/vendor/supplier (Use separate sheet if necessary).
MANUFACTURER OF VENDOR/
MATERIALS/EQUIPMENT SUPPLIER
Name of company
Page 12 of 12