You are on page 1of 1

Installation and Startup Guide | Job setup and engineering

3. Create a new conventional BACtalk job on Server2 (for example, new


devices or a new school building to add to an existing school district
job) and merge it with the backed up target job from Server1.

4. Back up the new merged conventional job.

5. Restore the backup of the merged conventional job to Server1.

6. If desired, convert to SQL Server and then complete the job


configuration.

X To merge new data with a SQL Server Envision for BACtalk v2.6 job

Note Server1 is Online and running a SQL Server Envision for BACtalk v2.6
database. Server2 is Offline and running BACtalk.

1. Create a new conventional BACtalk job on Server2 (for example, add


new devices or a new school building to an existing school district job,
or add a new building to an existing campus job).

2. Back up the new job on Server2.

3. Merge the backed up job with the target job on Server1and then restart
Envision for BACtalk in the target job to complete the merge process.
Data automatically gets stored to the SQL Server database.

4. Complete job configuration on Server1.

Verifying General System Setup


Use the General System Setup dialog box to define settings that apply to a
particular operator workstation and how it is used within the BACtalk system.
Depending on the installation type, verifying system setup may include the
following. See the quick steps (beginning on page 9) for your installation type
for a list of the tasks that apply.

• Set the device instance for the operator workstation. This determines
how this operator workstation is identified to other devices on the
BACnet network.
• Verify the Ethernet setup. This determines how this operator
workstation communicates with other devices on the BACnet network.
• Identify the operator workstation as a server or client. See “Setting up a
client/server relationship” on page 25 for detailed instructions.

X To set the device instance for the operator workstation


1. Start Envision for BACtalk and log in.

2. On the Tools menu, click General System Setup.

3. On the Identification tab, type a device instance for this operator


workstation.

4. Type a name and a description for the operator workstation.

5. Click OK, or continue with the next procedure.

© Honeywell. All Rights Reserved. LTBT-TM-ADMIN26 Rev. A 41