Professional Documents
Culture Documents
MOUNTING LOCATION ( See FIG. 1 ) MOUNTING THE DETECTOR ( FIG. 2 ) FIG. 2 - THE BACK COVER
• If heavy blinds or curtains cover the glass, 1. Use a small screwdriver to push the prong
you must locate the detector behind the on top of the case and open the case.
blinds on the window frame or above it, 2. Snap out the detector PCB.
otherwise the blinds might block the 3. Insert the wires through the wiring hole (B).
sound. Make sure to test the unit 4. Use the mounting holes (A) to mount the A
thoroughly for proper detection. detector.
• Install the detector in a direct line of sight 5. Connect the wires to the terminal.(See
with the protected glass. Terminal Connections)
• Do not mount the unit in front of air ducts, 6. Reinstall the detector PCB.
or close to bells (measuring 0.5m (or 7. Close the case.
larger) in diameter).
• For a few protected glasses in one room,
JUMPERS ( FIG. 4 )
locate the detector in optimal distance
from them to achieve the best detection. • JP1 - Shock / Glass selector for detection
calibration.
Note: for symmetrical cover of the detection • JP2 – Memory LED control.
area it is recommended to place the • JP3 - Reduces the sensitivity of sound B
detector on the ceiling. detection by 50%. A
7 8 9
• Make sure to disconnect the jumper at Use #22 AWG (0.5mm) or wires with a larger
JP1. When the jumper is disconnected, diameter. Use the following table to determine
the detector will detect both shock and required wire gauge (diameter) and length of
sound frequencies. wire between the detector and the control
• To ensure maximum protection against panel.
false alarms, activate any device in the
area, which might automatically cycle
pumps, generators, heating/air Wire Length m 200 300 400 800
conditioning units, etc. If the cycling Wire Diameter mm .5 .75 1.0 1.5
devices trigger an alarm, mount the unit in Wire Length ft 800 1200 2000 3400
a different location. Wire Gauge # 22 20 18 16
16 17 18