You are on page 1of 2

1 2 3

The GBD-PLUS is the ultimate answer for all FIG. 1 - MOUNTING


those tired of false alarms. It listens for

GBD-PLUS sounds of breaking glass, which produce two


sequential signals of different frequencies.
The unique phased frequency detection
circuitry of this detector allows detection of
COMPACT both shock signal and the strong signal of
GLASS BREAK DETECTOR glass breakage creating a “false alarm free”
glass break detector.
The detector does not need to be attached to
the window, providing volume protection, and
allowing you to protect several windows with
one detector.
FEATURES
• Shock and/or breakage selectable
• Analyzes two frequencies
• Unique signal analysis ignores The detector offers flexible installation. It can
environmental disturbances be either ceiling mounted or wall mounted as
• Memory LED shown in the figure above.
ELECTRONIC ENGINEERING LTD. • ASIC based electronics
• Sensitivity adjustment
INSTALLATION INSTRUCTIONS • New ultra compact design
• Flush mount installation (option)
P/N 7101352 Ver. C A.Y. • Outstanding detection range and reliability
4 5 6

MOUNTING LOCATION ( See FIG. 1 ) MOUNTING THE DETECTOR ( FIG. 2 ) FIG. 2 - THE BACK COVER

• If heavy blinds or curtains cover the glass, 1. Use a small screwdriver to push the prong
you must locate the detector behind the on top of the case and open the case.
blinds on the window frame or above it, 2. Snap out the detector PCB.
otherwise the blinds might block the 3. Insert the wires through the wiring hole (B).
sound. Make sure to test the unit 4. Use the mounting holes (A) to mount the A
thoroughly for proper detection. detector.
• Install the detector in a direct line of sight 5. Connect the wires to the terminal.(See
with the protected glass. Terminal Connections)
• Do not mount the unit in front of air ducts, 6. Reinstall the detector PCB.
or close to bells (measuring 0.5m (or 7. Close the case.
larger) in diameter).
• For a few protected glasses in one room,
JUMPERS ( FIG. 4 )
locate the detector in optimal distance
from them to achieve the best detection. • JP1 - Shock / Glass selector for detection
calibration.
Note: for symmetrical cover of the detection • JP2 – Memory LED control.
area it is recommended to place the • JP3 - Reduces the sensitivity of sound B
detector on the ceiling. detection by 50%. A

7 8 9

FIG. 3 - TERMINAL BLOCK THE CALIBRATION TOOL ( * ) TESTING THE DETECTOR


The Simulator/Tester & Calibration tool is First use the Simulator in manual mode to
especially designed to check phased simulate the noise of glass breaking. Check
frequency glass break detectors. that the yellow LED is ON. If it does not light,
Since the detector will react to the high the sensitivity calibration is necessary (See
frequency breakage sound only when it Sound Calibration).
comes sequentially after a low frequency Now use your hand or a padded object to
SHOCK sound, this device is necessary to carefully strike the glass. If the green LED
TERMINAL BLOCK CONNECTIONS check for proper operation of the GBD-PLUS does not light, adjust as necessary (See
without actually breaking the glass. Shock Calibration).
Terminal 1 - Marked - ( GND ) Now use the Simulator in automatic mode
Connect to ground of the control panel. Manual mode: and check that the red LED lights. If the red
Terminal 2 - Marked + ( +12V ) In this mode, the Simulator will emit the high LED is ON, your detector is working properly.
Connect to the positive Voltage output of 9-16 frequency sound of breaking glass for "Glass" Otherwise try adjusting the sound and shock
Vdc source (usually from the alarm control unit) adjustment. setting until the red LED lights.
Terminals 3 & 4 - Marked TAMPER Automatic mode:
If a Tamper function is required connect these In order to simulate breaking glass, place the
terminals to a 24hour normally closed protective zone Simulator on the surface of the protected
in the control unit. If the front cover of the detector is glass, and gently hit it with your hand. The
opened, an immediate alarm signal will be sent to the Simulator will then emit the sound of breaking
control unit.
glass. Be careful not to break the glass while
Terminals 5 & 6 - Marked RELAY testing the detector.
These are the output relay contacts of the detector. ∗ It is recommended to use simulator CROW
Connect to the control at zone input.
P/N: 0040011
10 11 12

GLASS BREAK ADJUSTMENT SHOCK ADJUSTMENT THE MEMORY FUNCTION


To adjust the glass break setting To adjust the shock setting The alarm memory function allows the
(increase/decrease sensitivity) place the (increase/decrease sensitivity) place the identification of an alerting detector out of
jumper JP1 according the GLASS marking jumper JP1 according the SHOCK marking multiple detectors connected to one (or the
(connecting the middle pin with the upper pin) (connecting the middle pin with the lower pin) same) zone of the control panel.
- (See Fig. 4) Green LED is constantly ON. - (See Fig. 4) Yellow LED is constantly ON. To enable this function, Set ON jumper JP2
Now you can adjust the sensitivity by rotating Now you can adjust the sensitivity by rotating (MEM) (connected on both pins - See Fig. 4)
the upper potentiometer (marked as GLASS the lower potentiometer (marked as SHOCK In case of an alarm, the Red LED will stay
CAL. - see Fig. 4). CAL. - see Fig. 4). ON until memory function is reset.
Operate the Sound Break Simulator and Hit gently on the protected glass and rotate
To reset the memory function, switch OFF
rotate the potentiometer clock-wise to the potentiometer clock-wise to increase
(disconnect) the voltage wire (+12V) from the
increase sensitivity, and counter-clock-wise to sensitivity, and counter-clock-wise to
TERMINAL BLOCK for minimum 15 seconds
decrease sensitivity until the Yellow and Red decrease sensitivity until the Green and Red
then switch on (reconnect) voltage wire
LED’s are illuminating for each glass break LED’s are illuminating for each hit.
(+12V).
sound. Remember that rotating the Remember that rotating the potentiometer will
(The control panel key ON/OFF can be used
potentiometer will have no effect upon the have no effect upon the settings if the middle
for this application if it control the voltage
settings if the middle pin of JP1 is not pin of JP1 is not connected to the lower pin.
(+12V).
connected to the upper pin.
Note
SENSITIVITY SETTING
Note • When the jumper is set for SHOCK
• When the jumper is set for GLASS adjustment, only the low frequency of the For some installations you may find that GBD-
adjustment, only the high frequency sound shock signal prior to glass breakage is plus is too sensitive. Use JUMPER JP3 to
of breaking glass is detected. detected. decrease sensitivity to 50%.
JP3 OPEN - 100% sensitivity
JP3 CONNECTED - 50% sensitivity
13 14 15

FINAL TESTING FIG. 4 - PCB Layout WIRE SIZE REQUIREMENTS

• Make sure to disconnect the jumper at Use #22 AWG (0.5mm) or wires with a larger
JP1. When the jumper is disconnected, diameter. Use the following table to determine
the detector will detect both shock and required wire gauge (diameter) and length of
sound frequencies. wire between the detector and the control
• To ensure maximum protection against panel.
false alarms, activate any device in the
area, which might automatically cycle
pumps, generators, heating/air Wire Length m 200 300 400 800
conditioning units, etc. If the cycling Wire Diameter mm .5 .75 1.0 1.5
devices trigger an alarm, mount the unit in Wire Length ft 800 1200 2000 3400
a different location. Wire Gauge # 22 20 18 16

16 17 18

TECHNICAL SPECIFICATIONS CROW LIMITED WARRANTY CROW ELECTRONIC ENGINEERING LTD.


(Crow) warrants this product to be free from defects in materials and workmanship ISRAEL: 57 Hamelacha St., Holon 58855
Power Input 9 - 16 Vdc under normal use and service for a period of one year from the last day of the Tel: 972-3-5569937 /8 /9
week and year whose numbers are printed on the printed circuit board inside this Fax: 972-3-5592981
Current Consumption Standby: 22mA at 12Vdc product.
E-mail: support@crow.co.il
Active: 25mA at 12Vdc Crow’s obligation is limited to repairing or replacing this product, at its option, free USA: 2160 North Central Road,
of charge for materials or labor, if it is proved to be defective in materials or Fort Lee, N.J. 07024
Detection Range 10m (33ft), Adjustable Tel: 1-800-GET CROW
workmanship under normal use and service. Crow shall have no obligation under or (201) 944 0005
Dimensions 78mm x 51mm x 21mm this Limited Warranty or otherwise if the product is altered or improperly repaired Fax: (201) 944 1199
(3.07 `` x 2.01`` x 0.83) or serviced by anyone other then Crow. E-mail: support@crowelec.com
Mounting Ceiling or Wall There are no warranties, expressed or implied, of merchantability or fitness for a AUSTRALIA: 429 Nepean HWY Brighton East Vic 3187
particular purpose or otherwise, which extend beyond the description on the face Tel: 61-3-9596 7222
Alarm Output Relay N.C 50mA/24Vdc with hereof. In no case shall Crow be liable to anyone for any consequential or Fax: 61-3-9596 0888
27 Ohm in line resistor incidental damages for breach of this or any other warranty, expressed or implied, E-mail: crow@crowaust.com.au
or upon any other basis of liability whatsoever, even if the loss or damage is
Tamper Switch N.C 50mA 24Vdc with caused by Crow’s own negligence or fault.
POLAND: VIDICON 01-231 Warszawa
Ul. Plocka 17
10 Ohm in line resistor Crow does not represent that this product can not be compromised or Tel: 48 22 562 3000
circumvented; that this product will prevent any person injury or property loss or Fax: 48 22 562 3030
Operating Temperature -20°C to 50°C E-mail: vidicon@vidicon.pl
damage by burglary, robbery, fire or otherwise; or that this product will in all cases
Range (-4°F to 122°F) provide adequate warning or protection. Purchaser understands that a properly LATIN AMERICA: CROW LATIN AMERICA
Operating Humidity 95% max relative humidity installed and maintained product can only reduce the risk of burglary, robbery or 5753 NW 151ST.Street
other events occurring without providing an alarm, but it is not insurance or a MIAMI LAKES,
Range non condensing FL 33014 – USA
guarantee that such will not occur or that there will be no personal injury or
Tel: +1-305-823-8700
Storage Temperature -30°C to 70°C property loss or damage as a result. Consequently, Crow shall have no liability for Fax: +1-305-823-8711
Range (-22°F to 158°F) any personal injury; property damage or any other loss based on claim that this E-mail: sales@crowlatinamerica.com
product failed to give any warning. However, if Crow is held liable, whether directly
Electro condenser ITALY: DEATRONIC
or indirectly, for any loss or damage arising under this limited warranty or VIA Giulianello 4/14
microphone otherwise, regardless of cause or origin, Crow’s maximum liability shall not in any 00178 ROMA, ITALY
case exceed the purchase price of this product, which shall be the complete and Tel: +39-0676-12912
RFI Protection 30V/m 10 -1000MHz
exclusive remedy against Crow. Fax: +39-0676-12601
EMI Protection 50,000V electrical E-mail: info@deatronic.com
interference from lightning These instructions supersede all previous issues prior to July 2003.
CROW reserves the rights to change specifications
without prior notice
N345
35352CE50

You might also like