You are on page 1of 1

Critical

Fault Message Description / Effect Recommended Action Fault


ANF011 Auxiliary Ground Fault This fault occurs when the ground fault 1. Check the wiring and condition of all circuitry X
detection circuit in the MCC-ZLV is in the MCC-ZLV.
triggered. The emergency shutdown 2. Check that the ground fault test button is not
sequence will occur. pressed.
ANF012 Rotary Motor Blower Control This fault occurs when there is no feedback 1. Check the operation and/or wiring of the
Fault from the rotary motor blower. This will blower motor and motor contactor.
prevent the rotary drive from operating. 2. On the operator display, check for feedback
from the blower motor.
ANF013 Rotary Input Power Fault This fault occurs if the power supply to the 1. Check the connection and/or wiring of the
rotary control circuitry is disconnected. This rotary control panel.
will prevent the rotary drive from operating.
ANF014 Rotary Stall Fault This fault occurs when rotary motor stall 1. Adjust speed of the rotary motor.
detection settings are 95% of stall armature
current and hot armature voltage drop at
100% stall armature current. This will
prevent the rotary drive from operating.
ANF015 Rotary Drive Incomplete This fault occurs if the drive armature 1. Check the operation and/or wiring of the
Sequence current signal is not active before a certain rotary drive.
delay. This will prevent the rotary drive 2. Check the incoming voltage to the rotary
from operating. control panel.
ANF016 Rotary Drive Internal Fault This fault occurs when the rotary drive fails 1. Check the operation and/or wiring of the
to respond to the control panel. This will rotary drive control panel.
prevent the rotary drive from operating.
ANF017 Rotary Field Loss This fault occurs if the rotary control field 1. Check the operation and/or wiring of the
current is less than 50% of weak field rotary motor and rotary control panel.
current. This will prevent the rotary drive
from operating.
ANF018 Rotary Field Over Current This fault occurs if the rotary motor field 1. Check the operation and/or wiring of the
current exceeds 16.2 A (120% of maximum rotary motor.
running current of 13.5 A). This will prevent
the rotary drive from operating.
ANF019 Hoist/Pulldown Drive Internal This fault occurs when the hoist / pulldown 1. Check the operation and/or wiring of the
Fault drive fails to respond to the control panel. hoist/pulldown drive control panel.
This will prevent the hoist/pulldown drive
from operating.

Page 81 of 128 Issued :

X-4138

You might also like