You are on page 1of 9

String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 1

02/02/2022 14:16:39

String Information Test Information


Site Name: Telmex | Metro | Culh 01f Test Start Date: 02/02/2022 10:07:28
String ID: Bb1alpha Operator:
# of Batteries: 24 Float Voltage:
Float Current:

String Specific Battery Details Battery Definition Test Settings


# of Straps: 0 Manufacturer: Gnb Noise Filtering: Auto
Float: On Model: 100G33 Polarity Correction: On
Voltage Reference/Cell: 2.230 Cell Type: Lead Acid (AGM) Battery Test Start: Auto
Voltage Reference/Battery: 2.230 Capacity: 1600.0 (Ah) Strap Test Start: Auto
# of Cells/Battery: 1 Auto Start Delay: 1
Test Level: Battery

Baseline Information Test Parameters Hardware Settings


Impedance Reference: 0.184 (mΩ) Impedance Serial Number: EC2000-1103496
ACF: 1.543 Voltage MAC Address: 00:0D:15:00:A8:5E
Baseline Type: Auto Generated in EC2000 CELScan Hardware Version: 19333301
(Sulfation/Dryout)
Baselined from Test Date: 02/02/2022 10:07:28 Firmware Version: 2.1.8
Data Origin: EC2000

Applied Alarms

Impedance (%) Voltage (V/Cell) Sulfation (%) Dryout (%) Strap (%)
High Fail 125.0 2.35 20 20 Undefined
High Warn 117.0 2.30 15 15 Undefined
Low Warn 70.0 2.20
Low Fail 50.0 2.15
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 2
02/02/2022 14:16:39

Impedance (mΩ)
Healthy High Fail: 125.0% High Warn: 117.0% Low Warn: 70.0% Low Fail: 50.0%

0.9
0.8
Impedance (mΩ)

0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 3
02/02/2022 14:16:39

Voltage (V)
Healthy High Fail: 2.35 V/Cell High Warn: 2.30 V/Cell Low Warn: 2.20 V/Cell Low Fail: 2.15 V/Cell

2.36
2.34
2.32
Voltage (V/Battery)

2.3
2.28
2.26
2.24
2.22
2.2
2.18
2.16
2.14

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 4
02/02/2022 14:16:39

Sulfation (%)
Healthy High Fail: 20% High Warn: 15%

100
90
80
Sulfation (%)

70
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 5
02/02/2022 14:16:39

Dryout (%)
Healthy High Fail: 20% High Warn: 15%

80

70

60
Dryout (%)

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 6
02/02/2022 14:16:39

Temperature (°C)

100
90
80
Temperature (°C)

70
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 7
02/02/2022 14:16:39

Battery # Result Impedance Impedance (%) Voltage Sulfation Dryout Temperature


(mΩ) (Population Ref.) (V) (%) (%) (°C)
1 Fail 0.323 175.5 2.249 31 0 27.1
2 Fail 0.233 126.7 2.251 11 0 27.1
3 Pass 0.168 91.3 2.241 0 0 27.1
4 Pass 0.189 102.8 2.244 1 0 27.1
5 Pass 0.202 109.8 2.246 3 0 27.1
6 Pass 0.187 101.7 2.242 1 0 27.1
7 Pass 0.184 100.0 2.243 0 0 27.1
8 Pass 0.193 104.9 2.250 1 0 27.1
9 Pass 0.198 107.2 2.247 2 0 27.1
10 Pass 0.195 105.8 2.245 2 0 27.1
11 Pass 0.214 116.0 2.253 5 0 27.1
12 Pass 0.204 111.0 2.250 2 0 27.1
13 Fail 0.572 310.6 2.252 0 41 27.1
14 Pass 0.192 104.3 2.247 1 0 27.1
15 Pass 0.188 102.2 2.252 1 0 27.1
16 Pass 0.185 100.6 2.256 1 0 27.1
17 Pass 0.186 100.7 2.255 2 0 27.1
18 Fail 0.233 126.4 2.250 9 0 27.1
19 Fail 0.480 260.3 2.255 0 33 27.1
20 Pass 0.214 116.2 2.245 8 0 27.1
21 Warning 0.222 120.2 2.251 8 0 27.1
22 Fail 0.242 131.3 2.247 11 0 27.1
23 Fail 0.279 151.6 2.241 18 0 27.1
24 Fail 0.444 241.0 2.250 54 29 27.1
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 8
02/02/2022 14:16:39

Battery # Installation Manufactured Replaced


Date Date
1 No
2 No
3 No
4 No
5 No
6 No
7 No
8 No
9 No
10 No
11 No
12 No
13 No
14 No
15 No
16 No
17 No
18 No
19 No
20 No
21 No
22 No
23 No
24 No
String Report for: Telmex | Metro | Culh 01f | Bb1alpha on 02/02/2022 10:07:28 Page: 9
02/02/2022 14:16:39

Summary
Test Summary
Test Start Date & Time: 02/02/2022 10:07:28
Test End Date & Time: 02/02/2022 10:18:11
Total Number of Batteries Tested: 24
Number of Batteries Passed: 15
Number of Batteries Failed: 8
Number of Batteries Warned: 1

Test Statistics

Coefficient of
Maximum Minimum Mean Std. Deviation Variation %
Impedance (mΩ): 0.572 0.168 0.247 0.102 41.5
Impedance (%) (Population-referenced): 310.6 91.3 134.1 55.6 41.5
Voltage (V): 2.256 2.241 2.248 0.004 0.2
Temperature (°C): 27.1 27.1 27.1 0.0 0.0
Sulfation (%): 54 0
Dryout (%): 41 0