String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 1

02/02/2022 14:20:56

String Information Test Information


Site Name: Telmex | Metro | Culh 01f Test Start Date: 02/02/2022 10:40:47
String ID: Bb4alpha Operator:
# of Batteries: 24 Float Voltage:
Float Current:

String Specific Battery Details Battery Definition Test Settings


# of Straps: 0 Manufacturer: Gnb Noise Filtering: Auto
Float: On Model: 100G33 Polarity Correction: On
Voltage Reference/Cell: 2.230 Cell Type: Lead Acid (AGM) Battery Test Start: Auto
Voltage Reference/Battery: 2.230 Capacity: 1600.0 (Ah) Strap Test Start: Auto
# of Cells/Battery: 1 Auto Start Delay: 1
Test Level: Battery

Baseline Information Test Parameters Hardware Settings


Impedance Reference: 0.185 (mΩ) Impedance Serial Number: EC2000-1103496
ACF: 1.477 Voltage MAC Address: 00:0D:15:00:A8:5E
Baseline Type: Auto Generated in EC2000 CELScan Hardware Version: 19333301
(Sulfation/Dryout)
Baselined from Test Date: 02/02/2022 10:40:47 Firmware Version: 2.1.8
Data Origin: EC2000

Applied Alarms

Impedance (%) Voltage (V/Cell) Sulfation (%) Dryout (%) Strap (%)
High Fail 125.0 2.35 20 20 Undefined
High Warn 117.0 2.30 15 15 Undefined
Low Warn 70.0 2.20
Low Fail 50.0 2.15
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 2
02/02/2022 14:20:56

Impedance (mΩ)
Healthy High Fail: 125.0% High Warn: 117.0% Low Warn: 70.0% Low Fail: 50.0%

11
10
9
Impedance (mΩ)

8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 3
02/02/2022 14:20:56

Voltage (V)
Healthy High Fail: 2.35 V/Cell High Warn: 2.30 V/Cell Low Warn: 2.20 V/Cell Low Fail: 2.15 V/Cell

2.9
2.8
2.7
Voltage (V/Battery)

2.6
2.5
2.4
2.3
2.2
2.1
2
1.9

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 4
02/02/2022 14:20:56

Sulfation (%)
Healthy High Fail: 20% High Warn: 15%

55
50
45
40
Sulfation (%)

35
30
25
20
15
10
5
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 5
02/02/2022 14:20:56

Dryout (%)
Healthy High Fail: 20% High Warn: 15%
200
180
160
140
Dryout (%)

120
100
80
60
40
20
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 6
02/02/2022 14:20:56

Temperature (°C)

100
90
80
Temperature (°C)

70
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 7
02/02/2022 14:20:56

Battery # Result Impedance Impedance (%) Voltage Sulfation Dryout Temperature


(mΩ) (Population Ref.) (V) (%) (%) (°C)
1 Fail 0.325 175.6 2.229 29 0 27.0
2 Fail 5.743 3100.9 2.569 0 100 27.0
3 Pass 0.200 108.2 2.234 4 0 27.0
4 Fail 0.300 161.9 2.231 24 0 27.0
5 Fail 0.298 161.2 2.222 20 0 27.0
6 Fail 0.274 147.9 2.226 18 0 27.0
7 Pass 0.192 103.9 2.234 1 0 27.0
8 Pass 0.191 103.1 2.228 0 0 27.0
9 Fail 0.236 127.7 2.240 11 0 27.0
10 Pass 0.189 102.0 2.237 0 0 27.0
11 Pass 0.197 106.3 2.238 2 0 27.0
12 Pass 0.191 103.1 2.237 0 0 27.0
13 Pass 0.206 111.1 2.242 4 0 27.0
14 Pass 0.185 100.0 2.234 0 0 27.0
15 Pass 0.190 102.4 2.236 0 0 27.0
16 Pass 0.171 92.1 2.246 0 0 27.0
17 Pass 0.189 102.0 2.239 1 0 27.0
18 Warning 0.225 121.6 2.239 7 0 27.0
19 Fail 0.237 128.1 2.240 10 0 27.0
20 Warning 0.227 122.6 2.236 7 0 27.0
21 Warning 0.227 122.5 2.233 7 0 27.0
22 Fail 0.236 127.7 2.235 9 0 27.0
23 Warning 0.227 122.8 2.228 6 0 27.0
24 Fail 0.254 136.9 2.223 13 0 27.0
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 8
02/02/2022 14:20:56

Battery # Installation Manufactured Replaced


Date Date
1 No
2 No
3 No
4 No
5 No
6 No
7 No
8 No
9 No
10 No
11 No
12 No
13 No
14 No
15 No
16 No
17 No
18 No
19 No
20 No
21 No
22 No
23 No
24 No
String Report for: Telmex | Metro | Culh 01f | Bb4alpha on 02/02/2022 10:40:47 Page: 9
02/02/2022 14:20:56

Summary
Test Summary
Test Start Date & Time: 02/02/2022 10:40:47
Test End Date & Time: 02/02/2022 10:56:46
Total Number of Batteries Tested: 24
Number of Batteries Passed: 11
Number of Batteries Failed: 9
Number of Batteries Warned: 4

Test Statistics

Coefficient of
Maximum Minimum Mean Std. Deviation Variation %
Impedance (mΩ): 5.743 0.171 0.455 1.103 242.7
Impedance (%) (Population-referenced): 3100.9 92.1 245.5 595.8 242.7
Voltage (V): 2.569 2.222 2.248 0.067 3.0
Temperature (°C): 27.0 27.0 27.0 0.0 0.0
Sulfation (%): 29 0
Dryout (%): 100 0