( 9324-RLDx ) Studio 5000 programming software. All you need for discrete, process, batch, motion, safety etc.
Version 29.00.01

Catalog Number Studio 5000 Logix Designer 

These release notes describe version information for ( 9324-RLDx ) Studio 5000 programming software. All you need for discrete, process, batch, motion,
safety etc., version 29.00.01.

System Requirements
This release has the following system requirements.

Hardware requirements for Studio 5000 Logix Designer version 29

The personal computer must meet these minimum requirements. Using a computer meeting or exceeding the recommended characteristics will improve
performance.

Characteristic Minimum Recommended

Processor Intel® Core 2 Duo at 2.8 GHz Intel Core i5 at 2.4 GHz


RAM Memory 4 GB 8 GB
Hard Disk Space 16 GB free 20 GB free
Graphics Device DirectX 9, with WDDM 1.0 or DirectX 9, with WDDM 1.0 or
higher driver higher driver

  

System Requirements Installation notes for Studio 5000 Logix Designer version 29

Review these notes before attempting to install this version of the Studio 5000® environment.

Prior to Installation

Keep the following considerations in mind before you install the Studio 5000 environment.

Be certain that no copies of Logix Designer application or RSLogix 5000 software are currently running.
Some antivirus software blocks or disrupts the Studio 5000 environment installation. If you experience difficulty, try disabling your antivirus software
before installation and re-enable it after you install the Studio 5000 environment.
Make sure that you have Administrator privileges on the personal computer on which you want to install the Studio 5000 environment. You will not be
able to complete the installation without these privileges.
Close all other applications before running the setup process.
Ensure that there are no pending workstation reboot requests from either Windows Update or any installation program. If there is a pending request,
reboot the workstation before starting the Studio 5000 environment installation.
The Logix Designer application has an optimized EDS subsystem. While this provides significantly better installation time, it can cause some
compatibility issues with other software packages. The following list shows some of these incompatibilities.

Installing one of the following software versions will cause prior versions of RSNetWorx and the DeviceNet Tag Generator to become inoperable.

Logix Designer application v21 and later
RSNetWorx v25 and later
RSLinx v3.51 and later
Add-On Profiles using Core 9.0 and later
DeviceNet Tag Generator

Important: During the installation of Logix Designer application, the installation
stops and a dialog box opens if an incompatible version of
RSNetWorx software is detected on the PC. Upgrade RSNetWorx
software to version 21 or later or uninstall it from your PC, and restart
the Studio 5000 environment installation.
Installing the Software

Follow these steps to install the Studio 5000 environment.
1.  Start your personal computer.
2.  Insert the Studio 5000 environment installation DVD into your DVD-ROM drive.

The DVD-ROM should auto-start. If it does not auto-start, run Setup.exe from the root of the DVD.
The Studio 5000 environment supports multiple versions of the programming software on a single personal computer. With version 10 and later of the
application, you may install as many of the later major versions as needed plus one version earlier than version 10 (for example, version 8.02).

3.  Follow the directions that appear on your screen.

Note that the Studio 5000 environment may need to update several system files early in the installation process. These updates will likely require you
to restart your personal computer. Be sure to close all other applications before clicking OK to initiate this reboot.
When prompted for a serial number, enter the 10-digit serial number identifying your software license; otherwise, enter any sequence of characters,
not longer than 10 characters.

Important: The 10-digit serial number is used to determine what functionality to
enable while in Grace Period mode. Entering an invalid serial number
will result in the application operating in Service Edition mode, upload
and download only, while in Grace Period mode.
4.  When prompted, click Activate Studio 5000 to complete the activation of the software.
5.  Follow the directions that appear on your screen and refer to the FactoryTalk Activation insert for additional information.

Important: When a valid activation cannot be located by the application, the
application will enter a seven-day activation grace period, during
which you will be able to run the application with full functionality. If this
seven-day grace period ends before a valid activation has been found,
you will no longer be able to start the Logix Designer application.
6.  Click Close to complete the installation.

When the setup utility finishes, an entry for the Studio 5000 environment appears in the program list in the Rockwell Software group.

7.  Remove the Studio 5000 environment DVD from the DVD-ROM drive and store it in a safe place.

Starting the Studio 5000 Environment

To start the Studio 5000 environment, from the Start menu, choose All Programs>Rockwell Software>Studio 5000 from the menu.

If Studio 5000 environment does not start up or run properly, keep the following in mind:

Do you have the correct version of RSLinx Classic software installed? RSLinx Classic software provides communication between the controller and
your personal computer.
Does your computer have enough memory? Running the Studio 5000 Engineering and Design Environment requires a minimum of 4 GB of RAM.

Uninstalling the Software

Follow these steps to uninstall the software when using the default Start menu on the Windows 7, Windows 8, Windows Server 2008R2, or Windows Server
2012 operating system.

1.  From Windows Explorer, navigate to Control Panel\Programs\Programs and Features.
2.  From this dialog box, double-click Studio 5000 Logix Designer <version>, and follow the prompts to uninstall.
3.  If all Studio 5000 Logix Designer <version> applications have been uninstalled, from this dialog box, double-click Studio 5000 Launcher, and follow
the prompts to uninstall.

Tip: This will uninstall only the Studio 5000 environment. Other components that were
installed with the Studio 5000 environment (such as Start Page Media, Online Books,
or RSLinx) must be uninstalled separately. 

  

System Requirements Software requirements for Studio 5000 Logix Designer version 29.00

Operating system and service pack compatibility:

This version of the Logix Designer application has been tested on the following operating systems:
Microsoft® Windows® 7 Professional (64-bit) with Service Pack 1
Microsoft 7 Home Premium (32-bit) with Service Pack 1
Microsoft Windows Server 2008 R2 Standard Edition with Service Pack 1
Microsoft Windows 8 Professional (64-bit)
Microsoft Windows 8.1 Professional (64-bit)
Microsoft Windows Server 2012 Standard Edition (server version of Windows 8)

Important: While the Windows 8 and Windows 8.1 operating systems run
on many touch-enabled devices, various features of the Logix
Designer application may not be touch-enabled. Most
functions are expected to work with touch, but the software has
only been tested with a keyboard and mouse.
This version of Logix Designer is expected to operate correctly on all other editions and service packs of the following operating systems but has not
been tested:
Microsoft Windows 7
Microsoft Windows Server 2008 R2
Microsoft Windows 8
Microsoft Windows Server 2012
Microsoft Windows Server 2012 R2

Logix Designer application may fail to launch if the Microsoft
Important: Windows 10 operating system is installed on your personal
computer.
 
The Start Page requires the Adobe Flash Player ActiveX Control to be installed prior to operation of the Start Page.

The Adobe Flash Player ActiveX Control can be downloaded from Adobe’s website at: http://get.adobe.com/flashplayer/

Note: For Windows 8 (and later), the Start Page will
work because those versions of Windows
have flash integrated.
For operating systems that support User Account Control (UAC), this version of the Logix Designer application was tested with UAC set to the most restrictive
level (Always notify for Windows 7). This version of the Logix Designer application is also expected to operate correctly when UAC is configured for any less
restrictive setting.

Running the Logix Designer application in conjunction with Fast-User Switching, in Safe mode, or via Remote Desktop is not supported.

Additional Software Product Considerations

Certain operations related to Factory Talk Security are slower on Windows 7 then they are on Windows 8.
Importing or Exporting a FactoryTalk Services Platform secured project
Securing a controller or a component of a controller with logical name or permission set
Clicking the Security tab in the Controller Properties dialog box.
FactoryTalk Services Platform is required to run this version of the Logix Designer application, as it performs some security functions in the Logix
Designer application.
RSLinx Classic communication software is required as part of the installation of the Logix Designer application, as it handles online communication with
controllers.
RSLinx Classic v3.80.00 is a component aligned to Logix Designer v28.01. RSLinx Classic v3.80.00 (CPR9 Service Release 8) has been tested, and
is compatible, with the following products:
FactoryTalk Services Platform v2.80.00
RSLinx Enterprise v5.80.00
RSNetWorx v25.00.00
FactoryTalk Activation Manager v4.00.00
RSLinx Classic v3.80.00, Logix Designer application v28.01, and device profiles that ship with the Logix Designer application v28.01 are not
compatible with:
RSNetWorx v11.00.00 or earlier
DeviceNet Tag Generator v11.0.20.0

RSNetWorx and the DeviceNet Tag Generator must be upgraded prior to installing these products.
FactoryTalk View SE software and RSLinx Enterprise communication software are not required to install the Logix Designer application; however, these
products are required in order to fully use the alarm capabilities introduced with RSLogix 5000 v16.
Microsoft .NET Framework 4 Language Pack is required to show the localized resources for the components developed by .NET for supported
languages of the Logix Designer application v21 and later. You need to download and install Microsoft .NET Framework 4 Language Pack or later on
the computer in which the Logix Designer application local language is installed.
Be sure to check the software requirements for other Rockwell Software® products that you intend to install to be sure that these products are also
compatible with the system.

Cross Product Revision Interaction

Before performing this upgrade, note that Logix5000 controllers and ControlLogix Motion modules in your system must contain a revision of firmware that is
compatible with this version of the Logix Designer application. However, earlier versions of network and I/O modules can operate in your system with the new
controller firmware contained in this release. Additionally, other software tools such as RSNetWorx for ControlNet and RSLinx Classic software have been
tested to be sure of compatibility with this version of software. Because of this, we recommend that you use the most current versions of these tools.

Rockwell Automation’s Product Compatibility and Download Center (PCDC) provides product-related downloads including firmware, release notes,
associated software, drivers, tools and utilities. Use the PCDC to determine how different products interact and to compare features and capabilities between
different series of products and associated firmware versions.

Use the following URL to browse to the PCDC:

http://compatibility.rockwellautomation.com/Pages/home.aspx

Firmware
Most of the modules supported by the Logix Designer application use Flash-ROM for the storage of firmware. If you possess a module that requires a
firmware change, the ControlFLASH software tool can be used to perform an update to this Flash-ROM. This software tool and the firmware images for most
of the supported modules are contained on a DVD-ROM shipped with Rockwell Software Studio 5000 Automation Engineering & Design Environment™.
Starting with version 10.00.00 of the application, you can access the ControlFLASH tool from within the application (from the Tools menu), or you can
automatically update your firmware as part of the project download process.

For additional information and assistance in performing a Flash-ROM update, review the ControlFLASH Firmware Upgrade Software User Manual,
publication 1756-UM105.

In addition, Rockwell Automation Services & Support has created a website from which you can download firmware images for Logix products. Go to
http://www.rockwellautomation.com/rockwellautomation/support/firmware/overview.page? for a list of popular firmware and other downloads, and to view
firmware compatibility for a given product. Your Logix Designer application serial number is required to complete the download. .

Firmware for ControlLogix Redundancy

The firmware associated with this standard release version of the programming software does not support redundancy. Software versions 8, 11, 13, 15, 16,
19, 20, and 24 support redundancy, but a separate firmware revision for the hardware in the local chassis is required. The redundancy firmware revisions
are released later than the standard revisions are released and are available for download via the same methods as for standard firmware. Go to
http://www.rockwellautomation.com/rockwellautomation/support/firmware/overview.page? for a list of popular firmware and other downloads, and to view
firmware compatibility for a given product. Your programming software serial number is required to complete the download.

Separately Installed I/O Configuration Profiles

With version 13 and later of the application, new I/O configuration profiles can be delivered independently from the application's release. These profiles can
be obtained independently and installed on a personal computer with the application to extend the I/O configuration support beyond the capabilities initially
supported when the application was released. This capability was initially limited to a single I/O platform, but with each new release, new I/O platforms are
added. If you are using one of the supported platforms and the configuration profile for a specific product was not included with the application, check with
the module or device vendor to determine if one is available. Additionally, I/O configuration profiles for modules or devices from Rockwell Automation are
generally provided with the application. However, at times, a module or device configuration profile may not be completed in time to make a release. In these
instances, the I/O configuration profiles will be made available via the Rockwell Automation Services & Support website
http://www.rockwellautomation.com/global/support/downloads.page? The following table provides a listing of versions of the application and their respective
ability to support the field addition of I/O configuration profiles.

I/O Platform I/O Profile Logix Designer/


Communication Methods RSLogix 5000
Supported Version

Compact I/O™ (1769) Local to CompactLogix 13.00 or later


CompactBlock™ Guard I/O™ DeviceNet 14.00, 16.00 or later
(1732, 1791DS)
CompactBlock Guard I/O EtherNet/IP 16.00 or later
(1791ES)
EtherNet/IP (1746-SLC IO) EtherNet/IP 20.00 or later
POINT I/O™ (1734) ControlNet, EtherNet/IP 15.00 or later
ArmorPOINT® I/O (1738) ControlNet, EtherNet/IP 15.00 or later
PointGuard I/O (1734) EtherNet/IP 17.00 or later

ControlLogix (1756) Local, ControlNet, 15.00 or later


EtherNet/IP
ControlNet Direct Connect ControlNet 15.00 or later
EtherNet/IP Direct Connect EtherNet/IP 15.00 or later
CompactLogix™ I/O (5069) EtherNet/IP 28.00 or later

New devices supported

The following table lists new hardware supported in this release.

  

Catalog Description Vendor


number

Emulate 5570 Studio 5000 Logix Emulate Controller Rockwell Automation


Bus module Bus module Ethernet/IP interface card Advanced Energy
Industries, Inc.
Thyro-P Thyro-P Ethernet/IP interface card Advanced Energy
Industries, Inc.

1734-VA11-2 2 Point 11mm Valve Buerkert Werke GmbH &


Co. KG
1734-VA11-8 8 Point 11mm Valve Buerkert Werke GmbH &
Co. KG
1734-IA11-2 2 Point 11mm Bi Valve Buerkert Werke GmbH &
Co. KG
1734-VA16-2 2 Point 16mm Valve Buerkert Werke GmbH &
Co. KG
1734-VA16-4 4 Point 16mm Valve Buerkert Werke GmbH &
Co. KG
1734-IA16-2 2 Point 16mm Bi Valve Buerkert Werke GmbH &
Co. KG
1734-VA11-3 3 Point 11mm Valve Buerkert Werke GmbH &
Co. KG

1734-IA11-8 8 Point 11mm Bi Valve Buerkert Werke GmbH &


Co. KG
SWG70 Ethernet/IP Wireless HART Fieldgate Endress+Hauser
HMS-EN2SE-R Ethernt to Serial linking device HMS Industrail Networks
AB
IB-E01 2 Zone controller (standard) Itoh Denki Co., Ltd.
IB-E03B 2 Zone controller (standard) Itoh Denki Co., Ltd.

IB-E04F 2 Zone controller (standard) Itoh Denki Co., Ltd.


1407-CGCM- Combination Generator Control Rockwell Automation
DLR Module, 2-port
1756-IT16 16-channel non-isolated thermocouple Rockwell Automation
analog input
1756-IR12 12-channel non-isolated RTD analog Rockwell Automation
input

5069-L306ER CompactLogix 5380 controller Rockwell Automation


5069-L306ERM CompactLogix 5380 controller Rockwell Automation
5069-L310ER CompactLogix 5380 controller Rockwell Automation
5069-L310ERM CompactLogix 5380 controller Rockwell Automation
5069-L310ER- CompactLogix 5380 controller Rockwell Automation
NSE
5069-L320ERM CompactLogix 5380 controller Rockwell Automation

5069-L330ER CompactLogix 5380 controller Rockwell Automation


5069-L330ERM CompactLogix 5380 controller Rockwell Automation
5069-L340ER CompactLogix 5380 controller Rockwell Automation
1756-L81E ControlLogix 5580 controller Rockwell Automation
1756-L82E ControlLogix 5580 controller Rockwell Automation
1756-L84E ControlLogix 5580 controller Rockwell Automation
1426-M5E-A PowerMonitor 5000 M5 Rockwell Automation

1426-M5E-DNT- PowerMonitor 5000 M5 with DeviceNet Rockwell Automation


A card
1426-M5E-CNT- PowerMonitor 5000 M5 with ControlNet Rockwell Automation
A card
1426-M6E-A PowerMonitor 5000 M6 Rockwell Automation
1426-M6E-DNT- PowerMonitor 5000 M6 with DeviceNet Rockwell Automation
A card

1426-M6E-CNT- PowerMonitor 5000 M6 with ControlNet Rockwell Automation


A card
1426-M8E-A PowerMonitor 5000 M8 Rockwell Automation
1426-M8E-DNT- PowerMonitor 5000 M8 with DeviceNet Rockwell Automation
A card
1426-M8E-CNT- PowerMonitor 5000 M8 with ControlNet Rockwell Automation
A card

ETHERNET- Generic Ethernet/IP safety and standard Rockwell Automation


SAFETY- module
STANDARD-
MODULE
Electronic Data Sheets

The version of RSLinx Classic software provided with this version of the Logix Designer application includes an updated set of electronic data sheet (EDS)
files for Rockwell Automation products. Installing this software ensures that RSLinx Classic software and RSNetWorx software will be able to work with the
new revisions of firmware. These EDS files are also available separately by contacting Rockwell Automation Services & Support (phone +1 440-646-3434),
or using the Internet (http://www.rockwellautomation.com/resources/eds/).

To upload EDS file from the device within RSLinx Classic, perform the following steps:

  
1.  Connect the device to the computer.
2.  Open RSLinx Classic, and browse for the device in RSWho.
3.  Once you find the device, right-click it, and select Upload EDS file from device.

  

System Features
This release includes the following system features.

Controller Message to Self Addition

In the v29.00 release of Logix Designer, a Message instruction can be configured to perform a message to the controller itself by using "THIS" in the path for
the MSG (Message to Self) instruction.

The following table lists functions that a controller can perform on itself.

Function 5580 controllers 5380 controllers


LCD disable for 5380 and See Knowledgebase article KB869648.
5580 controllers
Disable the embedded See Knowledgebase See Knowledgebase article
webpage article KB869649. KB869651.

Disable the embedded See Knowledgebase See Knowledgebase article


Ethernet port article KB869650. KB869652.
Click the following URL to browse to the Rockwell Automation Knowledge Base:

https://rockwellautomation.custhelp.com/app/answers/list

Powerflex 755

The Powerflex 755 feature development adds 24-Bit Resolution capability to supported feedback devices and Servo I/O support for Powerflex 755 CIP
Motion drives. The 755 CIP Motion drives have also been updated to accept new 11 and 22 Series servo I/O cards that should be placed in slot 7.

Dual configurable Ethernet ports

Controllers such as the CompactLogix 5380 support dual configurable Ethernet ports. Dual configurable Ethernet ports allow pairs of physical Ethernet ports
to be configured in either a Linear/DLR or Dual-IP mode. When configured for Linear/DLR mode, both Ethernet ports reside on the same Ethernet network
and share IP settings. When configured for Dual-IP mode, both Ethernet ports reside on a different Ethernet network with their own IP settings. 

Support for PanelView 5000 HMI Button Control

The 5x80 family of controllers now supports HMI button control for the PanelView 5000. The new HMIBC instruction interacts with the HMI and provides the
following benefits:

Reduces lag and improved accuracy for manual jog operations.
Provides greater flexibility than physical buttons with comparable performance.
Eliminates the need for custom logic to verify active communications.

Instruction-based alarm support

Instruction-based alarms (ALMA, ALMD) are supported on the 5x80 family of controllers in this release.

String Literals

String literal is the representation of a fixed string value within Logix Designer programming languages. Use the string literal feature to assign string literals to
a string tag, or assign a string tag to another string tag in the following editors: Structured Text, Ladder Logic, and embedded Structure Text within
Sequential Function Chart. This feature is available for the 5x80 family of controllers only.

Kinetix 5700-VPC motor support

The Logix Designer application supports selection, configuration, and control of Rockwell Automation's new Kinetix VPC motors with Interior Permanent
Magnet (IPM) technology.
Controller Properties updates

Improved controller capacity calculation

The controller capacity algorithm has been improved to provide a more accurate calculation of the available memory of the controller.
Memory tab has been renamed

The Memory tab on the Controller Properties dialog box has been renamed the Capacity tab.
Node Count indication

The Capacity tab contains a Node Count for controllers that have limits on the number of Ethernet nodes they support in the I/O Configuration tree. The
Node Count feature shows the maximum number of Ethernet nodes supported by the controller and number of used Ethernet nodes in the I/O Configuration
tree.

  

Corrected Anomalies
This release corrects the following anomalies.

A JSR instruction with SBR instruction and RET instruction does not pass back data thru the RET correctly (Lgx00181341)

Corrected Anomaly with Studio 5000 Logix Designer v28.01

When using a JSR instruction with the SBR instruction (to pass parameters to the routine) and the RET instruction (to pass parameters from the routine)
under certain data type formats, the data is not fully passed back thru the RET correctly. This occurs when then the RET contains a 1 dimensional member
UDT. See Rockwell Automation Knowledgebase Tech Note #824690. (Lgx00181341)

Add instruction error code 111, "An Axis With Maximum Acceleration of Zero is Invalid" (Lgx00179479)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Add instruction error code 111, "An Axis With Maximum Acceleration of Zero is Invalid." (Lgx00179479)

Add On Instruction with multiple Inputs with the same variable has one instance with the wrong value (Lgx00178841, Lgx00178900)

Corrected Anomaly with Studio 5000 Logix Designer v28.01

When an Add-On Instruction is called in a periodic task and the Add-On Instruction has multiple Inputs with the same variable, one instance of input has a
value of 0 instead of 1. (Lgx00178841, Lgx00178900)

Alias bit is not updated (Lgx00180466)

Corrected Anomaly with Studio 5000 Logix Designer v28.01

An alias bit is not updated in the same rung in a project using the ControlLogix 5580 controller. (Lgx00180466)

Alias tag definitions sometimes lost during simultaneous online edits on same controller (Lgx00171058)

Corrected Anomaly with Studio 5000 Logix Designer v29.00 and v28.02

Alias tag definitions are sometimes lost when multiple users perform online edits on the same controller. (Lgx00171058, Lgx00181031)

Cannot overwrite existing Add-On Instruction when imported and existing AOIs have the same edit date (Lgx00183585)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When you import an Add-On Instruction while offline, you cannot overwrite an existing AOI when the imported and existing AOIs have the same edit date.
(Lgx00183585)

Change button sometimes missing from Module Properties dialog box (Lgx00175573)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The Change button is sometimes missing from the Module Properties dialog box. (Lgx00175573)

Check box in Select Module Type dialog box misplaced in 150% resolution (Lgx00128244)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The check box in the Select Module Type dialog box is misplaced in 150% resolution. (Lgx00128244)
Clearing Enable Alarm check box does not disable High and Low alarms (Lgx00179379, Lgx00156945, Lgx00158243, Lgx00160986)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Clearing the Enable Alarm check box on the Alarm tab in the 1794-IF8IHNFXT Module Profile dialog box does not disable the High and Low alarms when
Current Range is configured for 4 to 20 mA - Milliamps x 1000 (2000 to 22000). (Lgx00179379, Lgx00156945, Lgx00158243, Lgx00160986).

  

CodeMeter installation sometimes fails (Lgx00179433)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

CodeMeter installation sometimes fails. (Lgx00179433)

Commissioning tests stay in testing phase and do not complete (Lgx00177511)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Commissioning tests (hookup, motor analyzer, autotune) stay in the "testing" phase and do not complete when the default Torque Bandwidth on the
Torque/Current Loop tab in the Axis Properties dialog box is set to 0 Hz. (Lgx00177511)

Controller serial number sometimes overwritten when loading project from SD card (Lgx00183376)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When you load a project from the SD card, the controller serial number is sometimes overwritten. (Lgx00183376)

Copy-paste errors on Function Block instructions and Add-On Instructions in Function Block routines (Lgx00182706, Lgx00182837)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When copying a Function Block instruction and an Add-On Instruction in a Function Block routine and pasting in a new sheet or routine, only the Add-On
Instruction is pasted in the new sheet or routine. The Function Block instruction is not pasted in the sheet or routine and an error is generated.
(Lgx00182706, Lgx00182837)

Core and first-party Add-On Profiles contain invalid version numbers (Lgx00172292, Lgx00156346)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Core and first-party Add-On Profiles contain invalid version numbers. (Lgx00172292, Lgx00156346)

Counts are incorrect for Current Range selections on Configuration tab in Module Properties Report dialog box (Lgx00153764)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Counts are incorrect for the Current Range selections on the Configuration tab in the Module Properties Report dialog box. (Lgx00153764)

Creating alias for Cam, Cam Profile, or Output Cam tag generates error (Lgx00180076)

Corrected Anomaly with Studio 5000 Logix Designer v29.00 and v28.02

Creating an alias for a Cam, Cam Profile, or Output Cam tag generates an error. (Lgx00180076, Lgx00180235)

Creating new project in v26 and adding CIP drive to the I/O structure causes project to fail to download (Lgx00168210, Lgx00179057)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When you create a new project in version 26 of the Logix Designer application and add a CIP drive to the I/O structure, the project does not download to the
controller. (Lgx00168210, Lgx00179057)

Download of safety projects with comments (Lgx00177998)

Corrected Anomaly with Studio 5000 Logix Designer v28.01
Rung comments in a safety project do not get downloaded to the controller. (Lgx00177998)
EDS AOP feature reports error when device is added with configuration data type smaller than configuration values (Lgx00154242)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The EDS AOP feature reports an error when you add a device for which the configuration data type is smaller than the configuration values. (Lgx00154242)

Empty Action body while editing a Sequential Function Block routine online (Lgx00178412)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

An empty Action body while editing a Sequential Function Block routine online. See Rockwell Automation Knowledgebase Tech Note #823196.
(Lgx00178412)

Enhanced Cam Editor not fully disabled even when Maintain Project permission has been denied (Lgx00029563)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The Enhanced Cam Editor is not fully disabled even when Maintain Project permission has been denied for the user. (Lgx00029563)

Errors and Warnings pane on Import Configuration dialog box sometimes fails to display errors (Lgx00163240)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The Errors and Warnings pane on the Import Configuration dialog box sometimes fails to display expected errors. (Lgx00163240)

Fatal error occurs when opening an Equipment Sequence diagram (Lgx00186631)

Corrected Anomaly with Studio 5000 Logix Designer v29.00.01

Fatal error occurs when opening an Equipment Sequence diagram. (Lgx00186631)

  

Fatal error occurs when the trend configuration changes (Lgx00182252)

Corrected Anomaly with Studio 5000 Logix Designer v29.00 and v28.02

A fatal error occurs when the trend configuration changes. (Lgx00182252, Lgx00182426)

Fatal error when selecting tags in Function Block (Lgx00176849)
Corrected Anomaly with Studio 5000 Logix Designer v29.00

Fatal error when selecting tags using the Tag drop down list in a Function Block (Lgx00176849)

Fatal error while searching for text in an Equipment Sequence diagram. (Lgx00177916)

Corrected Anomaly with Studio 5000 Logix Designer v28.01

A fatal error can occur when using the Find dialog box to search for text in an Equipment Sequence diagram. (Lgx00177916, Lgx00177497)

Fatal error occurs when deleting uncommitted row in Connection Configuration dialog box

Studio 5000 Logix Designer v28

When working with a program parameter in the Connection Configuration dialog box, if your cursor is in the Name field and you press the Shift +Tab
keys to select the entire row and then press the Delete key to delete the row, a fatal error occurs. (Lgx00170925)

Find All command fails to find tag names embedded in Structured Text (Lgx00168112)

Anomaly

Studio 5000 Logix Designer v27.00

The Find All command fails to find tag names embedded in Structured Text. (Lgx00168112)

  
 

Find All search limited to Edit Zones produces incorrect results (Lgx00139950)
Corrected Anomaly with Studio 5000 Logix Designer v29.00

Incorrect search results appear in the Structured Text (ST) Editor and in the Sequential Function Chart (SFC) Editor when you conduct a Find All search and
limit the search to Edit Zones. (Lgx00139950)

Firmware cannot be updated after licensed connection key has been revoked (Lgx00168994, Lgx00169634, Lgx00156630)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When the controller contains firmware that has revoked the licensed connection key for older revisions of software, those older revisions of software cannot
establish a connection with the controller in order to flash the controller back to a compatible revision of firmware. (Lgx00168994, Lgx00169634,
Lgx00156630)

GCC Compile Error occurs when project contains ALMA instructions in FBD routine (Lgx00137675)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

A GCC Compile Error occurs when you download a project that contains ALMA instructions in FBD routine. (Lgx00137675)

Go To dialog context varies within FBD Editor (Lgx00143603)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The Go To dialog context varies within the Function Block Diagram (FBD) Editor. (Lgx00143603)

Guest Users cannot flash 1756-L7x controller firmware using Autoflash (Lgx00183696)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Guest Users cannot flash 1756-L7x controller firmware using Autoflash. (Lgx00183696)

Handling of Source Key names is different in v28 project than in a v24 project (Lgx00179531)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The behavior of handling Source Key names is different in a v28 project than in a v24 project. (Lgx00179531)

Import Configuration Error pane fails to display expected errors and warnings (Lgx00163240)

Anomaly

Studio 5000 Logix Designer v27.00

The Errors and Warnings pane on the Import Configuration dialog box sometimes fails to display expected errors. (Lgx00163240)

  

Import secured and bound L5k file, always displays warning that PAS out of date (Lgx00182839)

Corrected Anomaly with Studio 5000 Logix Designer v28.01

Importing an L5K file that is secured and bound, Logix Designer application displays a warning message that the Primary Action Set (PAS) is out of date.
(Lgx00182839)

Increase Add-On Instruction InOut parameter limit to 64 and decrease AOI nesting levels to 16 (Lgx00181291)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Increase AOI InOut parameter limit to 64 and decrease AOI nesting levels to 16. (Lgx00181291)

Infinite loop sometimes prevents import of L5X file (Lgx00179816)

Corrected Anomaly with Studio 5000 Logix Designer v29.00 and v28.02

An infinite loop, triggered by a module that has bad data for an input or output tag, sometimes locks the import and prevents import of an L5X file.
(Lgx00179816, Lgx00179941)

Invalid characters in exported XML project file causes import to fail (Lgx00172128)

Corrected Anomaly with Studio 5000 Logix Designer v29.00
Invalid characters in an exported XML project file causes import to fail for that project. (Lgx00172128)

Issue with alias of string arrays (Lgx00179379)

Corrected Anomaly with Studio 5000 Logix Designer v28.01

When a string is aliased to another string which is a member of a string array, the string values are inserted only in even number indices. (Lgx00178379)

Logix Designer fails to set a default value for ProgrammaticallySendEventTrigger (x168499)

Anomaly

Studio 5000 Logix Designer v27.00

When a project is imported, Logix Designer fails to set a default value for ProgrammaticallySendEventTrigger and the import fails. (Lgx00168499)

  
 

Logix Designer fails to set default value for ProgrammaticallySendEventTrigger and import fails (Lgx00168499)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When a project is imported, Logix Designer fails to set a default value for ProgrammaticallySendEventTrigger and the import fails. (Lgx00168499)

Message dialog box for Add-On Profile time synch error should not contain Help button (Lgx00183837)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The Message dialog box for an Add-On Profile time synch error should not contain a Help button. (Lgx00183837)

Module Info page shows wrong string (Lgx00006004)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When the internal state attribute in the Device Identity object is 0, the Module Info page shows the string "Self-Test," but it should display "Self Test or State
Unknown." (Lgx00006004)

Output data remains high for inhibited modules during testing (Lgx00177604)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Output data remains high for inhibited modules during testing. (Lgx00177604)

Passive hookup tests do not run when Kinetix 6200 drive is in Shutdown state (Lgx00183678)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Passive hookup tests do not run when the Kinetix 6200 drive is in the Shutdown state. (Lgx00183678)

Performance problems during various security actions related to Wibu on Windows 7

Known Anomaly First Identified in Studio 5000 Logix Designer v28

Corrected Anomaly with Studio 5000 Logix Designer v29.00 and v28.02

The Logix Designer application can take from 18 to 20 seconds to respond when a project is secured at the controller level with the Logical Name option or
the Permission Set option in the Controller Properties dialog box Security tab. This performance issue can be experienced when working with the
properties of secured components and when editing permissions in FactoryTalk Service Platform. These performance issues have been traced to Wibu
performance on Windows 7. (Lgx00175521, Lgx00171830)

  

Position Unwind not calculated correctly on Axis Parameter List dialog box (Lgx00179155)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Position Unwind is not calculated correctly on the Axis Parameter List dialog box. (Lgx00179155)
Project containing Add-On Instructions fails to download to safety controller on second attempt (Lgx00168232)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Project containing Add-On Instructions fails to download to a safety controller on second attempt. (Lgx00168232)

Project containing AOIs fails to download to a safety controller on second attempt (x168232)

Anomaly

Studio 5000 Logix Designer v27.00

A project containing an Add-On Instruction downloads with errors under the following conditions:

The project is downloaded to a safety controller with the Download Project Documentation and Extended Properties check box unselected.
The project is uploaded from the controller and the Logix Designer application is taken offline from the controller.
When offline, the project is downloaded to the safety controller again with the Download Project Documentation and Extended Properties check box
unselected, and the following error occurs:

Invalid signature ID. Reseal instruction to resolve. (x168232)

  
 

Project documentation, extended properties, and custom properties not included when copy-pasting project components from one
language-switching project to another (Lgx00162447)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Project documentation, extended properties, and custom properties are not included when you copy and paste project components from one language-
switching project to another. (Lgx00162447)

Remove Alarm Buffer object from GSV/SSV instructions (Lgx00138886)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Remove the Alarm Buffer object from the GSV/SSV instructions. (Lgx00138886)

Removing SD card from controller while flashing firmware can lock up the controller (Lgx00170010)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Removing the SD card from the controller while flashing the firmware can lock up the controller. (Lgx00170010)

Safety Lock LED sometimes fails to show correct status after you restore project from SD card (Lgx00178417)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The Safety Lock LED sometimes fails to show the correct status after you restore a project from the SD card. (Lgx00178417)

Safety modules fail to instantiate after installation of Ethernet module AOP profile 10.00.3664 (Lgx00170167)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

After installing Ethernet module AOP profile 10.00.3664, safety modules fail to instantiate. (Lgx00170167)

Sealed AOI in different language fails verification (Lgx00177571)

Corrected Anomaly with Studio 5000 Logix Designer v29.00
When an AOI that was sealed in a project that used a specific documentation language (English, for example) is imported into a project where the
documentation language is different (Italian, for example), the project cannot be verified. (Lgx00177571)

Important: As a result of a correction of this anomaly, AOI signatures that were signed in a previous version of RSLogix 5000 or Studio 5000 Logix Designer
will break upon import or project conversion into version 29.00 of Studio 5000 Logix Designer. You must un-seal and then re-seal each AOI to get a new
signature.

Size of .ACD file increases following download using v21.03 (Lgx00157573, Lgx00152925)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The size of an .ACD file increases dramatically following download using Logix Designer version 21.03. (Lgx00157573, Lgx00152925)
Stop Action nomenclature misleading on CIP Actions tab (Lgx00165639, Lgx00146859)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Stop Action nomenclature on CIP Actions tab is misleading. (Lgx00165639, Lgx00146859)

String values sometimes inserted only in even number indices (Lgx00178120)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When a string is aliased to another string which is a member of a string array, the string values are inserted only in even-number indices. (Lgx00178120).

  

Tool tip for undefined tag in Ladder Editor needs improvement (Lgx00176367)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

The tool tip for an undefined tag in the Ladder Editor needs improvement. (Lgx00176367)

Unable to import sealed Add-On Instructions when online with the controller (Lgx00185323)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

Unable to import sealed Add-On Instructions when online with the controller. (Lgx00185323)

When two public parameters are aliased to same local program scoped tag Logix cannot find the tag (Lgx00175994)

Corrected Anomaly with Studio 5000 Logix Designer v29.00 and v28.02

When two public parameters are aliased to the same local program scoped tag, Logix cannot find the tag whose physical address is the tag that the second
public parameter points to. (Lgx00175994, Lgx00184548).

  

When you lock a safety task and generate a signature, Logix deletes all comments in safety task (Lgx00177873)

Corrected Anomaly with Studio 5000 Logix Designer v29.00

When you lock a safety task and generate a signature, the Logix Designer application deletes all comments made in the safety task. (Lgx00177873)

Known Anomalies
This release has the following known anomalies.

1769-L35 Controller adds 100 years to date on power-up (Lgx00182366)
Studio 5000 Logix Designer v29.00

When a 1769-L35 controller powers up, it sometimes adds 100 years to the displayed date. (Lgx00182366)

Follow these steps to correct the issue:
1.  Power down the controller.
2.  Disconnect the controller battery.
3.  Wait five minutes.
4.  Reconnect the battery.
5.  When the controller powers up, re-download the project.

Access Denied dialog box does not appear when users without FactoryTalk Security access attempt to modify Motion Configuration
(Lgx00184951)

Studio 5000 Logix Designer v29.00

When a user without Motion: Modify Configuration security credentials attempts to modify the motion configuration, an Access Denied dialog box does not
appear. (Lgx00184951)
Cannot delete tag from Safety project (Lgx00184580)

Studio 5000 Logix Designer v29.00

Users with correct security credentials cannot use the Cut option to delete a tag from a safety program. (Lgx00184580).

As a workaround, copy and paste the tag and then use the Delete option to remove the original tag from the program.

Changing 5380 Controller EtherNet/IP Mode incorrectly modifies MSG path port (Lgx00184756)

Studio 5000 Logix Designer v29.00

When you change the Ethernet/IP Mode on a 5380 controller, the Logix Designer application sometimes incorrectly modifies the communication path for an
MSG instruction. (Lgx00184756)

Changing Data Context for AOI does not change metadata context (Lgx00185356)

Studio 5000 Logix Designer v29.00

When you create a description for a parameter in an Add-On Instruction and then change that description in one instance of the AOI in the Tag Editor, no
modification of the description appears for that instance in Parameters and Local Tags when the scope is set to Add-On. (Lgx00185356)

  

Controller displays incorrect date and time (Lgx00182342)

Studio 5000 Logix Designer v29.00

The controller sometimes displays an incorrect date and time: the year is displayed as a large number (for example, 586,384) and the month, day, and time
are incorrect. (Lgx00182342).

  

Error setting STRING values

Studio 5000 Logix Designer v28

When editing existing standard STRINGs or entering a new STRING, if there is a non-alphanumeric character in the STRING, such as a space, period or
apostrophe, error message sometimes open that indicate that the length of the string is too long. If the non-alphanumeric characters are removed, the
STRING can be saved. (Lgx00159141)

Filter buttons missing when importing rungs into an AOI (Lgx00156489)

Anomaly

Studio 5000 Logix Designer v27.00

When you import rungs into an Add-On Instruction, the following filter options are missing when you click Final Name on the Configure Tag References pane
of the Import Configuration dialog box:

• Input

• Output

• InOut

• Local Filter

Only the Show controller tags and Show program tags check boxes are available. (Lgx00156489)

  
 

Instructions incorrect in Structured Text Editor when using drag-and-drop on more than one instruction (Lgx00184727)

Studio 5000 Logix Designer v29.00

When you copy instructions from the Ladder Editor to the Structured Text Editor using drag-and-drop, the instructions are incorrect in the Structured Text
Editor when you copy multiple instructions at the same time. (Lgx00184727)

As a workaround, copy the instructions from the Ladder Editor to the Structured Text Editor by copying them one at a time.

Labels are cut off and dislocated in BOOTP-DHCP Server applications (Lgx00152848)
Anomaly
Studio 5000 Logix Designer v26

When the font size in Windows 7 is set to 125%, the labels in the Network Settings and DHCP properties of BOOTP-DHCP Server application are cut off,
making them unreadable. They are also dislocated, where they do not match with the proper input fields.

Link error sometimes occurs after new module has been created (Lgx00179911)

Studio 5000 Logix Designer v29.00

When you delete a module from a project and create a new one with the same name as the deleted module, the Logix Designer application sometimes
reports a link error for the module. (Lgx00179911)

The following conditions must also be true:
A 5580 controller is configured in the I/O tree under Ethernet.
The project contains a logic reference, such as a GSV or SSV instruction, to the deleted module.

As a workaround, export the project and then import it into a new program.

Low controller memory can prevent connection to the controller (Lgx00179908)

Studio 5000 Logix Designer v29.00

When controller data and logic memory are low, Logix Designer application sometimes reports that it cannot connect to the controller. (Lgx00179908)

MGSD can cause Group Overlap faults in systems with large number of axes (Lgx00174272)

Studio 5000 Logix Designer v29.00

The Motion Group Shutdown (MGSD) instruction can cause a Motion Group Overlap fault when used in a project that contains a large number of axes and
the Coarse Update Rate is set too low. (Lgx00174272)

As a workaround, increase the motion group's coarse update rate.

  

New FactoryTalk Security users sometimes fail to appear in FactoryTalk Security when Logix Designer is open (Lgx00184021)

Studio 5000 Logix Designer v29.00

When you add a new user in FactoryTalk Security while the Logix Designer application is open, the new user sometimes does not appear in FactoryTalk
Security until you close the Logix Designer application. (Lgx00184021)

Output state user defined value must be 0 when Hold Last State is selected

Studio 5000 Logix Designer v28

A module fault on the 1758-OF8 of: (Code 16#0009) Module Configuration Rejected: Parameter error. Additional Fault Code 16#000e will remain in
a fault state after a reset of the slot and when the OK LED is green. As a workaround, the Output State User Defined value must be set to 0 when Hold Last
State is selected in the 1756-OF8 module. (Lgx00164117)

Phase Manager and Sequence Manager sometimes show different phase states (Lgx00183769)

Studio 5000 Logix Designer v29.00

The Phase Manager and the Equipment Sequence Manager sometimes show a different state of phase when the controller is switched from run to program
mode. (Lgx00183769)

Possible communication with wrong device on 5380 controller when changing Ethernet/IP Mode (Lgx00185070)

Studio 5000 Logix Designer v29.00

When you change the Ethernet/IP Mode from Dual-IP to Linear/DLR on a controller that supports Dual-IP, it is possible that miscommunication can occur if
multiple devices on your network use the same IP address on different subnets. (Lgx00185070)

The following example shows one possible configuration that could lead to miscommunication:

In Dual-IP mode, on port A1, the address of Target A on your network is 192.168.1.11. Target A is part of your project configuration. On a separate subnet
via a gateway, another device, Target B, is assigned the same address. Target B is not part of your project configuration.

When you make the offline change to the project, Target A is added to the project I/O tree. When you download the project to the controller and switch to
Linear/DLR mode using port A1/A2, the controller adopts the port A2 IP settings, with subnet, as the controller IP settings. The device in the I/O tree at
192.168.1.11 is not on the same subnet as the controller, so any communications to the original Target A are directed to the gateway and are sent to Target
B. Although Target B was not part of your project configuration, it could receive communication sent to Target A.

Several object-backed tags can be incorrectly created as local tags (Lgx00183744)

Studio 5000 Logix Designer v29.00

The Logix Designer application normally reports an error and does not allow you to configure an object-backed tag as a local tag. However, for the following
data types, the Logix Designer application incorrectly allows you to configure an object-backed tag as a local tag:
ALARM_DIGITAL
ALARM_ANALOG
HMIBC
COORDINATE_SYSTEM

(Lgx00183744)

Standard tags mapped to safety tags sometimes cannot be edited in secure project (Lgx00184776)

Studio 5000 Logix Designer v29.00

Users attempting to edit a standard tag that is mapped to a safety tag in a secured project sometimes cannot edit the standard tag. (Lgx00184776)

Tag properties sometimes disappear from Properties pane for AOI tags (Lgx00184764)

Studio 5000 Logix Designer v29.00
When you update or insert a value for an Add-On Instruction tag and then click outside the Tag editor, the tag properties disappear from the Tag Properties
pane. The tag properties reappear when you select the updated tag. (Lgx00184764)

Trend restarts from the beginning when Pause is clicked (Lgx00184775)

Studio 5000 Logix Designer v29.00

When you click Pause during trending, the trend sometimes starts over from the beginning. (Lgx00184775)

When converting 5x80 projects, Invalid hostDataTypeID can cause fatal error (Lgx00185197)

Studio 5000 Logix Designer v29.00

When you convert a project for a 5x80 controller, a fatal error sometimes occurs when the compiler encounters an invalid hostDataTypeID when attempting
to generate the UDI. (Lgx00185197)

When creating Event task, Event configuration list can show unexpected module tags (Lgx00179922)

Studio 5000 Logix Designer v29.00

When you create a task in a project and set the task type to Event and set the trigger to Module Input Data State Change, module tags appear unexpectedly
in the Tag drop-down menu. (Lgx00179922)

When FactoryTalk Security Modify Logic access is denied, FBD properties are sometimes inaccessible (Lgx00184895)

Studio 5000 Logix Designer v29.00

When Modify Logic access is denied but View Logic access is allowed in FactoryTalk security settings, users sometimes cannot open the Properties dialog
box in the Function Block Diagram editor. (Lgx00184895)

As a workaround, select the FBD instruction and press Alt + Enter to open the Properties dialog box.

Functional Changes
This release has the following functional changes from the previous release.

Functional Changes in this release for Studio 5000 Logix Designer version 29

The following items explain changes that have been made in this or earlier releases in the way that the Logix Designer application works, compared to earlier
releases.

Studio 5000 Logix Emulate

In version 29.00 of Studio 5000 Logix Designer, RSLogix 5000 Emulate software has been renamed to Studio 5000 Logix Emulate software. The catalog
number has changed from Emulate to Emulate 5570.

Upload button removed from Studio 5000 Launcher

In version 29.00 of Logix Designer, the Upload button has been removed from the Studio 5000 launcher.

Controller Properties Project tab updates

The Download Project Documentation and Extended Properties check box and the Download Custom Properties check box are now on the
Controller Properties Project tab. They are selected by default. Rockwell Automation recommends that you always download project documentation. See
Download project Documentation and Extended properties in Application notes on page 1 for more information.

Changes to Add-On Instructions (AOI)

The following changes have been made to Add-On Instructions in this release:

Signatures break for AOIs from earlier releases: As a result of the correction for anomaly Lgx00177571, when you use version 29.00 or later to open
a project from a release earlier than version 29.00, the signature breaks for any AOI included in the project. In the same way, when you import an AOI
from a project created in a release earlier than version 29.00, the signature breaks for that AOI. You must un-seal and then re-seal each AOI to get a
new signature.
Nesting limit: The nesting limit for AOIs in Logix Designer v29 has decreased from 25 levels deep to 16 levels.
InOut parameters: The number of InOut parameters permitted within an AOI in Logix Designer v29 has increased from 40 to 64 InOut parameters.

Instruction behavior changes when replacing controllers

Behavior changes occur for some instructions when you replace a ControlLogix 5560 or ControlLogix 5700 controller with a ControlLogix 5580 controller, or
replace a CompactLogix 5370 controller with a CompactLogix 5380 controller. Refer to the Replacement Guidelines: Logix5000 Controllers Reference
Manual, publication 1756-RM100, for detailed considerations and explanations of the changes that you may have to make to your project when replacing
controllers.

Firmware Supervisor with firmware in new DMK file format

In December 2015, firmware for modules may be provided in a new Device Management Kit (DMK) file format, for example, 1756-L73_28.011.dmk. Firmware
Supervisor only supports firmware with the NVS and BIN file format.
To use Firmware Supervisor with hardware modules whose firmware is provided in a DMK file format, you must first extract the NVS and BIN files from the
DMK file using the DMK Extraction Tool that is installed with ControlFLASH v13.00. Refer to the ControlFLASH online help for instructions on how to use the
DMK Extraction Tool.

Controller Memory Changes

This revision of Logix5000 controllers may require more memory than earlier revisions. Before upgrading to this revision, check the amount of unused
memory that you have in the controller using the Estimate tool on the Capacity tab of the Controller Properties dialog box.

For additional information about controller memory issues refer to the Knowledgebase at: http://www.rockwellautomation.com/support/.

For the 5x80 family of controllers, the Capacity tab in the Controller Properties dialog box has been redesigned to show the size of the source code of
your application rather than the physical memory the application uses to run. As a result, a new term ‘block’ has been defined that represents a unit of
executable code.

The block units are only used for application source code sizes. Data structures and messages are still sized in bytes to support the design and
implementation of communication interfaces with other devices.

For more information on migrating to a 5x80 controller, refer to the publication on the Literature Library, Replacement Guidelines: ControlLogix 5560/5570
Controller to ControlLogix 5580 Controller (1756-RM100).

Import/Export Changes

Import/Export Formats – Logix Designer application provides the following five different Import/Export file formats:

Full project exported to an ASCII text file (.L5K)
Full project exported to an Extensible Markup Language (XML) formatted file (.L5X)
Tag definitions and program documentation exported to ASCII text files in a Comma Separated Value (.CSV) format

Tip: For the v24.00, v26.00 and v27.00 releases, program parameter
connections are not included in the .CSV file.
Tag definitions and program documentation exported to ASCII text files in a Tab Separated Value (.TXT) format
Partial project exported to an Extensible Markup Language (XML) formatted file (.L5X)

Each of these formats is documented in Logix5000 Controllers Import/Export Reference Manual, publication 1756-RM084, which also describes modifications
that can be made for backward compatibility of export format files.

Import/Export Major and Minor Revision – Beginning with the version 9.00 release, the Import/Export version number is interpreted as a Major Revision and a
Minor Revision (major.minor). Each version of Logix Designer application exports *.L5K files with specific IE Version numbers. Logix Designer application
imports any *.L5K file with the same Major Revision number and the same or lower Minor Revision number. The Major Revision is incremented when there is
a significant change that affects compatibility with earlier versions. The Minor Revision is incremented whenever there is a change in the file format (for
example, a new module, an attribute is added, or the set of options for an attribute is changed). Generally, the Minor Revision is incremented for each
release.

The Import/Export version number for this version of Logix Designer application has been changed. If you export files (*.L5K) that were created in versions of
RSLogix 5000 software with an Import/Export version number less than 2, and you attempt to import them in the latest version of the application, an error is
generated. The error message is "Failed to open file *.L5K. Syntax error found while scanning the Import file." To work around the anomaly, edit the *.L5K file
and change the line IE_VER := x.x;, where x.x may be 1.0, 1.1, or 1.2 to IE_VER := 2.11;, save the file and retry the import.

Release Version Import/Export
Version

29.xx 2.20
28.xx 2.19           

27.xx 2.18
26.xx 2.17

24.xx 2.15

23.xx 2.14
21.xx 2.12

20.xx 2.11
19.xx 2.10

18.xx 2.9
17.xx 2.8

16.xx 2.7
15.xx 2.6

14.xx 2.5

13.xx 2.4
12.xx 2.3

11.xx 2.2
10.xx 2.1

9.00 2.0
5.02 1.2

2.xx, 6.xx, 7.xx, 8.xx 1.1

1.21, 1.23 1.0
1.10, 1.11 0.4
Import or Paste Error Messages – When attempting to import or paste between versions, if the IE version is invalid, an error message is displayed in the
results window. If the major or minor revision number is larger than accepted, the message "Error Line xxx: Invalid IE Version number. Cannot import/paste
into older version of RSLogix 5000" is displayed. If the major revision number is smaller than accepted, the message "Error Line xxx: Invalid IE Version
number. See Release Notes for more detail" is displayed.

Import/Export Format for Structured Text Routines – The Import/Export format for Structured Text routines was changed in version 12. The STX_ROUTINE
and END_STX_ROUTINE delimiters were changed to ST_ROUTINE and END_ST_ROUTINE, respectively. Version 12 or later of the application continues to
recognize the obsolete STX_ROUTINE when importing, but exports using the new format. Any attempt to Copy/Paste, Drag/Drop, or Import a version 12 or
later Structured Text routine into version 11 software will fail.

Online Editing Views for SFC and ST – With the addition of online editing for SFC and ST in version 13, new LOGIC and END_LOGIC delimiters were added
to identify Original, Pending Edits, and Test Edits views in the export file for the SFC and ST languages. These new delimiters are not recognized in older
versions of RSLogix 5000 software, so version 13 or later generated .L5K files with SFC or ST online edits should not be imported into versions earlier than
version 13.

Data Types and Keywords – If you are importing an older version project (earlier than version 11) you may get the error message "An error occurred while
creating DATATYPE xxxx (One or more arguments invalid.)" for some user-defined data types. The likely cause of this error is the use of reserved keywords
introduced in version 11 as data type names. Normally, user-defined data types that use keywords are renamed by appending a numeral. If an undefined
data type is nested within another data type, it may be that the undefined data type uses a reserved keyword name and causes the error. To work around
this anomaly, rename any undefined data types to non-keyword names.

Motion Axis Tags and Axis Object Attributes – In addition to the Import/Export changes described above, there have been many changes to motion axis tags
and axis object attributes that result in warning messages when importing older version *.L5K files. These warning messages are in the format:

Warning: Line ###: An error occurred while setting attribute <name_of_attribute> of tag <name_of_axis_tag> (Couldn’t be found).

The same type of warning message is displayed if you import objects that previously accepted NA as values. In this release, the not applicable values are
exported as <NA>.

  

Application Notes
This release has the following application notes.

The following information is provided to help you better understand the behavior of the Logix Designer application in other applications or under certain
circumstances.

Adding CodeMeter CmActLicense to the antivirus white list can prevent error
When an antivirus application is scanning the dynamic data of the CodeMeter CmActLicense, the Logix Designer application cannot access it. If access fails
on multiple attempts, the CmActLicense becomes invalid, and you must restart the computer to clear the error. To avoid this error, consider adding the path
for the CmActLicense (the default path is C:\ProgramData\CodeMeter\CmAct) to the antivirus application white list, or excluding the path from the virus scan.

License must be present to save changes to a License-protected component
To save changes to a component that is protected with License-Based Source Protection, a CmStick containing the required license must be plugged into
the computer running the Logix Designer application.

Make sure you save your edits to a project before removing the CmStick containing the required license. If the license is not present or the license has
expired, the Cancel/Retry dialog box appears requesting you to restore the CmStick and click Retry, or click Cancel to close Logix Designer application.

Important: Leaving the Cancel/Retry dialog box open for a long period of time
causes Windows to display the Component of the Logix Designer
Application has stopped working dialog box. In this event, closing
the Logix Designer application is required resulting in loss of any
unsaved changes.
   
Non-alphanumeric characters in a STRING need an escape carriage

When editing existing standard STRINGs or entering a new STRING, if there is a non-alphanumeric character in the STRING, such as a space, period or
apostrophe, you need to an escape carriage.
Phase Manager and SequenceManager not available on 5x80 family of controllers

The Phase Manager and SequenceManager features are not available for the 5x80 family of controllers in this release of the Logix Designer application.
Download Project Documentation and Extended Properties
To include or exclude project documentation and extended properties from a downloaded project, select or clear the Download Project Documentation
and Extended Properties check box on the Controller Properties dialog box - Project tab.

Downloading project documentation and extended properties to the controller can significantly increase the amount of time it takes to download a project,
especially if a project is heavily documented.

Keep the following considerations in mind when you clear Download Project Documentation and Extended Properties check box and download the
project to the controller:

Risk losing project documentation, extended properties and custom properties from the project.
If extended properties are used in program logic, the download fails. An error in the Error tab states that you cannot access extended properties in
logic when extended properties are not downloaded.
Attempting to add logic to a routine to access extended properties in logic generates an error in the Error tab. The error states that you cannot
access extended properties in logic when the extended properties are not downloaded.
Rung comments and Sequential Function Chart and Function Block Diagram text boxes no longer exist in the controller. Therefore, code comments
are no longer synchronized among multiple online workstations.
During online editing of rungs, other workstations display only rung comments for rungs that exactly match the rung type for the comment in
their offline database. For example, if Workstation 1 performs edits on a Normal rung, Workstation 2 will not display the rung comment while the
rung is in any phase of editing or testing (for example, I/R pair). When the edits are assembled and the rung returns to a Normal rung,
Workstation 2 will again display its rung comment.
Performing online edits of any type on a Sequential Function Chart routine causes other workstations to lose their text box comments for that
routine when the edits are accepted. For example, if Workstation 1 begins pending edits on a Sequential Function Chart routine and accepts
those edits in any controller mode, when Workstation 2 processes those edits, all text boxes in the Sequential Function Chart routine will
become blank, even if they were not modified as part of the edit. Canceling these edits will not restore the text box contents.
Performing online edits on a Function Block Diagram routine in Program mode causes other workstations to lose their text box comments for
that routine when the edits are accepted. This is the same behavior described for Sequential Function Chart routines. In Run mode, the
contents are not lost when pending edits are accepted. They essentially become test edits, and will not be lost until those test edits are
subsequently assembled. As in Sequential Function Chart routines, canceling these edits will not restore the text box contents.

Configuring Equipment Sequence programs to generate events imposes constraints on the sequence
A limited number of events that report updates to input and output parameters of data type STRING can be generated at the same time.This affects the
generation of events:

Recording initial values of sequencing parameters
Recording step input data passed from a sequence to a phase
Recording phase output data passed from a phase to a sequence
Recording sequence output parameters updating

When using sequence events, keep these recommendations in mind:

Equipment Phases and Equipment Sequence should be run in periodic, and not continuous, tasks.
Set the scan rate of the Equipment Sequence to be faster than the time required for an Equipment Phase to run its state routine logic (not the scan
rate, but the time a phase spends executing it’s Running, Holding, Aborting, Stopping, or Resetting state routines).
The phase changes states faster than the scan rate of the equipment sequence program.
Generating events will constrain the performance of an equipment sequence.Only generate events when records for executing the sequence are
required.
Under rare and extreme conditions, the controller will not accept an operator command if an event to record the command cannot be generated.The
Abort command always succeeds. But under the same conditions, is not recorded with an event.
Sequence event generation can be affected by Avoid generating more than 60 events and alarms combined per second. Describe different ways that
multiple events can be generated simultaneously.

Sequence Manager Applications access to Equipment Sequence data from outside the controller.

FactoryTalk View Site Edition (SE) restricts the number of simultaneous clients connected to a controller to 50.
The Sequence Manager Controls should not use VBA to unnecessarily request a refresh of cached sequence configuration data as the refresh blocks
client applications from commanding sequences until the refresh is complete.
It is recommended that the user configure a second Event Client service that subscribes redundantly to generate sequence event data through its
own RSLinx Classic service.This ensures losing communications between the Client Service and the controller does not result in a loss of cached
event data.

Boundary Clock with NTP enabled can cause unwanted, or no motion on a CIP axis
Improper startup synchronization between the ControlLogix or CompactLogix processors, and PowerFlex or Kinetix CIP Motion Enabled Drive may result in
movement when none is expected, or lack of movement when movement is expected (sleep mode). In the case of unexpected movement, a Drive Fault with
Excessive Position Error is issued. While this is not a common occurrence, the possibility of unexpected motion or lack of motion does exist. (Lgx00173808)

MAOC with 1756-OB16IEFS scheduled Output Pulses wrong
Occasionally, the interpolated reg position of an axis will be out of tolerance. For example, the interpolated reg position of the axis should be around .45
revs, but will sometimes show up as .54 revs. The amount that it is off is consistent. During the 1000 rev move, about 120 will be wrong. The values that are
right are very accurate. The values that are wrong are consistently off by the same amount.

The workaround is for most cases is to set the RPI of the O1756-B16IEFS faster than the motion group update time. This will allow the normal sending of
data at the RPI to retry the previous schedule(s) before a new set of schedules are created.
This workaround cannot cover all cases because a new schedule may be set to expire before the modules RPI can perform the retry. In those cases, the
1756-OB16IEFS will do its normal Late Schedule processing and update the Schedule Status and LateScheduleCount in the input tag.

Logix Designer shuts down when WIBU detects malicious debugger

When WIBU AxProtector detects a potentially malicious debugger application, Logix Designer shuts down. As a workaround, disable debugging applications
that are running on your computer and restart Logix Designer. (Lgx00165361)

Upgrade requires reseal of validated Safety Add-On Instructions
When upgrading to Logix Designer application v23 or later, any Safety Add-On Instructions that are sealed with a signature in GuardLogix need to be
resealed. (Lgx00156316)

Equipment Phase parameter alias change
In Logix Designer application versions 21 and earlier, Equipment Phase parameters were allowed to alias any in-scope tag. Starting in version 24, Equipment
Phase parameters can only alias local, non-parameter tags.

Logix projects designed to work with both FactoryTalk Batch and a Logix internal sequencer program might fail verification when you upgrade to Logix
Designer application version 24. You can use the following steps to modify projects with input and output parameter tags (required for FactoryTalk Batch
interoperation) that use aliases.

For projects that fail verification, the following errors appear in the errors tab.

Error: Parameter '\T200_Heat.SetPoint_P01': Input and Output parameters cannot alias global tags.

Error: Parameter '\T200_Heat.Temperature_PV': Input and Output parameters cannot alias global tags.

There are two options for resolving the verification errors.

Method 1:

1.  Create a new public parameter tag to represent the internal sequencing program parameter.

Set the Alias For field of this tag to the same value that was specified in the Alias For field of the unverified Input or Output parameter.
Set the Data Type field of this new tag to be the same as that of the unverified Input or Output parameter.

2.  Remove the alias from the unverified Input or Output parameter tag and instead create a connection.

The connection is from the unverified Input or Output tag to the newly created Public parameter tag. Make sure the data types match for both ends of
the connection.

3.  Test your changes to ensure that your logic continues to work as expected.

Method 2:

1.  Remove the alias to the controller scope tag, from the unverified phase Input or Output parameter

2.  If other programs or phases need to access the value of this phase Input or Output parameter, create an InOut parameter in the other program with
the connection set to the Input or Output parameter in the first phase.
3.  Test your changes to ensure that your logic continues to work as expected.

Install the most current version of FactoryTalk Activation
As a best practice to ensure optimal performance, install the most current version of FactoryTalk Activation on local and centralized activation servers. The
most current version is available at the following URL:

http://www.rockwellautomation.com/support/

If you use a remote activation server, refer to the following publication for more information:

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/612825

Required to re-register EDS files after upgrading to version 20 or later of the application
If the product described by the EDS file is to be used in the I/O configuration using EDS AOP, any EDS files that have been registered for RSLogix 5000
software version 19 and earlier must be re-registered after the installation of RSLogix 5000 software version 20 or later.

Versions 18 and later require updates to Custom Motion Database
If you currently use a Custom RSLogix 5000 Motion Database in RSLogix 5000 software version 12 through 17, you need an updated motion database to
work with versions 18 or later. The following table lists the motion database revisions that are used with these application versions.

Version of Application Motion Database
Revision

29.00 11.5.0 [ Motion.mdb format
]
28.00 10.5.0 [ Motion.mdb format
]

27.00 10.3.0 [ Motion.mdb format
]

26.01 10.3.0 [ Motion.mdb format
]
24.00 9.24.0 [ Motion.mdb format
]
23.00 9.22.0 [ Motion.mdb format
]
21.03 9.15.0 [ Motion.mdb format
]
21.00 9.8.0 [ Motion.mdb format ]
20.01 8.12.0 [ Motion.mdb format
]
20.00 8.9.0 [ Motion.mdb format ]
19.01 / 19.00 7.5.0 [ Motion.mdb format ]
18.02 / 18.01 / 18.00 6.9.0 [ Motion.mdb format ]

17.01 / 17.00 5.3.0 [ *Motion.md format ]
16.04 / 16.03 / 16.00 4.2.0 [ *Motion.md format ]
15.03 / 15.02 / 15.01 / 15.00 3.24.0 [ *Motion.md format ]
14.01 / 14.00 3.12.0 [ *Motion.md format ]

13.04 / 13.03 / 13.02 / 13.01 / 13.00 3.12.0 [ *Motion.md format ]
12.06 / 12.05 / 12.04 / 12.03 / 12.02 / 12.01 / 3.3.0 [ *Motion.md format ]
12.00
* Before a Custom Motor can be used in version 18 or later, any Custom Motor currently in a motion database file at revision 5 or earlier (Motion.db format)
must be converted to the newer Motion.mdb format.

To initiate the process of getting the database updated, please email your request to raeptechsupport@ra.rockwell.com. Please include any prior tech
support case number if your current database includes non-Rockwell motors.

LINT members must align on 8-byte boundaries
Beginning with version 25 of the Logix Designer application, LINT members must be aligned on 8-byte boundaries, and the UDT that contains LINT members
should be sized as a multiple of 8 bytes. This impacts you if either of the following situations are true:

You use this tag as a producer, and at least one consumer (controller) has firmware earlier than version 25.
You use this tag as a consumer, and the producer (controller) has firmware earlier than version 25.

If you use a tag with LINT members as a producer (Source Tag), for each consumer (controller) that has firmware earlier than version 25, you need to align
the LINT members on the 8-byte boundary for the data type of the consumer tag (Target Tag).

If you use a tag with LINT members as a consumer (Target Tag), for the producer (controller) that has firmware earlier than version 25, you need to align the
LINT members on the 8-byte boundary for the data type of the producer tag (Source Tag).

For more information, refer to the following topic in the Logix Designer online help:

LINT data types within this tag now align on 8-byte boundaries. Check produce/consume connection.

(Lgx00167772)

Fatal error handling
There is a log file generated that records abnormal events and that can be delivered to Rockwell Automation Services & Support so that the anomaly can be
recorded, diagnosed, and fixed. An abnormal termination of the Logix Designer application will result in a short period of program unresponsiveness followed
by the appearance of a dialog box that identifies the fatal error. The dialog box contains specific details about the cause of the error. In addition, this
information is appended to the file fatal error log file.

In order to more effectively address software error conditions, starting with version 15.00, the Fatal Error information is also stored in a file named RSLogix
5000 Fatal Error.Dmp. This file, containing the exact memory image at the time the error occurred, greatly extends our ability to determine the cause of the
Fatal Error and to address product anomalies if those were the case. Due to the size of the dump file, special arrangements must be made in order for
Technical Support to acquire these files. If it is not needed, the RSLogix 5000 Fatal Error.Dmp file can also be deleted.

These diagnostic files are now located in C:\Users\Public\Public Documents\Rockwell Automation\RSLogix 5000\Logs for the supported operating
systems.

SequenceManager changed the Equipment Phase Monitor
The appearance of the Equipment Phase Monitor has been updated as part of SequenceManager:

The command symbols used in the Command Bar of the Equipment Sequence Diagram Monitor have been added to the Phase Monitor.
The Pause functionality of the Equipment Phase has been redesigned and simplified.
Pause and AutoPause buttons toggle enabled or disabled.
The Resume button is only enabled when the Equipment Phase is Paused.
A single state box is filled when the phase is Paused or unfilled when not-paused.

Project Export permission will affect the ability to cut, copy, and drag-n-drop out of versions 28 and later

If FactoryTalk Security is being used, users now require the "Project Export" permission in order to copy a component onto the clipboard or to drag and drop
a component from one project into another.

No backward controller morphing for 5x80 family of controllers

In versions 28 and later of Studio 5000 Logix Designer, an existing project can be converted to use the 5x80 family of controllers. However, once a project is
converted to use a 5x80 controller, the project cannot be reverted back to use the previous controller type by using the Controller Properties dialog box
Change Controller option. The original controller for the project will not be a controller type option in the Change Controller dialog box drop down menu.
If a project needs to be reverted back to the previous family of the controller, the project will need to be exported to an .L5k or .L5x file format and then
manually modified. Refer to the Logix5000 Controllers Import/Export Reference Manual, publication 1756-RM084 for more information about modification of
the controller type.

Behavior changes in the 5x80 and 5x70 family of Logix controllers

Refer to the Replacement Guidelines: Logix5000 Controllers Reference Manual, publication 1756-RM100, for detailed considerations and explanations of
the changes that you may have to make to your project when replacing controllers.

PLC-5/SLC translator tool renamed the RSLogix Project Migrator

In release v28.00, the PLC-5/SLC translator tool was been renamed the RSLogix Project Migrator. The tool converts RSLogix 5 and RSLogix 500
projects into .L5K files that you can import into Logix Designer. It includes the following enhancements:
Improved handling of symbol and comment truncation.
Improved SLC I/O migration.
Ability to migrate MicroLogix projects.

  

Legal Notices for Studio 5000 Logix Designer version 29.00

Copyright Notice

© 2016 Rockwell Automation, Inc. All rights reserved. Printed in USA.

This document and any accompanying Rockwell Software products are copyrighted by Rockwell Automation, Inc. Any reproduction and/or distribution without
prior written consent from Rockwell Automation, Inc. is strictly prohibited. Please refer to the license agreement for details.

End User License Agreement (EULA)

You can view the Rockwell Automation End-User License Agreement ("EULA") by opening the License.rtf file located in your product's install folder on your
hard drive.

Other Licenses

Botan (http://botan.randombit.net/) is distributed under these terms:

Copyright (C) 1999-2013, 2014 Jack Lloyd

2001 Peter J Jones

2004-2007 Justin Karneges

2004 Vaclav Ovsik

2005 Matthew Gregan

2005-2006 Matt Johnston

2006 Luca Piccarreta

2007 Yves Jerschow

2007-2008 FlexSecure GmbH

2007-2008 Technische Universitat Darmstadt

2007-2008 Falko Strenzke

2007-2008 Martin Doering

2007 Manuel Hartl

2007 Christoph Ludwig

2007 Patrick Sona
2010 Olivier de Gaalon

2012 Vojtech Kral

2012 Markus Wanner

2013 Joel Low
All rights reserved.

Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are met:

1.  Redistributions of source code must retain the above copyright notice, this list of conditions, and the following disclaimer.

2.  Redistributions in binary form must reproduce the above copyright notice, this list of conditions, and the following disclaimer in the documentation
and/or other materials provided with the distribution.

THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND CONTRIBUTORS "AS IS" AND ANY EXPRESS OR IMPLIED WARRANTIES,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED.
IN NO EVENT SHALL THE COPYRIGHT HOLDER OR CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR
CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR
PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR
TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE
POSSIBILITY OF SUCH DAMAGE.

The package GNU Compiler Collection (GCC) is licensed under the following licenses:

GNU General Public License v3.0, the text of which is available at http://www.gnu.org/licenses/gpl-3.0-standalone.html. Copyright © 2007 Free Software
Foundation, Inc.

MIT License, the text of which is available at http://www.opensource.org/licenses/MIT.

GNU General Public License v3.0 with GCC Runtime Library exception (v3.1), the text of which is available at https://olex-
secure.openlogic.com/licenses/base_license/gpl-gcc-v3-license-base. Copyright (C) 2009 Free Software Foundation, Inc.

GNU Lesser General Public License v2.1, the text of which is available at http://www.gnu.org/licenses/old-licenses/lgpl-2.1-standalone.html. Copyright (C)
1991, 1999 Free Software Foundation, Inc.

GNU General Public License v2.0, the text of which is available at http://www.gnu.org/licenses/old-licenses/gpl-2.0-standalone.html. Copyright (C) 1989, 1991
Free Software Foundation, Inc.

Mozilla Public License 1.1, the text of which is available at http://www.mozilla.org/MPL/MPL-1.1.html.

Unicode, Inc. License Agreement, the text of which is available at http://www.unicode.org/copyright.html. Copyright © 1991-2009 Unicode, Inc.

GNU Library General Public License v2.0, the text of which is available at http://www.gnu.org/licenses/old-licenses/lgpl-2.0-standalone.html. Copyright (C)
1991 Free Software Foundation, Inc

BSD 3-clause New or Revised License, the text of which is available at http://www.opensource.org/licenses/BSD-3-Clause.

BSD 2-clause (FreeBSD License), the text of which is available at http://www.freebsd.org/copyright/freebsd-license.html. Copyright 1992-2012 The FreeBSD
Project.

GNU Free Documentation License v1.3, the text of which is available at http://www.gnu.org/licenses/fdl-1.3.txt. Copyright © 2000, 2001, 2002, 2007, 2008
Free Software Foundation, Inc.

GNU General Public License v2.0 w/ServerHandler library exception, the text of which is available at https://olex-secure.openlogic.com/licenses/gpl-
serverhandler-exception. Copyright (C) 1989, 1991 Free Software Foundation, Inc

GNU Lesser General Public License v3.0, the text of which is available at http://www.gnu.org/licenses/lgpl-3.0-standalone.html. Copyright © 2007 Free
Software Foundation, Inc.

Creative Commons Attribution 3.0, the text of which is available at http://creativecommons.org/licenses/by/3.0/legalcode.

Independent JPEG Group License, the text of which is available at https://olex-secure.openlogic.com/licenses/ijg-license.

Boost Software License 1.0, and BSD 3-clause (University of California Regents), the text of which is available at http://www.boost.org/LICENSE_1_0.txt.

The package Newlib is licensed under the following licenses:

GNU General Public License v2.0 w/Autoconf exception, the text of which is available at http://spdx.org/licenses/GPL-2.0-with-autoconf-exception. Copyright
(C) 1989, 1991 Free Software Foundation, Inc.

GNU General Public License v3.0 w/Autoconf exception, the text of which is available at http://spdx.org/licenses/GPL-3.0-with-autoconf-exception. Copyright
© 2009 Free Software Foundation, Inc.

OpenSSL distributed under these terms:

Copyright (c) 1998-2011 The OpenSSL Project. All rights reserved.

Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are met:

1.  Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.

2.  Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation
and/or other materials provided with the distribution.
3.  All advertising materials mentioning features or use of this software must display the following acknowledgment: "This product includes software
developed by the OpenSSL Project for use in the OpenSSL Toolkit. (http://www.openssl.org/)"
4.  The names "OpenSSL Toolkit" and "OpenSSL Project" must not be used to endorse or promote products derived from this software without prior
written permission. For written permission, please contact openssl-core@openssl.org.
5.  Products derived from this software may not be called "OpenSSL" nor may "OpenSSL" appear in their names without prior written permission of the
OpenSSL Project.
6.  Redistributions of any form whatsoever must retain the following acknowledgment: "This product includes software developed by the OpenSSL Project
for use in the OpenSSL Toolkit (http://www.openssl.org/)"

THIS SOFTWARE IS PROVIDED BY THE OpenSSL PROJECT ``AS IS'' AND ANY EXPRESSED OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED
TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE
OpenSSL PROJECT OR ITS CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL
DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR
BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT
(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF
SUCH DAMAGE.

===================================================================

Trademark Notices

Allen-Bradley, Rockwell Automation, RSAlarm, RSAnimator, RSBatch, RSData, RSLogix, Studio 5000, RSLadder, RSLinx, RSNetWorx, RSPower,
RSSidewinderX, RSSql, RSTrainer, RSTrend, RSTune, RSView32, RSView, SoftLogix, AdvanceDDE, ControlView, Packed DDE, WINtelligent, WINtelligent
Series, WINtelligent LINX, WINtelligent LOGIC 5, WINtelligent VIEW, WINtelligent RECIPE, WINtelligent VISION, WINtelligent VISION2, PLC-2, PLC-3, PLC-5,
Data Highway Plus, Data Highway II, MicroLogix, Network DTL, Pyramid Integrator, PanelBuilder, PanelView, SLC, SLC 500, SLC 5/03, ControlFLASH,
FactoryTalk, FactoryTalk Services Platform, FactoryTalk View, Kinetix, CompactLogix, Compact GuardLogix, Compact I/O, GuardLogix, CompactBlock Guard
I/O, DH+, FlexLogix, PhaseManager, ControlLogix, and SequenceManager are trademarks of Rockwell Automation, Inc.Any Rockwell Automation software or
hardware not mentioned here is also a trademark, registered or otherwise, of Rockwell Automation, Inc.

Other Trademarks

CmFAS Assistant, CmDongle, CodeMeter, CodeMeter Control Center, and WIBU are trademarks of WIBU-SYSTEMS AG in the United States and/or other
countries. Intel is a trademark of Intel Corporation. Microsoft and Windows are trademarks of Microsoft Corporation. ControlNet, <OCCN>, EtherNet/IP are
trademarks of ODVA, Inc.

All other trademarks are the property of their respective holders and are hereby acknowledged.

Warranty

This product is warranted in accordance with the product license. The product’s performance may be affected by system configuration, the application being
performed, operator control, maintenance, and other related factors. Rockwell Automation is not responsible for these intervening factors. The instructions
in this document do not cover all the details or variations in the equipment, procedure, or process described, nor do they provide directions for meeting
every possible contingency during installation, operation, or maintenance. This product’s implementation may vary among users.

This document is current as of the time of release of the product; however, the accompanying software may have changed since the release. Rockwell
Automation, Inc. reserves the right to change any information contained in this document or the software at any time without prior notice. It is your
responsibility to obtain the most current information available from Rockwell when installing or using this product.

Environmental Compliance

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-
us/sustainability-ethics/product-environmental-compliance.page.

  

Copyright © 2016 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation, Allen-Bradley, and Rockwell Software are trademarks of Rockwell Automation, Inc.
To view a complete list of Rockwell Automation trademarks please click here.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

You might also like