Trax export

Substation S/E Principal 13.2 kV


Position +K01 SA - 1
Job #
Asset ID

Reason Mantenimiento
Weather Parcialmente Nublado
Ambient Temperature 30 °C
Humidity 52.00 %
Date 2022-01-31
Tester Carlos Orozco

Current Transformer Information


Number of CTs 3

CT1
Manufacturer SIEMENS
Year 2019
Serial 2019 - 1003096827
Number of cores 3
Type 4MR12 - PL AYC
Standard IEC 61869 - 2
Frequency 60
Primary voltage (kV) 14.4
Notes

Core 1
Label T1L1
Taps 2
Type Protection
Burden 0
FS Alf
Accuracy class 5P20
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 1S3
Notes

Core 2
Label T1L1
Taps 2
Type Protection
Burden 0
FS Alf
Accuracy class 5P20
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 2S1
Notes

Core 3
Label T1L1
Taps 2
Type Meter
Burden 0
FS Alf 0
Accuracy class 0.5
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 3S1
Notes

CT2
Manufacturer SIEMENS
Year 2019
Serial 2019 - 1003096828
Number of cores 2
Type 4MR12 - PL AYC
Standard IEC 61869 - 2
Frequency 60
Primary voltage (kV) 14.4
Notes

Core 1
Label T1L1
Taps 2
Type Protection
Burden 0
FS Alf 1.05
Accuracy class 5P20
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 1S3
Notes

Core 2
Label T1L1
Taps 2
Type Meter
Burden 0
FS Alf 0
Accuracy class 0.5
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 2S3
Notes

CT3
Manufacturer SIEMENS
Year 2019
Serial 2019 - 1003096830
Number of cores 3
Type AMR12 - PL AYC
Standard IEC 61869 - 2
Frequency 60
Primary voltage (kV) 14.4
Notes

Core 1
Label T1L3
Taps 2
Type Meter
Burden 0
FS Alf 0
Accuracy class 5P20
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 1S1
Notes

Core 2
Label T1L3
Taps 2
Type Protection
Burden 0
FS Alf 0
Accuracy class 0.5
Primary nominal current 2000
Secondary nominal current 5
CT VA rating 15VA
In service tap 2S1
Notes

Core 3
Label
Taps 2
Type Meter
Burden 0
FS Alf 0
Accuracy class
Primary nominal current
Secondary nominal current 5
CT VA rating 1.5VA
In service tap 3S1
Notes

Voltage Transformer Information


Number of VTs 3

VT1
Manufacturer SIEMENS
Serial 2019 - 1003097079
Year 2019
Number of secondaries 3
Primary voltage (kV) 14.4
Max neutral tap voltage 120
Secondary 1
Label T5L1
Taps 2
Burden
Accuracy class
Primary nominal voltage 14000
Secondary nominal voltage 120
VT VA rating 1
Notes
Secondary 2
Label T5L1
Taps 2
Burden
Accuracy class
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 1
Notes

Secondary 3
Label T5L1
Taps 2
Burden
Accuracy class
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 1
Notes

VT2
Manufacturer SIEMENS
Serial 2019 - 1003097077
Year 2019
Number of secondaries 3
Primary voltage (kV) 14.4
Max neutral tap voltage 120
Secondary 1
Label T5L2
Taps 2
Burden
Accuracy class 0.5
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 10
Notes

Secondary 2
Label T5L2
Taps 2
Burden
Accuracy class 3P
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 10
Notes

Secondary 3
Label T5L2
Taps 2
Burden
Accuracy class 3P
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 15
Notes
VT3
Manufacturer SIEMENS
Serial 2019 - 1003097080
Year 2019
Number of secondaries 3
Primary voltage (kV) 14.4
Max neutral tap voltage 120
Secondary 1
Label T5L3
Taps 2
Burden
Accuracy class 0.5
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 10
Notes

Secondary 2
Label T5L3
Taps 2
Burden
Accuracy class 3P
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 10
Notes

Secondary 3
Label T5L3
Taps 2
Burden
Accuracy class 3P
Primary nominal voltage 14400
Secondary nominal voltage 120
VT VA rating 15
Notes

Current Transformer Winding Resistance Measurements


# Designation Current Measured Resistance Stability
l1 : 2S1-2S2 200.0m 384.2m 99.98
l1 : 3S1-3S2 200.0m 385.5m 99.98
CT2 : 1S1-1S2 200.0m 385.6m 99.98
CT2 : 2S1-2S2 200.0m 384.8m 99.97
CT3 : 1S1-1S2
CT3 : 2S1-2S2 199.9m 385.1m 100.0
CT3 : 3S1-3S2 199.9m 384.7m 99.97

nucleo dos no habilitadox

CT ratio I measurements
# Designation I Is Ratio Measured ratio Ratio Error Phase Error
Polarity Test frequency
l1 : P1-P2/1S1-1S2 2.000k : 5.000 ( 400.0 )
---
l1 : P1-P2/2S1-2S2 100.0 251.1m 2.000k : 5.000 ( 400.0 ) 398.3 4.150m
50.51m Pass 60.00
l1 : P1-P2/3S1-3S2 99.10 248.8m 2.000k : 5.000 ( 400.0 ) 398.4 4.044m
44.48m Pass 60.00
CT2 : P1-P2/1S1-1S2 100.0 245.0m 2.000k : 5.000 ( 400.0 ) 408.2 -
20.05m -3.609 Pass 60.00
CT2 : P1-P2/2S1-2S2 99.10 248.8m 2.000k : 5.000 ( 400.0 ) 398.4 4.055m
88.93m Pass 60.00
CT3 : P1-P2/1S1-1S2 100.0 251.2m 2.000k : 5.000 ( 400.0 ) 398.1 4.661m
-2.231m Pass 60.00
CT3 : P1-P2/2S1-2S2 99.07 248.5m 2.000k : 5.000 ( 400.0 ) 398.6 3.486m
69.77m Pass 60.00

VT ratio measurements
# Designation U Ratio Measured ratio Ratio Error Phase Error Polarity
Current Test frequency
VT1 : A-N/1a-1n 2.001k 8.083k : 69.28 ( 116.7 ) 296.1 -605.9m 64.35
Pass 1.279m 60.00
VT1 : A-N/1a-1n 14.00k : 120.0 ( 116.7 ) ---
VT1 : A-N/2a-2n 2.001k 8.314k : 69.28 ( 120.0 ) 259.8 -538.2m 66.14
Pass 1.217m 60.00
VT1 : A-N/3a-3n 2.001k 8.314k : 40.00 ( 207.8 ) 260.2 -201.1m 62.49
Pass 1.207m 60.00
VT1 : A-N/3a-3n 14.40k : 120.0 ( 120.0 ) ---
VT2 : A-N/1a-1n 2.001k 8.314k : 69.28 ( 120.0 ) 285.5 -579.7m 67.73
Pass 1.259m 60.00
VT2 : A-N/2a-2n 2.001k 8.314k : 69.28 ( 120.0 ) 294.9 -593.1m 66.33
Pass 1.271m 60.00
VT2 : A-N/3a-3n 2.001k 8.314k : 40.00 ( 207.8 ) 261.7 -205.9m 64.90
Pass 1.209m 60.00
VT3 : A-N/1a-1n 2.001k 8.314k : 69.28 ( 120.0 ) 260.4 -539.1m 64.70
Pass 1.208m 60.00
VT3 : A-N/1a-1n 14.40k : 120.0 ( 120.0 ) ---
VT3 : A-N/2a-2n 2.001k 8.314k : 69.28 ( 120.0 ) 263.7 -544.9m 61.23
Pass 1.212m 60.00
VT3 : A-N/2a-2n 14.40k : 120.0 ( 120.0 ) ---
VT3 : A-N/3a-3n 2.001k 8.314k : 40.00 ( 207.8 ) 301.7 -311.1m 65.18
Pass 1.278m 60.00
VT3 : A-N/3a-3n 14.40k : 120.0 ( 120.0 ) ---