Model: PEFY-P50VMA-E

Job Name:
System Reference: Date:
SPECIFICATIONS:
Capacity*
Cooling Btu/h 19,100
Heating Btu/h 21,500
* Cooling / Heating capacity indicated at the maximum value at operation under the following conditions:
Cooling | Indoor : 81° F (27° C) DB / 19° C (66° F) WB
Cooling | Outdoor : 95° F (35° C) DB
Heating | Indoor : 68° F (20° C) DB
Heating | Outdoor : 45° F (7° C) DB / 43° F (6°C) WB

Electrical
Electrical Power
220 / 230 / 240V, 1-phase, 50/60Hz
Requirements
Minimum Circuit
A 1.54 (50/60 Hz)
Ampacity (MCA)

Power Input

Cooling kW 0.11

Heating kW 0.09

External Dimensions
GENERAL FEATURES:
• R410A refrigerant
• 9-7/8” (250mm) high for low ceiling heights Unit (H x W x D) 9-7/8 x 35-7/16 x 28-7/8
• Ducted flexible fan coil supporting multiple configurations for In. (mm) (250 x 900 x 732)
installation.
• Multiple fan speed settings Net Weight
• 0–10V DC analog input to control motor speed
• Built-in condensate lift; lifts to 27-9/16” (700mm) Unit Lbs.(kg) 58 (26)
• Auto fan mode
External Finish Galvanized steel plate
ACCESSORIES:
Filter Box (FBM2-2) Heat Exchanger Cross fin (Aluminum fin and copper tube)
External Heat Adapter (CN24RELAY-KIT-CM3)
Fan
Type x Quanity Sirocco fan x 1

External Static Pressure mmH2O <3.6>-5.1-<7.1>-<10.2>-<15.3>

Airflow rate
CFM 424 - 512 - 600
(Low-Mid-High)
Motor Type DC motor
Motor Output kW 0.085 (50/60 Hz)

Air Filter PP honeycomb fabric

Refrigerant Piping Diameter

Liquid (High Pressure) In.(mm) 1/4 (6.35) Brazed

Gas (Low Pressure) In.(mm) 1/2 (12.70) Brazed

Field Drain Pipe Size In.(mm) O.D. 1-1/4 (32)

Sound Level

Low-Mid-High dB(A) 28 - 32 - 35
Notes:

Specifications are subject to change without notice. © 2015 Mitsubishi Electric US, Inc.
Note 1. Use M10 screw for the Suspension bolt (field supply).
2 x E - ø2.9 Suspension bolt hole 2. Keep the service space for the maintenance at the bottom.
15
4 - 14 x 30 Slot 18 210 3. This chart indicates for PEFY-P63·71·80·100·125·140VMA-E
models, which have 2 fans. PEFY-P20·25·32·40·50VMA-E models
have 1 fan.

Specifications are subject to change without notice.


4. In case of the inlet duct is used, remove the air filter
(supply with the unit), then install the filter
(field supply) at suction side.
Model:

A
C
Air Air

D (Duct)
outlet inlet

100 x (E - 1) = F
B (Suspension bolt pitch)

100

20
30
73
21

10

100

40
23

58
57 643 (Suspension bolt pitch)
Air Filter

732 Control box


2 Refrigerant piping
32 700
Brazing connection (liquid)
238 Drain pipe Drain pump 1 2
Model A B C D E F G Gas pipe Liquid pipe
41

122

23
10 (O.D.ø32)

40
PEFY-P20,25,32VMA-E 700 754 800 660 7 600 658
PEFY-P40,50VMA-E 900 954 1000 860 9 800 858 ø12.7 ø6.35
PEFY-P63,71,80VMA-E 1100 1154 1200 1060 11 1000 1058
PEFY-P100,125VMA-E 1400 1454 1500 1360 14 1300 1358 ø15.88 ø9.52
217

100
PEFY-P50VMA-E- DIMENSIONS

250

PEFY-P140VMA-E 1600 1654 1700 1560 16 1500 1558

178 (Duct)
33
Terminal block (Transmission)
2 x 2 - ø2.9
136 67
1 Refrigerant piping 356 Drain pipe (O.D.ø32) Terminal block (Power source)
Brazing connection (gas) (Spontaneous draining)
Unit : mm

© 2015 Mitsubishi Electric US, Inc.


FORM# PEFY-P50VMA-E-20151118

Specifications are subject to change without notice.


Model:

Less than 300mm


0
65 -10
(Actual length)

50 777 Access door

H
50
Less than 700mm

Drain hose (I.D.ø32)


<accessory>
250
Note2 ~30 450
0 450
300
an
re th
Mo
Required space for service and maintenance

6 J K x (M - 1) = N J
11

P - ø2.9 K L K
112
112

More than 10mm


Ceiling surface Access door
Model H J K L M N P
PEFY-P20,25,32VMA-E 800 44 150 300 10

More than 20mm


PEFY-P40VMA-E
1000 54 260 4 780 10
PEFY-P50VMA-E
Make the access door at the appointed position properly for service maintenance.
PEFY-P63,71,80VMA-E 1200 49 330 4 990 10
PEFY-P100,125VMA-E 1500 54 320 5 1280 12
PEFY-P140VMA-E 1700 54 370 5 1480 12
PEFY-P50VMA-E- DIMENSIONS
Unit : mm

© 2015 Mitsubishi Electric US, Inc.


Toll Free: 800-433-4822 www.mehvac.com