This paper proposes a remote monitoring system as part of Distributed Control System (DCS) of process plant. Remote
plant critical alarms from DCS are continuously monitored online through Supervisory Control and Data Acquisition (SCADA)
system. A report, which contains alarm details formulated through MS-Excel, is sent to respective e-mail recipients through
Outlook Express. For system maintenance, M2M gateway and Virtual Private Network (VPN) technology are used in remote
monitoring. Service engineers can remotely view real time conditions of plant area, diagnose problem and help plant engineers to
rectify it to avoid plant failures and maximizing plant process availability.
Keywords: Distributed control system, Supervisory control and data acquisition system, Virtual private network
Fig. 2— Architecture of proposed remote monitoring system for distributed control of industrial process plant
860 J SCI IND RES VOL 68 OCTOBER 2009
Alarms are used in any plant for ensuring fault free plant engineers. Proposed system was successfully
operation. A separate database is made in MS Access / implemented in process control area of a leading MNC.
MY SQL in SCADA for maintaining alarm code, date
and time of occurrence of alarm, alarm description, alarm Conclusions
meaning, alarm cause and action. Whenever an alarm Industrial process plant can be monitored remotely
event concerning alarm occurs in plant, SCADA scans by proposed system architecture having GPRS and
alarm code in DCS alarm information file. Alarm code is wireless Internet connection in conjunction with DCS-
then compared with database and alarm report file is SCADA. It improves reliability, response time, plant
generated in MS Excel. Each alarm report consists of interface under continuous remote real time monitoring
alarm description, alarm meaning, alarm cause, action under adverse environmental conditions of process plants
etc., besides information about alarms that occurred 30 for maximizing plant operational conditions.
minutes earlier. It sharpens diagnostic procedure to
identify causes of faults. Acknowledgements
A SCADA- VB (Visual Basic) application is created Protocol Automation Technology, Bangalore, India,
for transferring generated alarm report automatically to financially supported this project. Authors thank all project
MS outlook express, which is configured with customer partners for meaningful discussions.
user ID. It takes GPRS radio communication and Internet
technology to communicate between remote monitoring References
computer and field monitoring computer4. M2M gateway 1 Li H-Y, Web-based remote monitoring and control for process
is used to built wireless GPRS networks running plants, in Proc of Int Conf on Machine Learning & Cybernetics,
independent of mobile operators. It issues virtual static 2005 936-941.
2 Kubo M & Ikeda H, New Remote Maintenance System (RMS)
IP addresses for remote field devices and sites. Alarm
for Distributed Control System, in SICE-ICASE Int Joint Conf,
report is transmitted to GPRS network using M2M 8, TP27-53/I59/(2006).
gateway. GPRS network connects Internet. Whenever, 3 Oltean S E, Abrudean M & Dulau M, Remote monitor and
connection is established, report from outlook express is control application for thermal processes using TCP/IP, in IEEE
forwarded to Global response centre / Customer Service Int Conf on Automation, Quality & Testing Robotics, (IEEE,
USA) 25-28 May 2006, 209-213.
Department. Forwarded information contains all details
4 Rotharmel S, IP based telecom power system monitoring solu-
pertaining to plant operation alarms. Through Virtual tion in GPRS networks, in Int Conf on Telecom Energy, INTELEC
Private Network (VPN) service5, engineers can view 2007, 2007, 769-774.
real time conditions of affected plant area and diagnose 5 Venkateswaran R, Virtual Private Networks, IEEE Potentials
problem remotely for providing solution measures to (Lucent Technol. Bell Lab., USA) 2001, 11-15.