HVAC Load Analysis


for

Sanna Trujillo

Prepared By:

viernes, 18 de Febrero de 2022


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 2

General Project Data Input


General Project Information
Project file name: C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV
Project title: Sanna Trujillo
Project date: jueves, 17 de Febrero de 2022
Weather reference city: LA LIBERTAD , TRUJILLO, PERU
Client name: Sanna Trujillo
Barometric pressure: 29.800 in.Hg.
Altitude: 112 feet
Latitude: -8 Degrees
Mean daily temperature range: 15 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique zones in this project: 3

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 1.20 Watts per square foot
Equipment requirements: 1.20 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 0
Equipment profile number: 0
People profile number: 0
Building default ceiling height: 10.00 feet
Building default wall height: 10.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:17 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
January 77 73 50% 72 57.07 -10
February 78 74 50% 72 64.10 -8
March 78 74 50% 72 61.72 -9
April 76 72 50% 72 51.85 -11
May 74 70 50% 72 44.05 -13
June 71 67 50% 72 36.09 -15
July 70 66 50% 72 29.85 -17
August 68 64 50% 72 25.70 -18
September 68 64 50% 72 25.70 -18
October 69 65 50% 72 27.46 -18
November 71 67 50% 72 36.09 -15
December 74 70 50% 72 45.44 -13
Winter 68 72

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 8 0.350 No Sí

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 C 0.300 L

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.355 10 0

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 0.990 0.900 0.700 2 0.000

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:17 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 4

Building Summary Loads


Building peaks in March at 4pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 0 0 0.00 0 0 0 0.00
Wall 0 0 0.00 0 0 0 0.00
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 0 0 0.00
Lighting 607 0 0.00 0 2,279 2,279 3.29
Equipment 10,000 0 0.00 0 37,534 37,534 54.13
People 3 0 0.00 558 698 1,256 1.81
Partition 2,171 0 0.00 0 8,478 8,478 12.23
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 372 0 0.00 16,067 2,444 18,511 26.69
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 1,287 1,287 1.86
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 16,625 52,720 69,345 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 16,067 2,444 18,511 26.69
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 558 48,988 49,547 71.45
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 1,287 1,287 1.86
Building Totals 0 0.00 16,625 52,720 69,345 100.00

Check Figures
Total Building Supply Air (based on a 17° TD): 2,630 CFM
Total Building Vent. Air (14.14% of Supply): 372 CFM
Total Conditioned Air Space: 506 Sq.ft
Supply Air Per Unit Area: 5.1989 CFM/Sq.ft
Area Per Cooling Capacity: 87.6 Sq.ft/Ton
Cooling Capacity Per Area: 0.0114 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 5.78 Tons

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 5

Air Handler #1 - Sala De Equipos - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Ssala De Equipos 95 0 21,592 209 None None
12am December 1 0 1,159 0 0 0
948 0.00 12.23 0 0 0
Zone Peak Totals: 95 0 21,592 209
Total Zones: 1 1 0 1,159 0 0 0
Unique Zones: 1 948 0.00 12.23 0 0 0

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 6

Air Handler #1 - Sala De Equipos - Total Load Summary


Air Handler Description: Sala De Equipos Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.22 HP
Fan Input: 65% motor and fan efficiency with 0.8 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 12am in December.
Outdoor Conditions: 62° DB, 61° WB, 77.82 grains
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.996 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 21,592 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 21,592 Btuh
Cooling Supply Air: 21,592 / (.996 X 1.1 X 17) = 1,159 CFM
Summer Vent Outside Air (0.0% of supply) = 0 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 0 CFM
Blow-thru fan sensible gain: 567 Btuh
Total sensible gain on return side of coil: 567 Btuh
Total sensible gain on air handling system: 22,159 Btuh
Zone space latent gain: 209 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 0 Btuh
Total latent gain on air handling system: 209 Btuh
Total system sensible and latent gain: 22,368 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 1,159 CFM
Total Air Handler Vent. Air (0.00% of Supply): 0 CFM
Total Conditioned Air Space: 95 Sq.ft
Supply Air Per Unit Area: 12.2299 CFM/Sq.ft
Area Per Cooling Capacity: 50.9 Sq.ft/Ton
Cooling Capacity Per Area: 0.0197 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 1.86 Tons

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 7

Air Handler #2 - Sala De Resonancia - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
2 Sala De Resonancia 352 0 17,733 220 None 6/Hr
12am December 1 0 952 0 0 352
3,522 0.00 2.70 0 0 352
Zone Peak Totals: 352 0 17,733 220
Total Zones: 1 1 0 952 0 0 352
Unique Zones: 1 3,522 0.00 2.70 0 0 352

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 8

Air Handler #2 - Sala De Resonancia - Total Load Summary


Air Handler Description: Sala De Resonancia Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.18 HP
Fan Input: 65% motor and fan efficiency with 0.8 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in March.
Outdoor Conditions: 77° DB, 74° WB, 121.06 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 12am is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 17,733.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.996 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 17,733 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 17,733 Btuh
Cooling Supply Air: 17,733 / (.996 X 1.1 X 17) = 952 CFM
Summer Vent Outside Air (37.0% of supply) = 352 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,315 Btuh 352 CFM
Blow-thru fan sensible gain: 466 Btuh
Total sensible gain on return side of coil: 2,781 Btuh
Total sensible gain on air handling system: 20,514 Btuh
Zone space latent gain: 220 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 15,218 Btuh
Total latent gain on air handling system: 15,438 Btuh
Total system sensible and latent gain: 35,952 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 952 CFM
Total Air Handler Vent. Air (36.99% of Supply): 352 CFM
Total Conditioned Air Space: 352 Sq.ft
Supply Air Per Unit Area: 2.7036 CFM/Sq.ft
Area Per Cooling Capacity: 117.5 Sq.ft/Ton
Cooling Capacity Per Area: 0.0085 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 3.00 Tons

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 9

Air Handler #3 - Sala De Control - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Zone Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
3 Sala De Control 59 0 9,663 130 None 2/Hr
12am December 1 0 519 0 0 20
590 0.00 8.80 0 0 20
Zone Peak Totals: 59 0 9,663 130
Total Zones: 1 1 0 519 0 0 20
Unique Zones: 1 590 0.00 8.80 0 0 20

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 10

Air Handler #3 - Sala De Control - Total Load Summary


Air Handler Description: Sala De Control Constant Volume - Sum of Peaks
Supply Air Fan: Blow-Thru with program estimated horsepower of 0.10 HP
Fan Input: 65% motor and fan efficiency with 0.8 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in March.
Outdoor Conditions: 77° DB, 74° WB, 121.06 grains
Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 12am is
different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 9,663.
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.996 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Zone space sensible gain: 9,663 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 9,663 Btuh
Cooling Supply Air: 9,663 / (.996 X 1.1 X 17) = 519 CFM
Summer Vent Outside Air (3.8% of supply) = 20 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 129 Btuh 20 CFM
Blow-thru fan sensible gain: 254 Btuh
Total sensible gain on return side of coil: 383 Btuh
Total sensible gain on air handling system: 10,047 Btuh
Zone space latent gain: 130 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 849 Btuh
Total latent gain on air handling system: 979 Btuh
Total system sensible and latent gain: 11,026 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 519 CFM
Total Air Handler Vent. Air (3.79% of Supply): 20 CFM
Total Conditioned Air Space: 59 Sq.ft
Supply Air Per Unit Area: 8.7994 CFM/Sq.ft
Area Per Cooling Capacity: 64.2 Sq.ft/Ton
Cooling Capacity Per Area: 0.0156 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 0.92 Tons

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 11

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Ssala De Equipos peaks (sensible) in December at 12am, Air Handler 1 (Sala De Equipos), Group
0, 8.8 x 10.8, Construction Type: 1 (Light)
Partition-1-1 94.79561 10/0 0.355 337 0.000 0
Partition-2-1 55.7 10/0 0.355 198 0.000 0
Partition-3-1 55.7 10/0 0.355 198 0.000 0
Partition-4-1 170.6 10/0 0.355 606 0.000 0
Partition-5-1 170.6 10/0 0.355 606 0.000 0
Lights-Prof=0 114 1.000 388
Equipment-Prof=0 5,000 1.000 17,061 0
People-Prof=0 0.9 1.000 237 190
Sub-total 19,629 190 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 21,592 209 0

Zone 2-Sala De Resonancia peaks (sensible) in December at 12am, Air Handler 2 (Sala De Resonancia),
Group 0, 32.7 x 10.8, Construction Type: 1 (Light)
Partition-1-1 352.1748 10/0 0.355 1,250 0.000 0
Partition-2-1 191 10/0 0.355 678 0.000 0
Partition-3-1 223.4 10/0 0.355 793 0.000 0
Partition-4-1 191 10/0 0.355 678 0.000 0
Partition-5-1 223.4 10/0 0.355 793 0.000 0
Lights-Prof=0 423 1.000 1,442
Equipment-Prof=0 3,000 1.000 10,236 0
People-Prof=0 1.0 1.000 250 200
Sub-total 16,121 200 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 17,733 220 0

Zone 3-Sala De Control peaks (sensible) in December at 12am, Air Handler 3 (Sala De Control), Group 0,
5.5 x 10.8, Construction Type: 1 (Light)
Partition-1-1 58.9648 10/0 0.355 209 0.000 0
Partition-2-1 65.6 10/0 0.355 233 0.000 0
Partition-3-1 126.3 10/0 0.355 448 0.000 0
Partition-4-1 65.6 10/0 0.355 233 0.000 0
Partition-5-1 126.3 10/0 0.355 448 0.000 0
Lights-Prof=0 71 1.000 241
Equipment-Prof=0 2,000 1.000 6,824 0
People-Prof=0 0.6 1.000 147 118
Sub-total 8,785 118 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 9,663 130 0

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 12

Air System #1 (Sala De Equipos) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.331 55.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 209 0.266 21,592 17.000 1,159
Sensible Reserve 0 0.000 0
Zone Condition 209 58.596 21,592 72.000 1,159
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 0 CFM 0 0.000 0 0.000
Blow-Thru Fan 567 0.447
Entering Coil Condition 209 58.596 22,159 72.447 1,159

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.996 x 1.10 x 1,159 x( 72.447 - 55.000 )= 22,159 Btuh


TLH = 0.996 x 0.68 x 1,159 x( 58.596 - 58.331 )= 209 Btuh
----------
SUM = 22,368 Btuh
GTH = 0.996 x 4.50 x 1,159 x( 26.540 - 22.246 )= 22,308 Btuh
Total System Load = 22,368 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 22,308 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 72.45 Dry bulb temperature: 72.00
Wet bulb temperature: 60.23
Relative humidity: 49.24
Enthalpy: 26.54 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 72.00
Wet bulb temperature: 53.40
Relative humidity: 90.40
Enthalpy: 22.25 Btu/lbm

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 13

Air System #2 (Sala De Resonancia) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.255 55.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 220 0.341 17,733 17.000 952
Sensible Reserve 0 0.000 0
Zone Condition 220 58.596 17,733 72.000 952
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 352 CFM 15,218 22.992 2,315 2.219
Blow-Thru Fan 466 0.447
Entering Coil Condition 15,438 81.589 20,514 74.666 952

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.996 x 1.10 x 952 x( 74.666 - 55.000 )= 20,514 Btuh


TLH = 0.996 x 0.68 x 952 x( 81.589 - 58.255 )= 15,046 Btuh
----------
SUM = 35,560 Btuh
GTH = 0.996 x 4.50 x 952 x( 30.675 - 22.235 )= 36,018 Btuh
Total System Load = 35,952 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 36,018 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 74.67 Dry bulb temperature: 72.00
Wet bulb temperature: 65.88
Relative humidity: 63.31
Enthalpy: 30.68 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 72.00
Wet bulb temperature: 53.38
Relative humidity: 90.28
Enthalpy: 22.23 Btu/lbm

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 14

Air System #3 (Sala De Control) Psychrometric Analysis


System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 58.227 55.000
Draw-Thru Fan 0 0.000 0
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 0 0.000 0
Zone Loads 130 0.369 9,663 17.000 519
Sensible Reserve 0 0.000 0
Zone Condition 130 58.597 9,663 72.000 519
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 20 CFM 849 2.355 129 0.227
Blow-Thru Fan 254 0.447
Entering Coil Condition 979 60.951 10,047 72.674 519

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.996 x 1.10 x 519 x( 72.674 - 55.000 )= 10,047 Btuh


TLH = 0.996 x 0.68 x 519 x( 60.951 - 58.227 )= 957 Btuh
----------
SUM = 11,004 Btuh
GTH = 0.996 x 4.50 x 519 x( 26.963 - 22.230 )= 11,005 Btuh
Total System Load = 11,026 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 11,005 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 72.67 Dry bulb temperature: 72.00
Wet bulb temperature: 60.84
Relative humidity: 50.81
Enthalpy: 26.96 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 72.00
Wet bulb temperature: 53.37
Relative humidity: 90.22
Enthalpy: 22.23 Btu/lbm

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
pReJkEr Sanna Trujillo
Hell Page 15

Building Pie Charts


Building peaks in March at 4pm.

Lighting - 3.29% Blow-Thru Fan - 1.86%

Cool. Vent. - 26.69%

Building
Net Gain
69,345
Btuh
Equipment - 54.13%

Partition - 12.23%

People - 1.81%

C:\Users\Edgar Chara\Desktop\SANNA TRUJILLO.CHV viernes, 18 de Febrero de 2022, 12:18 p. m.