Professional Documents
Culture Documents
Uzair Ahmed
Uzair Ahmed
Experiment 05
Objective:
To study the A.C power calculations.
To Calculate Active, Reactive Power and apparent power.
To study the power factor correction.
Introduction:
Power: Electrical Power is the rate of doing electrical work by transferring the electrical charge
from one point to the other within the circuit.
w = dq / dt
Real Power or Active Power: The power dissipated in the Resistor is the Active Power. It is
also called Real Power. This power is unidirectional (Source to Load). It does not flow back to
the Circuit. In AC the time averaging of instantaneous power is done over a complete cycle. It is
usually denoted by P.
It is calculated as P = VI cos
It is measured In Watts.
Reactive Power: The Power dissipated in the Inductance or Capacitance is known as the
Reactive Power. This power is bidirectional (Source to Load to Source).It moves back and forth.
It is usually denoted by Q.
It is calculated as Q = VI sin
It is measured in VARs.
Complex Power:
The Phasor sum of the Active and Reactive Power is the Complex Power. Its magnitude is
known as the apparent power. It is usually denoted by S.
It is a Phasor quantity so we need to evaluate its magnitude and phase .It is calculated as
[S] = {Re(S)}2 +{Im(S)}2 = tan−1([Im(S) / Re(S )]
It is measured in VA.
The Phasor Diagram for the relation between the active and reactive power is shown below
Experiment 05 Page 1
Lab 05: Sinusoidal Steady State Power Measurements
(Real, Reactive and Apparent Power) and
PowerFactor Correction.
reference to each other.
Experiment 05 Page 2
Lab 05: Sinusoidal Steady State Power Measurements
(Real, Reactive and Apparent Power) and
PowerFactor Correction.
1. First of all we will construct the circuit on the PCB according to the circuit diagram (Fig
2) given below. We will choose values according to the values specified
Experiment 05 Page 3
Lab 05: Sinusoidal Steady State Power Measurements
Spring
(Real, Reactive and Apparent Power) and
2016
Power Factor Correction.
9. We will then calculate the value of Q by using the Pythagorean theorem.We can also
determine the value of Q by measuring the length of the Side of the Power Triangle.
1
10. We will then find the value of C by virtue of the formula C =
2fX
11. According to this value of C we will insert a closely valued Capacitence.in the circuit
Experiment 05 Page
3
With C:
Without C:
Experiment 05 Page
4
I With C:
Experiment 05 Page
5
I Without C:
Experiment 05 Page
6
Lab 05: Sinusoidal Steady State Power Measurements Spring
(Real, Reactive and Apparent Power) and 2016
Power Factor Correction.
amps). In less favorable circumstances you may have to use an oscilloscope to compare voltage
and current waveforms, measuring phase shift in degrees and calculating power factor by the
cosine of that phase shift.
Most likely, you will have access to a wattmeter for measuring true power, whose reading you
can compare against a calculation of apparent power (from multiplying total voltage and total
current measurements). From the values of true and apparent power, you can determine reactive
power and power factor. Let's do an example problem to see how this works:
Wattmeter reads true power; product of voltmeter and ammeter readings yields appearant
power.
First, we need to calculate the apparent power in kVA. We can do this by multiplying load
voltage by load current:
As we can see, 2.308 kVA is a much larger figure than 1.5 kW, which tells us that the power
factor in this circuit is rather poor (substantially less than 1). Now, we figure the power factor of
this load by dividing the true power by the apparent power:
Using this value for power factor, we can draw a power triangle, and from that determine the
reactive power of this load: (Figure below)
Experiment 05 Page 4
Lab 05: Sinusoidal Steady State Power Measurements Spring
(Real, Reactive and Apparent Power) and 2016
Power Factor Correction.
Reactive power may be calculated from true power and appearant power.
To determine the unknown (reactive power) triangle quantity, we use the Pythagorean Theorem
“backwards,” given the length of the hypotenuse (apparent power) and the length of the adjacent
side (true power):
If this load is an electric motor, or most any other industrial AC load, it will have a lagging
(inductive) power factor, which means that we'll have to correct for it with a capacitor of
appropriate size, wired in parallel. Now that we know the amount of reactive power (1.754
kVAR), we can calculate the size of capacitor needed to counteract its effects:
Experiment 05 Page 5
Lab 05: Sinusoidal Steady State Power Measurements Spring
(Real, Reactive and Apparent Power) and 2016
Power Factor Correction.
Rounding this answer off to 80 µF, we can place that size of capacitor in the circuit and calculate
the results: (Figure below)
Experiment 05 Page 6
Lab 05: Sinusoidal Steady State Power Measurements Spring
(Real, Reactive and Apparent Power) and 2016
Power Factor correction.
This correction, of course, will not change the amount of true power consumed by the load, but it
will result in a substantial reduction of apparent power, and of the total current drawn from the
240 Volt source: (Figure below)
Experiment 05 Page 7
Lab 05: Sinusoidal Steady State Power Measurements Spring
(Real, Reactive and Apparent Power) and 2016
Power Factor Correction.
This gives a corrected power factor of (1.5kW / 1.5009 kVA), or 0.99994, and a new total
current of (1.50009 kVA / 240 Volts), or 6.25 amps, a substantial improvement over the
uncorrected value of 9.615 amps! This lower total current will translate to less heat losses in the
circuit wiring, meaning greater system efficiency (less power wasted).
Experiment 05 Page 8