NATIONAL INSTITUTE OF TECHNOLOGY SILCHAR
Electrical Engineering Department
MID Semester Examination (Online), Mareh-2022
Switchgear and Protection (EE-306)
Total Marks: 30 Time: 1 hr 15 Min
Instructions:
4
aia
All quesons ere compuluory. The mark against each question is shown at the ight se ofthe questions
Provide nceaary steps in solving al he numerical
‘Students need to write Name and Scholar number a the top ofeach page of the answer scrip distin
‘The tne wil tart 430 PM and wll fish a1 5.45 PM, Late submission i not ended.
Copying fom books wil be checked with Plagariem software aed i'sialaity Index more than 20%, marks wil be deducted fom the obtained marks
Answer script mast be submited in PDF in Google class Reom onl.
Explain clearly the sources of short circuit power in a power system and the nature of
such power.
‘A three-phase transmission line operating at 33kV and having a resistance and
reactance of 5Q and 20Q respectively is connected to a generating station busbar
through a ISMVA step-up transformer which has a reactance of 0.06 per unit (p.v).
Two generators, one IOMVA having 0.1pu reactance and another SMVA having
0.075pu reactance are connected to the bus bar. Calculate the short circuit MVA and
fault MVA when fault occurs (a) at the high voltage terminals of the transformer, and
(b) at the load end of the transmission line
Enumerate the positions in which current limiting reactors may be connected. Also
explain the objective of sectionalizing the bus bars in a large power section.
Considera balanced three-phase delta load connected across an unbalanced three phase
supply system, as shown in Fig.1. The currents in lines a, and b are given.
1-104 A
Fig.1 Balanced delta-connected load on an unbalanced three-phase power supply.
Calculate the currents in the delta-connected load and also the symmetrical
components of line and delta currents. From these calculations, establish the phase
shifis of positive and negative sequence components in delta windings and line
currents.
Consider a sub-transmission system as shown in Fig. 2. A 13.8-KV generator G1
voltage is stepped up to 138 kV. At the consumer end the voltage is stepped down to
13.8kV, and generator Gz operates in synchronism with the supply system. Bus B has
a 10,000-hp motor load. A line-to-ground fault occurs at bus B. It is required to
calculate the fault current distribution throughout the system and also the fault
voltages. The resistance of the system components is ignored in the calculations. The
col
co2
C03
col
co2
+03
545impedance data for the system components are shown in Table 1. Assume suitable
data wherever necessary.
Fig.2 A single line diagram of power system
Tablel. Impedance Data
Equipment | Description Impedance data
G 13.8-KV, 60 MVA, | Sub-iransient reactance =15%,
0.85 power factor | Transient reactance = 20%,
generator Zero sequence reactance =
896, Negative sequence
reactance =16.8%
Tr T3.8/138KV step-up | Z = 9% on 50-MVA base ME X=
transformer, 50/84 Xo= 0.18
MVA, AY
connected, y
neutral solidly
grounded
Ieee Transmission line, 5 | Conductors at 15% (4.57 m) | Xi= X=
miles long, 266.8 | equivalent spacing
KCMIL, ACSR
Te [138/132 kV, 30|Z=8%
MYA step-down
transformer, Y-A
connected, high
voltage Y neutral
solidly grounded
Gz 13.8 kV, 30 MVA | Sub-transient reactance =11%,
0.85 power factor | Transient reactance =15%.
generator Zero sequence reactance =
6%,
‘Negative sequence reactance
=16.5% tea
M 10,000 HP | Locked rotor resistance = 16.7 | Xi=1.67
induction motor | % on motor base KVA.
load (consider 1 HP = 1 KVA)
Resistances are neglected in calculations.
KCMIL- Kilo circular miles, same as MCM.
ACSR: Aluminum Conductor Stee! Reinforced.