You are on page 1of 2
NATIONAL INSTITUTE OF TECHNOLOGY SILCHAR Electrical Engineering Department MID Semester Examination (Online), Mareh-2022 Switchgear and Protection (EE-306) Total Marks: 30 Time: 1 hr 15 Min Instructions: 4 aia All quesons ere compuluory. The mark against each question is shown at the ight se ofthe questions Provide nceaary steps in solving al he numerical ‘Students need to write Name and Scholar number a the top ofeach page of the answer scrip distin ‘The tne wil tart 430 PM and wll fish a1 5.45 PM, Late submission i not ended. Copying fom books wil be checked with Plagariem software aed i'sialaity Index more than 20%, marks wil be deducted fom the obtained marks Answer script mast be submited in PDF in Google class Reom onl. Explain clearly the sources of short circuit power in a power system and the nature of such power. ‘A three-phase transmission line operating at 33kV and having a resistance and reactance of 5Q and 20Q respectively is connected to a generating station busbar through a ISMVA step-up transformer which has a reactance of 0.06 per unit (p.v). Two generators, one IOMVA having 0.1pu reactance and another SMVA having 0.075pu reactance are connected to the bus bar. Calculate the short circuit MVA and fault MVA when fault occurs (a) at the high voltage terminals of the transformer, and (b) at the load end of the transmission line Enumerate the positions in which current limiting reactors may be connected. Also explain the objective of sectionalizing the bus bars in a large power section. Considera balanced three-phase delta load connected across an unbalanced three phase supply system, as shown in Fig.1. The currents in lines a, and b are given. 1-104 A Fig.1 Balanced delta-connected load on an unbalanced three-phase power supply. Calculate the currents in the delta-connected load and also the symmetrical components of line and delta currents. From these calculations, establish the phase shifis of positive and negative sequence components in delta windings and line currents. Consider a sub-transmission system as shown in Fig. 2. A 13.8-KV generator G1 voltage is stepped up to 138 kV. At the consumer end the voltage is stepped down to 13.8kV, and generator Gz operates in synchronism with the supply system. Bus B has a 10,000-hp motor load. A line-to-ground fault occurs at bus B. It is required to calculate the fault current distribution throughout the system and also the fault voltages. The resistance of the system components is ignored in the calculations. The col co2 C03 col co2 +03 545 impedance data for the system components are shown in Table 1. Assume suitable data wherever necessary. Fig.2 A single line diagram of power system Tablel. Impedance Data Equipment | Description Impedance data G 13.8-KV, 60 MVA, | Sub-iransient reactance =15%, 0.85 power factor | Transient reactance = 20%, generator Zero sequence reactance = 896, Negative sequence reactance =16.8% Tr T3.8/138KV step-up | Z = 9% on 50-MVA base ME X= transformer, 50/84 Xo= 0.18 MVA, AY connected, y neutral solidly grounded Ieee Transmission line, 5 | Conductors at 15% (4.57 m) | Xi= X= miles long, 266.8 | equivalent spacing KCMIL, ACSR Te [138/132 kV, 30|Z=8% MYA step-down transformer, Y-A connected, high voltage Y neutral solidly grounded Gz 13.8 kV, 30 MVA | Sub-transient reactance =11%, 0.85 power factor | Transient reactance =15%. generator Zero sequence reactance = 6%, ‘Negative sequence reactance =16.5% tea M 10,000 HP | Locked rotor resistance = 16.7 | Xi=1.67 induction motor | % on motor base KVA. load (consider 1 HP = 1 KVA) Resistances are neglected in calculations. KCMIL- Kilo circular miles, same as MCM. ACSR: Aluminum Conductor Stee! Reinforced.

You might also like