You are on page 1of 56

Liquid immersed

Distribution Transformer

Trung Nam

Rated Power: 5000 kVA


Material No.: 2200014307
Siemens Aktiengesellschaft Österreich
Transformers Weiz

Table of contents
1 - Safety Regulations 3
1.1 - Introduction 3
1.2 - Warning instructions and pictograms 3
1.3 - Generally applicable safety regulations 4

2 - Technical design 6
2.1 - Designs 6
Design Hermetically Sealed 6

2.2 - Tank 7
Corrugated Wall Tank 7

2.3 - Iron Core 8


2.4 - Windings 9
2.5 - Bushings 10
2.6 - Insulating Fluids 11
2.7 - Surface Protection 12
2.8 - Protection devices and transformer components 13
Bushing 1kV-3150A CEDASPE 14
Bushing 400T1-AR EUROMOLD 15
Insulating fluid Nytro-Taurus NYNAS 17
Resistance thermometer RODAX PT100-PPO 19
Pressure relief device T10 ELMEK 20
Protection block DGPT2 AUTOMATION-2000 21

3 - Delivery 37
3.1 - Lifting and Transporting 37
3.2 - Securing transformers on trucks 42
3.3 - Incoming goods inspection 45
3.4 - Storage 46

4 - Installation- Commissioning- Operation 47


4.1 - Installation 47
4.2 - Commissioning 50
4.3 - Operation 48

5 - Service and Maintenance 52


6 - Disposal 54
7 - Warranty 55
8 - Imprint 56

2200014307_R00_Usermanual.pdf Rev. 0 Page 2 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

1 Safety regulations

1.1 Introduction
Compliance with the general safety regulations, the regulations and legal requirements applicable to
the specific installation site, and the regulations outlined in this User Manual is essential during
every phase of the lifecycle of the transformer, without exception.

These operating instructions contain important danger, warning and safety instructions that must be
observed by the user.

This transformer is only intended for the defined application use described in the User Manual
Operation outside the definition of proper use is not permitted, and in the case of non-compliance
with the described safety measures any warranty or liability claims against Siemens Weiz will be
invalidated.

This transformer must be transported, installed, commissioned, operated, maintained and disposed
of exclusively by qualified personnel. It is recommended that these activities are supervised by the
operator personnel.
The qualified personnel must be authorized to perform this work and must be familiar with the
procedures for handling transformers and the safety-related instructions in this User Manual.

1.2 Warning instructions and pictograms


Compliance with the safety instructions defined in this User Manual is essential during every phase
of the lifecycle of the transformer. The phases are delivery, installation, commissioning, operation,
maintenance and disposal of the transformer.

This symbol indicates a high level of risk. Ignoring the safety


instructions will result in a high level of danger for personnel,
environment and property.

This symbol indicates a medium level of risk. Ignoring the safety


instructions will result in danger for personnel, environment and
property.

This symbol indicates a low level of risk. Ignoring the safety instructions
will result in a low level of danger or possibility of danger for personnel,
environment and property.

2200014307_R00_Usermanual.pdf Rev. 0 Page 3 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

Prohibited Lifting or tieing down of Operating is prohibited


transformer components using
lifting eyes is prohibited

Warning against Warning against dangerous, Warning against suspended


hazardous location electrical voltage loads

Requirement Refer to User Manual Use personal protective


clothing and equipment

1.3 Generally applicable safety regulations


The generally applicable safety regulations have been drafted with reference to the ISO 60076
standard and must be complied with under all circumstances.

For all activities involved in the lifecycle of the transformer, qualified


personnel must be deployed with sufficient knowledge and experience of
handling transformers who are also familiar with the applicable standards,
regulations, guidelines and accident prevention regulations.

Lifting tackle (ropes, chains, hooks) and lifting gear (lifting beams, crossbars)
must be inspected before use. It is only permitted to use approved and
suitable lifting gear.

2200014307_R00_Usermanual.pdf Rev. 0 Page 4 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

Before any work starts on the transformer, the "5 Safety Rules" must be
applied:
1. Isolate
2. Lockout and tagout to prevent reconnection
3. Check that the equipment is at zero potential
4. Perform grounding and short-circuiting
5. Provide protection by covers or barriers for any neighboring live parts

Compliance with the safety instructions of this User Manual is essential under
all circumstances.

To prevent damage to bushings, it is not permitted to tie down transformer


components, such as the protective casing or tank, using the lifting eyes.
Compliance with the safety pictograms applied to the transformer is
mandatory.

The applicable national regulations and guidelines, as well as the User


Manuals for all equipment that is deployed, must be observed.

For all activities involved in the lifecycle of the transformer, the applicable
safety regulations must be observed regarding the wearing of personal
protective clothing and equipment.

2200014307_R00_Usermanual.pdf Rev. 0 Page 5 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.0 Technical description

2.1 Hermetically sealed design


In the hermetically sealed transformer design, the entire internal volume of the tank is filled with
insulating fluid as far as the bottom edge of the cover and including the bushings.

Hermetically sealed transformers are equipped with a corrugated wall tank. The change in volume of
the insulating fluid, resulting from the temperature rise of the transformer during operation, is
compensated by expansion of the corrugated wall.

The hermetically sealed system ensures that there is no contact between the insulating fluid and the
ambient air.

2200014307_R00_Usermanual.pdf Rev. 0 Page 6 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.2 Corrugated wall tank


With this tank design, heat is dissipated through the surface of the corrugated walls arranged on the
outside of the transformer. The surface and the number of corrugated walls are determined by the
amount of heat to be dissipated.

The corrugated walls are made of cold-rolled 1 to 1.5 mm flat steel.

The corrugated walls of transformers with built-on conservators can be beaded for the purposes of
surface bracing. With this type of tank, the expansion in the insulating fluid is transferred to the
conservator.

The corrugated wall tank is welded onto two wheel brackets. In accordance with the transport
concept the wheels are either mounted, or supplied disassembled and separately with the
transformer.

The corrugated wall tank has an M12 ground connection. The screws of the ground connection are
painted red. All the main components of the transformer that are removable are connected to the
ground potential of the corrugated wall tank by means of ribbon cable.

Corrugated wall tanks are equipped as standard with a main ground connection. This ground
connection is labelled with a ground symbol.

The tank is sealed with a sheet steel cover. This can be chamfered or flat. The thickness of the
sheet steel and the bracing is dimensioned for the prospective stresses during operation and
transport.

The cover can be mounted on the tank by bolting or welding.


The cover is fitted with at least two lifting eyes, one M12 ground connection, one or more
thermometer bags, as well as customized connections.

2200014307_R00_Usermanual.pdf Rev. 0 Page 7 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.3 Iron core


The iron core has an oval or round cross-section depending on the prevailing short-circuit forces of
the winding.

The electric sheet steel is grain-oriented, silicon-alloyed and cold-rolled. Depending on the quality,
subsequent laser treatment may be required.

The standard three-phase core comprises a top and bottom yoke and three legs. The core is fixed in
the transformer by means of a clamping structure that is connected to the transformer cover via
threaded rods or steel bands.

The core laminations are coated with special insulation on both sides. The yoke and leg laminations
are cut free of burrs and coated using the STEP-LAP technique to reduce no-load losses and
operating noise as far as possible.

2200014307_R00_Usermanual.pdf Rev. 0 Page 8 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.4 High-voltage and low-voltage windings


The low-voltage winding is wound around a round or oval mandrel by a winding machine. The high-
voltage winding is wound concentrically onto the low-voltage winding. The high-voltage and low-
voltage windings are separated by the high-low space. This can be fitted with a grounded screening
foil, if required.

The winding conductors can be constructed from round, flat or strip material. The material of the
high-voltage and low-voltage windings can be copper or aluminum.

The conductor materials are bare or insulated with lacquer or paper.

The insulation material of the windings is partially coated with epoxy resin. In the course of the
drying process, the layers of the winding bond to form a compact winding block.

The layer insulation is wedge-shaped to counteract the stress on the winding caused by the
alternating voltage.

2.4.1 Tap changer


The windings can be fitted with a tap changer for adapting the transformer to the line voltage. The
tap changer alters the ratio of the high-voltage winding to the low-voltage winding for the purpose of
setting the no-load voltage required at the secondary side.

All connecting leads in the transformer are designed with short-circuit protection and sufficient
breakdown strength.

Unless an on-load tap changer is installed, the tap changer is only permitted
to be operated in the zero-voltage state.

2.4.2 Cooling methods


The table describes the possible cooling methods for the insulating fluid and windings

Air cooling Water cooling


Forced Forced
Natural cooling Natural cooling
cooling cooling
Natural
ONAN ONAF ONWF
Mineral

cooling
oil

Forced
cooling
OFAF OFWF

Natural
cooling
KNAN KNAF KNWF
Ester

Forced
cooling
KFAF KFWF

2200014307_R00_Usermanual.pdf Rev. 0 Page 9 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.5 Bushings
The high-voltage and low-voltage windings are connected in the transformer according to the
specified vector group and routed out of the transformer via terminal leads and bushings typically
located in the transformer cover.

Depending on the customer requirements, the bushings can be designed as straight or angled,
porcelain or plug-type bushings.

To provide protection against electric shock, the bushings can be implemented with voltage-isolated
covers (terminal boxes) or as plug-type bushings with proetction against electric shock, as required.
In both cases, direct access to live bushing components is prevented.

Compliance with the tightening torques specified in Section 4.1.2 is essential


to prevent damage to the bushings.

2200014307_R00_Usermanual.pdf Rev. 0 Page 10 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.6 Insulating fluids


The insulating fluid in the transformer serves to cool the active part in the tank and to insulate it
against flashover.

Mineral oil, silicon oil and insulating fluids based on ester are in general use.

Mineral oils are available in inhibited and non-inhibited form. Inhibited mineral oils are oils that have
been artificially aged to give greater resistance to aging. Non-inhibited oils age in a controlled and
predictable manner under constant load.

Silicon oils are only used when expressly requested by the customer, due to their poor levels of
viscosity and low environmental compatibility.

Insulating fluids based on ester have excellent environmental compatibility and are preferred in
applications subject to high environmental requirements.

2200014307_R00_Usermanual.pdf Rev. 0 Page 11 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.7 Surface protection


The surface finish of Siemens Weiz transformers comply with the applicable version of ISO standard
12944 – 4 / Sa 2.5 for coated steel components and 12944 – 4 / Be for zinc-plated steel
components.

The surface coating complies with ISO 12944 – 5.

Coat
Corrosion Intermediate
Preparation Primer Top coat thickness
category coat
(NDFT)

C5-M Sa 2.5 40 µm 2 x 80 µm 40 µm 240 µm

C4 Sa 2.5 40 µm 2x40 µm 40 µm 160 µm

C2 Sa 2.5 40 µm 40 µm 40 µm 120 µm

Zinc-plated transformers are manufactured to ISO 1461.

2200014307_R00_Usermanual.pdf Rev. 0 Page 12 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

2.8 Protection devices and transformer components


Protection devices are purchased components. Please find the information regarding assembly,
implementing, maintenance and possibly disposal on the following pages issued by manufacturers
and in the description of the components. Since the documentation is provided by the manufacturer
of the component, we can not affect the language they provide.

2200014307_R00_Usermanual.pdf Rev. 0 Page 13 of 56


2200014307_R00_Usermanual.pdf Rev. 0 Page 14 of 56
400T1 /400AR-1 /400AR-2
INTERFACE B
EQUIPMENT BUSHINGS

Application Technical characteristics Up to 36 kV - 400 A


For use in equipment insulated Each bushing is tested for
with oil fluid, typically for AC withstand and partial
transformers, switchgear, discharge prior to leaving the
capacitors... factory.
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV

Specifications and
standards
The plug-in type equipment
bushings are moulded epoxy
133
insulated parts and meet the
requirements of IEC 60137.
The (K)(M)400T1 also meets
CENELEC EN 50180 . C

10

Ordering instructions A
To order the equipment
bushing, specify the type.
The bushings are supplied B
with an earth jumper (/J) or an
Minimum oil level: Dia.
earth plate (/GS). This earth - 12 kV: 40 mm H
connection must be specified - 24 kV: 50 mm
- 36 kV: 75 mm
when ordering.
E.g. K400AR-1/J.
E

D
Dia. 70
Dia. F
Dia. G
In mm.

Equipment Voltage Current Dimensions (mm)


bushing Ur Ir
type (kV) (A) A B C D E Dia. F Dia. G Dia. H
400T1 12 400 310 144 30 M12 22 88 128 16
K400T1 24 400 310 144 30 M12 22 88 128 16
M400T1 36 400 310 144 30 M12 22 88 128 16
400AR-1 12 400 380 213 30 M12 22 74 128 16
K400AR-1 24 400 380 213 30 M12 22 74 128 16
M400AR-1 36 400 380 213 30 M12 22 74 128 16
400AR-2 12 400 329 138 36 M16 40 100 150 30
K400AR-2 24 400 329 138 36 M16 40 100 150 30
04/2012

M400AR-2 36 400 329 138 36 M16 40 100 150 30

8
2200014307_R00_Usermanual.pdf Rev. 0 Page 15 of 56
FIXINGS FOR
EQUIPMENT BUSHINGS
400AR-2/GS Bushing 400AR-2/J Bushing 400AR-1/J and 400T1/J
Bushings
bushing
bushing interface interface
fixing studs
fixing studs

fixing flange
fixing flange B DIN 42 538

NF C 52-053 F DIN 42 538


stud clamp E DIN 42 538
claw clamp
stud clamp

equipment
equipment

sealing gasket
sealing gasket

equipment
equipment
connection
connection

tabs for the tabs for the


bail restraint bail restraint

earth
jumper
earth
plate
earth
jumper

Bushing clamping kit Bushing clamping kit Bushing clamping kit


To order the bushing clamping To order the bushing clamping To order the bushing clamping
kit, according to NFC 52- kit, simply specify: KBCDS- kit, according to DIN 42 538
053 standards, simply specify 400B. standards, simply specify
KBCNF-400 (for bushing type Contents: - 1 x fixing flange KBCD-400B.
400AR-2). - 6 x stud clamp F Contents: - 1 x fixing flange B
Contents: - 4 x claw clamp NF - 1 x sealing gasket.
- 6 x stud clamp E
- 1 x sealing gasket.
- 1 x sealing gasket.

Fixing dimensions Fixing dimensions Fixing dimensions


standards NF C 52-053 standards DIN 42 538
French standards. German standards.

M10 or M12 M10 M10

50 to 70 60 55
25 30 30

4 fixing 6 fixing
Dia. 105 Dia. 105 6 fixing Dia. 90
studs studs
Dia. 171 Dia. 171 studs Dia. 140

In mm.

9
2200014307_R00_Usermanual.pdf Rev. 0 Page 16 of 56
STANDARD GRADE

Nytro Taurus
Electrical insulating oil

Nytro Taurus is an uninhibited transformer oil that conforms to IEC 60296 Edition 4.0. Developed and
formulated to deliver solid resistance to oil degradation, Nytro Taurus provides good oxidation stability
thanks to its natural inhibitors. This increases the possibilities for a longer transformer life with less
maintenance.

Designed for heavy duty Product description


This product has been specially developed for use in Nytro Taurus fulfils the requirements for IEC 60296
oil-filled electrical equipment – including power and Edition 4.0 uninhibited oil. Nynas classify this product
distribution transformers, rectifiers, circuit breakers and as a standard grade.
switchgears.
Nytro Taurus is rigorously analysed and passes the
following corrosion tests:
Performance and benefits - ASTM D1275
- IEC 62535
Good heat transfer. Thanks to low viscosity and - DIN 51353
viscosity index, this standard grade offers extremely
good heat transfer characteristics, ensuring heat is In accordance with IEC 60296 Edition 4.0, all additives
efficiently removed from core and windings. are declared.

Reliable oxidation stability. Developed and formulated


to deliver good resistance to oil degradation, this grade There’s more to us than this
also provides good oxidation stability for enhanced
transformer life and minimum maintenance. We’re delighted you chose one of our transformer oils.
If you have any questions about other products and
Very good low temperature properties. Naphthenic services, get in touch with your local Nynas contact.
characteristics allow the transformer to start at the Besides top quality oils, we offer a wide range of
lowest possible temperature – without using pour point services, including rapid delivery worldwide, sample
depressants. analysis, training, seminars and much more. All you
have to do is ask. Find out more at www.nynas.com
High dielectric strength. This insulating oil both meets
and exceeds the toughest demands on dielectric
strength – when stored and handled correctly.

2200014307_R00_Usermanual.pdf Rev. 0 Page 17 of 56


PRODUCT DATA SHEET

Nytro Taurus
PROPERTY UNIT TEST METHOD SPECIFICATION LIMITS TYPICAL DATA
MIN MAX
1 - Function
2
Viscosity, 40°C mm /s ISO 3104 12.0 9.8
2
Viscosity, -30°C mm /s ISO 3104 1800 1100
Pour point °C ISO 3016 -40 -51
Water content mg/kg IEC 60814 30 <20
Breakdown voltage
- Before treatment kV IEC 60156 30 40-60
- After treatment kV IEC 60296 70 >70
3
Density, 20°C kg/dm ISO 12185 0.895 0.868
DDF at 90°C IEC 60247 0.005 <0.001
2 - Refining/stability
Appearance IEC 60296 Clear, free from sediment complies
Acidity mg KOH/g IEC 62021 0.01 <0.01
Interfacial tension mN/m EN 14210 40 48

Corrosive sulphur DIN 51353 non-corrosive non-corrosive


Potentially corrosive sulphur IEC 62535 non-corrosive non-corrosive
Corrosive sulphur ASTM D 1275 non-corrosive non-corrosive
DBDS mg/kg IEC 62697-1 not detectable not detectable
Antioxidant wt % IEC 60666 not detectable not detectable

Metal passivator additives mg/kg IEC 60666 not detectable not detectable
2-Furfural and related compounds
mg/kg IEC 61198 0.05 <0.05
content
Aromatic content % IEC 60590 9
3 - Performance
Oxidation stability at 120°C,164 h IEC 61125 C
Total acidity mg KOH/g 1.2 0.60
Sludge wt % 0.8 0.14
DDF at 90°C 0.500 0.049
4 - Health, safety and environment (HSE)
Flash point, PM °C ISO 2719 135 150
PCA wt % IP 346 3 <3
PCB IEC 61619 not detectable not detectable
Nytro Taurus is an uninhibited insulating oil, meeting IEC 60296 Ed.4 (2012) General Severely Hydrotreated Insulating Oil
specifications. Breakdown voltage after treatment as per definition given in IEC 60296, Issuing date: 2017-10-11
section 6.4.

2200014307_R00_Usermanual.pdf Rev. 0 Page 18 of 56


2200014307_R00_Usermanual.pdf Rev. 0 Page 19 of 56
PRESSURE SAFETY VALVE

TYPE T-10

CONNECTION
TYPE CODE NO
DIAMETER
61101 R1”
T-10 61102 R1 ½”
61104 R2”
63101 R1”
T-10K1 63102 R1 ½”
63104 R2”

APPLICATION
The T-10 pressure safety valve is employed as a safety element in
distribution transformers of low rating. In the event of an explosion-
type pressure increase of the transformer tank, the excess pressure
must be relieved immediately in order to avoid damage to the tank.

These types are suıtable for hermetically sealed type transformers

CONSTRUCTION
The T-10 pressure safety valve consists of a brass cap, a conical valve
body, a rubber seal between the cap and body and a coil spring
holding the whole system. As soon as relief pressure is reached, the
valve cap lifts off and the excess pressure is relieved. The valve then
shuts itself down again automatically.

The valve can be infinitely set from 0.2 to 0.7 bar.

The valve can also be equipped with a specially manufactured


protective cap to prevent unauthorized operation of valve

PS 6 / B
2200014307_R00_Usermanual.pdf Rev. 0 Page 20 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 21 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 22 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 23 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 24 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 25 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 26 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 27 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 28 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 29 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 30 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 31 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 32 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 33 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 34 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 35 of 56
2200014307_R00_Usermanual.pdf Rev. 0 Page 36 of 56
Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.0 Delivery

3.1 Lifting and transporting


All transformers are fitted with lifting eyes. The lifting eyes are attached to the transformer cover.

Lifting tackle (ropes, chains, hooks) and lifting gear (lifting beams, crossbars)
must be inspected before use. It is only permitted to use approved and
suitable lifting gear.

Transformers are only permitted to be lifted using the lifting eyes attached to
the transformer cover.

2200014307_R00_Usermanual.pdf Rev. 0 Page 37 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.1.1 Lifting without a crossbar


Transformers without top-mounted protective casings can be lifted using ropes or chains.

The angle between the legs of the lifting gear must be ≤ 60°.

2200014307_R00_Usermanual.pdf Rev. 0 Page 38 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.1.2 Lifting with a crossbar


For transformers with top-mounted protective casings, a crossbar must be used.
Transformers with lifting eyes arranged transverse to the transformer length (as opposed to
lengthwise as shown in the diagram below) are only permitted to be moved using a crossbar.
Bending stress must not be applied to the lifting eyes.

The minimum permissible spacing between crossbar and transformer is 300 mm.

2200014307_R00_Usermanual.pdf Rev. 0 Page 39 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.1.3 Lifting with ground conveyors


Lifting and transporting with ground conveyors is permitted when the lifting mechanism of the ground
conveyor is placed immediately alongside or directly on the wheel brackets.

These transportation methods are likely to cause damage to the paint finish of the transformer.
Siemens Weiz will not accept any warranty claims from the customer for surface damage caused by
this transportation method.

It is not permitted to attach the lifting equipment to the corrugated walls.

2200014307_R00_Usermanual.pdf Rev. 0 Page 40 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.1.4 Pulling transformers


It is only permitted to pull transformers using the pulling eyes of the wheel brackets. Wheels must be
fitted for this purpose to the wheel brackets. The wheels must be mounted in the direction of towing.

The angle between the legs of the lifting gear must be ≥ 60°.

2200014307_R00_Usermanual.pdf Rev. 0 Page 41 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.2 Securing transformers on trucks


The information provided below has been compiled in compliance with EN 12195 "Load restraining
on road vehicles".

Unless special packaging is provided, the following minimum requirements apply to lashing
transformers onto trucks:

 To prevent tilting of transformers, they must be placed lengthwise on the truck. Wooden blocks
or pallets must be placed under the wheel brackets which, in turn, must be placed on anti-slip
matting.

To prevent the transformers from sliding across the loading surface of the
truck, the transformer must not make contact with the loading surface at any
point.

2200014307_R00_Usermanual.pdf Rev. 0 Page 42 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

 Only lashing straps may be used for securing the transformers to the loading surface.

 At least 2 lashing straps must be used for each transformer, which must be attached to the
fastening points provided on the frame of the loading surface on the truck.

Lashing straps must be checked before use. It is only permitted to use


lashing straps that have been approved in accordance with EN 12195-3.
Lashing straps are not permitted to be knotted.

 The lashing straps must be lashed through the lifting eyes located on the transformer cover and
around areas away from the corrugated walls of the tank. To prevent chafe points from occurring
where the straps change direction, edge protection must be inserted between the transformer
and the strap.

2200014307_R00_Usermanual.pdf Rev. 0 Page 43 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

 Lashing across the horizontal stiffening bar of the corrugated wall is not permitted, and would
result in damage to the transformer tank.

 If lashing eyes are mounted on the transformer tank, they must be used to secure the
transformer.

It is not permitted to lift the transformer using the lashing eyes on the
transformer tank, and this would result in damage to the transformer tank.

2200014307_R00_Usermanual.pdf Rev. 0 Page 44 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

 The straps must be tightened using the ratchet attached to the lashing strap and secured using a
strap lock.

To prevent damage to the bushings, it is not permitted to tie the transformer


down using lifting points of transformer components, such as those on the
protective casing. Observe the pictograms.

3.3 Incoming goods inspection


Before the transformers are shipped, they undergo a final inspection.

No matter how much care is taken, transport damage cannot be completely ruled out. The customer
must inspect the transformers for damage and leaks on delivery.

 The transformer must be inspected for damage

 The transformer must be inspected for leaks

 The rating plate data must be checked.

 The delivery documents must be compared with the scope of goods received.

 Any deviations from the contractually agreed scope of supply must be reported to Siemens
Weiz.

 By signing the delivery note, the customer or their authorized representative confirms that the
transformer was free of damage on delivery.

2200014307_R00_Usermanual.pdf Rev. 0 Page 45 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

3.4 Storage
 The ambient temperatures applicable to the storage of transformers correspond to the maximum
permissible ambient temperatures during operation and are stated on the data sheet. Siemens
Weiz transformers are designed as standard for operation at temperatures between -25° C and
+40°C.

 Transformers and their bushings must be protected from mechanical damage.

 If transformers are delivered in packaging, this must not be removed during storage.

 The transformer must be constantly stored on a solid base.

 It must be located at a suitable distance from water courses and open sewers.

 The transformer must be inspected for leak tightness.

 For transformers with built-on conservator, the silica gel of the dehumidifier must be checked
annually and replaced if necessary.

For conservator transformers and transformers with an open system, the


transport protection must be removed from the conservator and vent nozzle
before entering storage. Any supplied dehumidifier must be installed.

The applicable national regulations and guidelines, as well as the User


Manuals for all equipment that is deployed, must be observed.

2200014307_R00_Usermanual.pdf Rev. 0 Page 46 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

4.0 Installation, commissioning, operation


4.1 Installation

The applicable national regulations and guidelines, as well as the User


Manuals for all equipment that is deployed, must be observed.

Siemens Weiz transformers are supplied with wheels separately, or without, as required by the
customer.

The customer is responsible for installation.

Any data required for designing and rating the installation site, such as overall dimensions, spacing
of fixing holes, cable entry positions, or power losses will be supplied by Siemens Weiz.

The following points regarding the installation of transformers must be observed:

The foundations must be level, sufficiently large and rated for the static load.

In the case of outdoor installation, rain water must be diverted away from the transformer
foundations.

Collection troughs, hollows or basins for insulating fluids must be implemented in accordance
with the national regulations of the country of operation.

Unrestricted access to the rating plate, protective devices and display instruments must be
ensured.

For transformers without protective casings, compliance with the external clearances specified in
IEC 60076 is essential.

For installation indoors, depending on the power losses, an air flow of at least
3 – 4 m3 / min must be guaranteed.

The wheels of transformers must be equipped with clamping wedges or blocking devices.

When installation of the transformer has been completed, it must be inspected for damage to the
corrosion protection, especially on the lifting and pulling eyes.

2200014307_R00_Usermanual.pdf Rev. 0 Page 47 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

4.1.1 Electrical connections

Before any work starts on the transformer, the "5 Safety Rules" must be
applied:
1. Isolate
2. Lockout and tagout to prevent reconnection
3. Check that the equipment is at zero potential
4. Perform grounding and short-circuiting
5. Provide protection by covers or barriers for any neighboring live parts

The following points regarding the electrical connection of transformers must be observed:

Electrical connection of the transformer can be made on the high-voltage and low-voltage ends
via the bushings, copper busbars, terminals or plug-in sockets.

In all connection systems, supply lines must be fitted with strain relief. Inadequate strain relief
causes forces to be applied to the bushings and results in damage to the bushings and in
leakages.

If a protective casing is mounted on the transformer, the cable glands of the entry plate must not
be used as strain relief for the supply lines. Support for the deadweight of the cables must be
provided by the customer.

All screwed connections must be secured, to prevent loosening during operation.

The bending radii specified by the cable manufacturer must be complied with.

Dirt or condensate deposits resulting from transport or storage must be removed before
electrical connection.

Before commissioning, the transformer must be grounded through the main grounding point on
the wheel brackets. If the transformer cover and transformer tank are not connected by a
grounding strap, the transformer cover must also be grounded.

For porcelain bushings, the cable lug is clamped between the two nuts at the end of the bushing
(1) and (2). Nut (3) must not be loosened, because this would cause the insulating fluid to drain.

2200014307_R00_Usermanual.pdf Rev. 0 Page 48 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

4.1.2 Tightening torques


The tightening torques in the following tables must be observed. When the maximum torque has
been reached, it must be checked that the component is seated securely.
Standardized and tested tools must be used exclusively to achieve the required tightening torques.

Diagram: Description: Thread: Torque:


M8 10 Nm
M12 13 Nm
M20 30 Nm
Nut on conductor bolt for M30x2 70 Nm
high-voltage and low-
M42x3 110 Nm
voltage bushings
M48x3 180 Nm
M55x3 250 Nm
M75x3 250 Nm

M10 25 Nm

Clamping screw for low-


M12 40 Nm
voltage terminal lug

M16 90 Nm

Screws or cable lug for low-


M12 40 Nm
voltage busbar

Width across flats 6 25 Nm


Connecting terminal for low-
voltage bushing
Width across flats 8 55 Nm

Screws for cable entry


plates and protective casing M10 40 Nm
cover

M8 10 Nm
Nuts and bolts for outside
and inside cone bushings
M16x2 30 Nm

2200014307_R00_Usermanual.pdf Rev. 0 Page 49 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

4.2 Commissioning
The following points must be observed when commissioning the transformers:

For all activities involved in the lifecycle of the transformer, qualified


personnel must be deployed with sufficient knowledge and experience of
handling transformers who are also familiar with the applicable standards,
regulations, guidelines and accident prevention regulations.

Before commissioning starts, the transformer must be inspected for leaks. If any leaks are
detected, the transformer must not be commissioned. The oil level must be checked.

The position of the tap changer must be checked. The selected position must match the current
line voltage.

The relevant position for the voltage level is indicated on the rating plate.

For hermetically sealed transformers with temperature monitoring equipment, the maximum
permissible oil temperature on the rating plate must be observed.

Before commissioning, the transformer must be grounded through the main grounding point on
the carriage frame. If the transformer cover and transformer tank are not connected by a
grounding strap, the transformer cover must also be grounded.
It must be checked that grounding straps are installed for components and connected correctly.

For conservator transformers and transformers with an open system, the transport protection
must be removed from the conservator and vent nozzle before commissioning. Any supplied
dehumidifier must be installed.

It must be checked that the high-voltage and low-voltage connections have been installed
correctly. The tightening torques 4.1.2 must be observed.

If protective devices are mounted on the transformer, it must be checked that they are
functioning correctly before commissioning starts.

In cases where a Buchholz relay is installed, the transport restraint must be removed.

Before the voltage is applied, all covers, entry plates and caps must be installed.

During operation the bushings and all live parts have to be free from pollution.

2200014307_R00_Usermanual.pdf Rev. 0 Page 50 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

For transformers in parallel operation, the transmission ratios, including the tapping range, must
lie within the permissible tolerances. The matching short-circuit voltages must also lie within the
permissible tolerances of ± 10%.
The ratio of rated power is not permitted to exceed 1:3. The vector group must be identical.
Transformers with the hour digits 5 and 11 are the exception. These can operate in parallel with
each other provided that the terminals are connected as follows:

High-voltage: Low-voltage:

Busbar: L1 L2 L3 L1 L2 L3

Hour digit 5 1U 1V 1W 2U 2V 2W
Transformers

1U 1W 1V 2W 2V 2U
Hour digit 11
1W 1V 1U 2V 2U 2W
Alternatively
1V 1U 1W 2U 2W 2V

The applicable national regulations and guidelines, as well as the User


Manuals for all equipment that is deployed, must be observed.

4.3 Operation
Transformers with supervisory control must be monitored during operation for compliance with
operating limits.

Operation of the transformer outside the specified power limits will shorten
the life of the transformer.
(see IEC 60076-7)

2200014307_R00_Usermanual.pdf Rev. 0 Page 51 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

5.0 Service and maintenance


Transformers from Siemens Weiz can be generally regarded as maintenance-free. Disconnections
caused by supply conditions or scheduled process shutdowns should also be used for preventative
maintenance and service activities. Siemens Weiz recommends that service and maintenance
activities are recorded.
5.1 General recommendations for service and maintenance
The recommendations of Siemens Weiz for service and maintenance are shown in the table below:
Visual inspection of leak tightness
Inspection of corrosion protection

Replacement of the bladder of the


Replacement of the silica gel of

conservator (in case of bladder


Examination of insulating fluid

maintenance-free dehydrating
Operation of the tap changer

the dehumidifier (excepting


Functional check of the
supervisory control

conservator)
breather)
1 year

After 3
years, then
annually

Every 5
years

After 15
years

5.2 Removal of insulating fluid for analyses


The quality of the insulating fluid can be determined by removing and analyzing it. The results of this
analysis can be used to assess the condition of the active part.

Insulating fluid samples must be taken by suitably trained and qualified


personnel.

Removal must be performed in accordance with IEC 60475 for insulating fluids and IEC 60567 for
dissolved gases.

2200014307_R00_Usermanual.pdf Rev. 0 Page 52 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

5.2.1 Limiting values for the interpretation of insulating fluid examinations


The following limiting values refer exclusively to used insulating fluids.

OK No action necessary. Operation is permitted.

Insulating fluid must be replaced, regenerated or conditioned soon.


Overhaul
Temporary operation is permitted.

Danger Continued operation will cause damage to the active part of the
transformer. Operation is not permitted.

No. Test description OK Overhaul Danger


Breakdown voltage with 2.5 mm electrode
gap [kV]

Voltage class C up to 72.5 kV > 40 30 – 40 < 30


01
Voltage class B from 72.6 to 170 kV > 50 40 – 50 < 40

Voltage class A above 170 kV > 50 50 – 60 < 50


Interfacial tension [mN/m] for all voltage
02 > 50 28 – 22 < 22
classes
Dielectric loss factor at 90°C [W]

03 Voltage class B and C < 0,10 0,10 – 0,50 > 0,50

Voltage class A < 0,10 0,10 – 0,20 > 0,20


Specific contact resistance at
90 °C [G m]
04
Voltage classes B and C >3 0,20 – 3 < 0,20

Voltage class A > 10 1 – 10 <1


Neutralization number [mg KOH/g]

Voltage class C < 0,15 0,15 – 0,30 > 0,30


05
Voltage class B < 0,10 0,10 – 0,20 > 0,20

Voltage class A < 0,10 0,10 – 0,15 > 0,15


06 Color code according to ISO 2049 <2 2–3 >3

5.2.2 Inspection of insulating fluid condition


The condition of the insulating fluid of transformers must be checked periodically. The condition of
the insulating fluid must be checked in particular, following the removal of oil samples or following
detection of leaks, by means of the inspection windows, fill-level indicators or float switches
installed.

The Siemens Weiz service team must be contacted if the insulating fluid level falls below the
permitted level.

2200014307_R00_Usermanual.pdf Rev. 0 Page 53 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

6.0 Disposal

The applicable national regulations and guidelines, as well as the User


Manuals for all equipment that is deployed, must be observed.

The insulating fluid used in the transformer can present a danger to the environment if it enters the
ground or water courses.

The data sheets supplied for the insulating fluids and all other built-on components must be
consulted with regard to disposal of the transformer.

The manufacturer and trademark of the insulating fluid used are noted on the transformer rating
plate.

2200014307_R00_Usermanual.pdf Rev. 0 Page 54 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

7.0 Warranty, faults and damage

To ensure full warranty in the even of a fault or damage, all the safety
instructions of this User Manual must be complied with.

In the event of a fault or damage, the transformer must be isolated from the
power supply immediately to prevent secondary damage.

The warranty periods and warranty conditions are stated in the contract documentation.

Siemens Weiz will take no warranty in case of any changes on the transformer without approval
from Siemens Weiz. This is also valid in case of additional built up pumps, coolers, etc.

A service team from Siemens Weiz is available in the event of a fault or damage.

Siemens Aktiengesellschaft Österreich


Transformers Weiz

Transformer Lifecycle Management (TLM)

Elingasse 3
8160 Weiz
Austria

Tel: +43 51707 - 0


Fax: +43 51707 - 55445
Email: office.stw.at@siemens.com

2200014307_R00_Usermanual.pdf Rev. 0 Page 55 of 56


Siemens Aktiengesellschaft Österreich
Transformers Weiz

8.0 Imprint - Revision notes

Original User Manual of Siemens Aktiengesellschaft Österreich, Transformers Weiz

All rights are reserved for this document and for the information contained within it. Reproduction,
transmission to third parties and use of its contents are forbidden without the express permission of
Siemens AG Österreich, Transformers Weiz.

All rights reserved.


All trademarks and brands named in this document are the property of Siemens AG.

We reserve the right to make technical changes.


The information in this document comprises general descriptions of the technical possibilities, some
of which may not apply in the individual case. The performance features required for the individual
case must therefore always be specified in the contract.

Contact information:

Siemens AG Österreich
Transformers Weiz
E T TR LPT STW DT
Elingasse 3
8160 Weiz
Tel: +43 51707-0
www.siemens.at/transformers-weiz

Rev.: Reason for change: Date: Prepared by: Approved by:

0 Creation 2018-08-23 Friesenbichler, An. Friesenbichler, Andre.

2200014307_R00_Usermanual.pdf Rev. 0 Page 56 of 56

You might also like