You are on page 1of 23

ID-07-19-81

Installation instruction МКВ 252


High-voltage Cable Termination

Surname Signature Date


Terekhov 24.12.19
Developed by

Kintyukhin 24.12.19
Approval

Arkasil SK LLC
www.arkasil.com
info@arkasil.com
Installation instruction

МКВ 252
High-voltage Cable Termination.

Arkasil SK LLC 1
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
Table of contents
1. Field of application. ..................................................................................................................... 3
2. Generals. ...................................................................................................................................... 3
3. Cable preparation. ....................................................................................................................... 4
3.1. Quality of applied cable. ...........................................................................................................4
3.2. Determining point for cutting cable. ........................................................................................4
3.3. Straightening of the cable. .......................................................................................................5
4. Cable preparation for MKB 252 assembly. .................................................................................. 6
4.1. Cable sheath removal. ..............................................................................................................6
4.2. Cable stripping and grinding.....................................................................................................8
5. Assembly of main components. .................................................................................................. 9
5.1. Cable preparations for stress-cone assembly. .........................................................................9
5.2. Assembly of gasket and branch-pipe. ....................................................................................10
5.3. Centering sleeve installation. .................................................................................................12
5.4. Stress cone fitting. ..................................................................................................................12
5.5. Tape winding and control. ......................................................................................................13
5.6. Conductor connecting. ...........................................................................................................13
5.7. Composite insulator installation. ...........................................................................................15
5.8. Insulating compound filling. ...................................................................................................15
5.9. Top cover installation. ............................................................................................................16
5.10. Centering unit assembly. ......................................................................................................16
5.11. Shielding of centering unit. ..................................................................................................17
5.12. Screen wires soldering..........................................................................................................17
Appendix 1 ...................................................................................................................................179
Appendix 2 ..................................................................................................................................... 20
Appendix 3 ..................................................................................................................................... 21
Appendix 4 ..................................................................................................................................... 22

Arkasil SK LLC 2
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
1. Field of application.
Present instruction describes the assembling order of an HV cable termination MKB 252 for
cable with XLPE insulation and copper wires screen. Termination is suitable for both indoor and
outdoor installation.

2. Generals.
2.1. Read attentively the entire instruction before starting any actions.
2.2. Just after the package opening attentively check:
· Integrity of protective seals on the boxes and vessels with insulating compound.
· Integrity of the entire kit according with packing list.
· Cable diameter over insulation lies inside the stress cone stretching range.
· Availability of all required tools and additional materials (see Appendix 3, 4).
· Environmental conditions at the site are suitable for clean and correct installation (see
Cl.2.5).
2.3. The assembling must be realized by jointers brigade all members of which are certified in
working with high-voltage cables and special kinds of high-voltage accessories (which is
described in this installation instruction).
2.4. All of tapes should be winded with 50% overlap by default.
2.5. Environmental conditions for installation:
· Temperature range +10..+35 °С
· Relative humidity not exceeding 65%.
· Indoor conditions or a tent with no dust and moisture inside.
2.6. Add the environment temperature to the checklist (Cl.5. Appendix 1).
2.7. The assembling must be performed consequentially, following present instruction.
2.8. Prior to assembling fix the cable to the metallic frame by two non magnetic clamps at least
(Figure 2).
2.9. In case of horizontal installation perform the subsequent rise only after fixing of cable with
installed termination on a removable metal frame. Cable must be fixed coaxially with
termination according to Cl. 2.8.
2.10. Fill the operation assembly sheet in the checklist during the installation work (Appendix 1)

Arkasil SK LLC 3
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
3. Cable preparation.
3.1. Quality of applied cable.
Make sure that cable doesn’t have any flat sides, out-of-roundness or eccentricity doesn’t
exceed 5% (see Table 1). In case of unsatisfactory results, immediately contact to chief
engineer.

Table 1

Eccentricity not more than 5%

Out-of-roundness not more than


5%

Is not allowed

3.2. Determining point for cutting cable.


3.2.1. Prior installation cable should be fixed on a metal basement by two cable clamps.
3.2.2. Measure the length of external insulator L (Figure 1)

Figure 1 The length of external insulator Figure 2 The place for cable removing

3.2.3. Add the length of external insulator to the


checklist (Cl.3. Appendix 1)
3.2.4. Place a control mark for level of metallic frame
on the cable (Figure 2)
3.2.5. Trim the cable at a length of L+110 mm from
the control mark toward the free end (Figure 2).
3.2.6. Add the length of cut cable L+110mm to the
checklist (Cl.6. Appendix 1)

Arkasil SK LLC 4
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
3.3. Straightening of the cable.
Attention: Cable must be straightened in case if its bending exceeds 5mm/m.
3.3.1. Wind crepe paper over the sheath of the cable in one layer at a 3 meters length
3.3.2. Wind heat tape over the crepe paper (№6 Appendix 3). Wind tape with uniform spacing.
3.3.3. Install temperature-sensitive element and temperature-control device under heat tape.
Fix them with self-adhesive tape 13.
Attention: At least one temperature-sensitive element must be installed under each heat tape.
3.3.4. Fix the ends of heat tapes on cables with self-adhesive tape 13.
3.3.5. Wind crepe paper on the heat tapes with one layer. Leave plastic handle of the
temperature control element outside.
3.3.6. Cover heating section with felt (№48 Appendix 3) or with fire-resistant covering. Fix it
with self-adhesive tape 13 or with PVC tape.
3.3.7. Connect power cable with temperature-control device.
3.3.8. Turn on temperature-control device into electric mains. Choose correct temperature
according to the Table 2

Table 2
cross-section of cable’s conductor Time Temperature
to 1000 mm2 including 8 hours 85°С
over 1200 mm2 10 hours 85°С

3.3.9. Add temperature of heating to the checklist (Cl.1. Appendix 1).


3.3.10. Remove heat proof materials, crepe paper, temperature-control devices, temperature-
sensitive elements and heat tapes from the cable after heating.
3.3.11. Add time of heating the cable to the checklist. (Cl.2. Appendix 1).
3.3.12. Straighten the cable and fix it on metallic angle (№31 Appendix 3) with belts or with
binding bands. The cable must be fixed till its insulation temperature reduced to environment
temperature.

Arkasil SK LLC 5
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
4. Cable preparation for MKB 252 B assembly.
4.1. Cable sheath removal.
4.1.1. Mark the cable at a length L+155mm (Figure 4) from the Figure 3 Position of
conductor cut (for cable without aluminum foil L+105mm (Figure bandages
5)) towards the cable. Add the information about semiconducting
layer to the checklist (i.7 Appendix 1)
4.1.2. Heat the sheath with «soft» fire using gas burner (№10
Appendix 4) at a 50mm length from the line of cutting the sheath
towards the cut of conductor. (for cable without aluminum foil
heat the cable around across the line of cutting the sheath).
4.1.3. Make a cross-sectional cut on the sheath with the rip cord
(included in the termination’s set) across the line of cutting the
sheath (In case of absence of aluminum foil go to i.4.1.11.)
4.1.4. Make a cross-sectional cut on the sheath with the rip cord
across the line 50mm from the line of cutting the sheath towards
the cut of the conductor.
4.1.5. Remove the sheath at a length of 50mm from the line of
cutting the sheath towards the cut of the conductor, excluding
damage of the aluminum foil.
4.2.6. Clean open section of the aluminum foil with knife blade or
steel brush (№26 Appendix 3). Aluminum foil must have metallic
shine after cleaning from polymer layer and glue layer.
4.2.7. Make a notch on the edge of the aluminum foil around the
cable with a cable stripping knife.
4.2.8. Fix the edge of the aluminum foil (which is nearer to the
joint side) with
Figure 4 Removing of sheath on armored tape 27 in 5 Figure 5 Removing of sheath on
cable with aluminum foil turns. cable without aluminum foil
4.1.9. Move the cable
from side to side.
Control cutting of the
aluminum foil across
the notch.
4.1.10. Heat the
sheath with
«soft» fire using gas
burner from the cut of the aluminum foil (from the cut of the sheath for cable without
aluminum foil) towards the cut of the conductor
4.1.11. Make a slit on the heating sector of the cable with a «plow» knife (№8 Appendix 3)
4.1.12. Remove the sheath from the cable using devises for stripping sheath (Flaps for sheath,
pliers, etc.) (№27 Appendix 3)
4.1.13. Treat the edge of the sheath with rasp (№23 Appendix 3)
4.1.14. Add the information about removing of the sheath L to the checklist (i.8 Appendix 1)

Arkasil SK LLC 6
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
4.1.15. Remove ribs, galling and pollution from the sheath with special tool (№9 Appendix 3) at
a distance 500 mm from the sheath cut towards the cable (Figure 3).
4.1.16. Remove semiconducting layer (if it presents) with instrument for removing
semiconducting layer (№9 Appendix 3) over the length 500mm from the line of cutting the
sheath towards the cable (Figure.3).
4.1.17. Sand the sheath with abrasive tape with abrasive grit 80 over the length 500mm from
the line of cutting the sheath towards cable.
4.1.18. Check resistance of insulation on this section after removing semiconducting layer. Put 6
electroconductive bandages on the sheath. Bandages must be laid equal through the whole
sanded length. Attachment points of the bandages must not be situated on the same line they
must be offset to each other (Figure 3).
4.1.19. Measure resistance between every pare of bandages using megohmmeter with a 2,5 kV
working voltage or higher (№16 Appendix 3). The resistance must be 330megaohms or more.
Remove bandages after checking.
4.1.20. Clean the sheath with abrasive paper grit 80 and 320 at a distance of 500 mm from the
sheath edge towards the cable.
4.1.21. Remove the creped tape by length from the conductor cut to the shield wires bending.
(to the cut of the sheath for cable without aluminum foil)
4.1.22. Wind 4 layers of copper gauze tape on the distance of cleaned foil and over the bandage
of armored tape. After winding do not cut the tape and fix it on the sheath (wind the copper
gauze tape on the sheath at a length of 50mm from the cut of the sheath towards the cable for
cable without aluminum foil).
4.1.23. Unbend screen’s wires and fix them with PVC tape on the sheath. Make bending over
the bandage of armored tape.
4.1.24. Remove crepe paper at a distance from the cut of the conductor towards the line of
bending shield wires.
4.2 Cable stripping and grinding.
4.2.1. Place a wood piece on the edge of the insulation and settle the insulation be 3-5mm,
hammering it out towards the cable using a hummer (№24 Appendix 3).
4.2.2. Measure cable diameter over semiconducting layer. Determine the amount of
semiconducting layer removal from the cable insulation ØА. (Diameter ØА of cable by prepared
insulation must comply with the size group of stress-cone of cable termination. Size group is
indicated on stress-cone)
4.2.3. Add the information about the diameter of the cable across the semiconducting layer to
the checklist (p.9 Appendix 1)
4.2.4. Take off first step of insulation to ØА using «MAS130» (№5 Appendix 3) or a similar tool
at a L-645mm distance from the conductor cut towards the sheath cut (The transition cone
between the insulation and semi-conducting layer must not exceed 6°) (Figure 6).

Arkasil SK LLC 7
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
Attention! Sharp edges at the boundary of insulation and semi- Figure .6 Insulation
conducting layer are impermissible. The boundary undulation preparation
must not exceed 5 mm. Correction must be done with glass
(included in the termination’s set).
4.2.5. Take off the second step of insulation with «MAS130» or a
similar tool at a L-960 mm distance from the conductor cut
towards the sheath cut as deep as to ØА - 3 mm (Figure.6).
4.2.6. Determinate dimension G (Table 3).
4.2.7. Remove the insulation and semi-conducting layer from the
conductor at a G+20 mm distance from the conductor cut
towards the cable (Figure 6).
4.2.8. Add the dimension of clean conductor G+20 to the checklist
(Cl.4. Annex 1).
4.2.9. Add the length of removing of semiconducting layer to the
checklist (i.10. Appendix 1).
4.2.10. Add the diameter of the insulation to the checklist (i.12.
Appendix 1).
4.2.11. Add the information about size-group of the stress-cone
to the checklist (i.11. Appendix 1).
4.2.12. Add the diameter of the second step of the insulation (ØА-
3) to the checklist (i.13. Appendix 1).
4.2.13. In case of using cable with segmented conductor, remove
insulating paper between segments.
4.2.14. Clean the conductor with abrasive paper grit 320.
4.2.15. Use «MAS130» or similar to make a 30° facet on the top
of the insulation (Figure 6).
4.2.16. Wind the conductor with reverse side of PVC tape.
4.2.17. Clean the insulation and transitions with abrasive paper
grit 180 and 320. The first step of insulation polish with abrasive
paper grit 400.
Table 3
Cross-section area, Cable conductor material Al Cable conductor material Cu
mm2 G mm. Pressuring G мм. Pressuring
Quantity P mm. Quantity P mm.
400 105 4 17 80 3 17
500 105 4 17 80 3 17
630 140 4 25 80 3 17
800 140 4 25 105 3 25
1000 170 5 25 105 3 25
1200 170 5 25 105 3 25
1600 105 4 17
2000 105 4 17
2500 105 4 17

Arkasil SK LLC 8
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5. Assembly of main components.
5.1. Cable preparations for stress-cone assembly.
Figure 7 - Tape winding 5.1.1. Mark the place of installing of stress-cone
at a distance of 100mm from the boundary of
semiconducting layer and insulation towards the
sheath cut. (Figure 7)
5.1.2. Wind semiconducting «tape 13» in 1 layer
starting from bending of screen’s wires to the
distance 5mm from the line of installing the
stress-cone towards the sheath cut. Make a cone
of «tape 13» in the place of bending screen wires.
5.1.3. Unfix copper gauze tape which was fixed
earlier (Cl.4.1.20). Wind it in for layers over
screen’s wires. Start winding from the bending of
screen’s wires towards the cable.
5.1.4. Fix copper gauze tape with spiral spring, at
a distance 15mm from the bending of screen’s
wires towards the cable. (Do not cut the rest of
copper gauze tape).
5.1.5. Continue winding of copper gauze tape
over semiconducting layer in one layer with 50%
overlapping. Start winding from bending of screen
wires to the distance of 30mm from the line of
*For cable without aluminum foil stress-cone installing towards the conductor cut
1 – Cable
(Figure 7). Do not cut the copper gauze tape and
2 – Semiconducting tape 13
fix it with PVC tape.
3 – Copper gauze tape
4 – heat-shrinkable tube 5.1.6. Mark the place of heat-shrinkable tube at a
5 – Spiral spring distance 30mm from the line of stress-cone
installing towards the sheath cut.
5.1.7. Measure the distance from the place of heat-shrinkable tube to the bending of screen’s
wires N (Figure 7). Cut the heat-shrinkable tube at a length of N.
5.1.8. Pull the heat-shrinkable tube on the cable and shrink it with «soft» fire using as burner.
The top edge of the tube should be on the mark of placing heat-shrinkable tube. Lower edge of
heat-shrinkable tube shrink to the dimension 20mm from the bending of screen’s wires. (Figure
7)
5.1.9. Use glass-fiber fabric to protect tapes and cable from heat impact. (included to the scope
of supply)

Arkasil SK LLC 9
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.2. Assembly of gasket and branch-pipe.
5.2.1. Measure the cable in sheath over bent screen’s wires.
Figure 8
5.2.2. Cut the conical part branch-pipe according to the measured Cut of branch-pipe
diameter. (Figure 8)
5.2.3. Remove sharp edges using a file (№21 Appendix 3).
5.2.4. Pull the heat-shrinkable tube and the branch-pipe on the
sheath of the cable. Pull carefully. Do not damage prepared
insulation.
5.2.5. Make a the control mark at a distance L-145mm from the
conductor trimming line toward the sheath trimming line.
5.2.6. Wind «tape 33» over the top edge of heat-shrinkable tube for simplifying of the sealing
installation. (Figure 9)
5.2.7. Wind «tape 33» on the conductor.
5.2.8. Wipe the gasket and the prepared cable with a dustless napkin (№4 Appendix 4) which is
soaked in isopropyl spirit.
Figure 9
Preparing for gasket installation

Figure 10 Sealing
lubrication

Arkasil SK LLC 10
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
Figure 11 Installation of the gasket and the baseplate

5.2.9. Grease the prepared cable with silicone grease from top of the insulation to control mark
(Figure 9).
5.2.10. Grease the inside surface of the gasket with silicone grease (Figure 10).
5.2.11. Install the gasket into the Рис.12 Монтаж патрубка
baseplate groove. Pull gasket with
baseplate on the shrink tube on the
cable to the distance 100mm from the
control mark to the top of baseplate
(Figure 11).
5.2.12. Remove the rest of the silicone.
Remove «tape 33» from the edge of
shrink tube.
Attention! Lubricate only external
threads with graphite lubricant during
installation of mating parts.
5.2.13. Fasten the baseplate to support
insulators with screws M16 with
1 – Gasket 7 – Metalware М10
100N*m (fix the support insulators on 2 – Branch pipe 8 – Flat washer
the metallic construction in case of 3 – Base plate 9 – Spiral washer
assembly «vertical» way with screws 4 – Earthing angle 10 – Tape 33
M20 with 150Nm. Use angle washers in 5 – Set screw М10 11 – Mastic tape
case there are any angles between 6 – Barrel set screw М10 12 – Support insulators
holes and nuts).
5.2.14. Screw fixing studs M10 into the base plate till stop. (orient the lengthened stud
«50mm» on the side of earthing angle connection) (Figure 12).
5.2.15. Fasten the branch pipe to the baseplate with M10 nuts and 30Nm force. Install the
earthing angle on the lengthen stud.

Arkasil SK LLC 11
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.3. Centering sleeve installation.
Figure 13 - Centering sleeve
5.3.1. Fix the insert on the centering sleeve with two screws
assembly
M5 (Lubricate the screws with thread fixing agent before
installation) (Figure 13).
5.3.2. Screw studs M10 into the baseplate.
Warning: using graphite or any other conductive grease
inside the composite insulator is strictly prohibited.
5.3.3. Install centering insert on the baseplate, and fix with
screws M10 and force 30N*m (Figure 15).

5.4. Stress cone fitting.


5.4.1. Prior to stress-cone installation make sure that it is
clean and has good casting quality. Check inner surface by
means of visual inspection under perfect illumination.
5.4.2. In case of detecting any dirt, clean the stress-cone and the insulation with a dustless
napkin which is watered in purified petrol or isopropyl spirit.
5.4.3. Unwind copper gauze tape (Cl.5.1.5.) to the edge of shrink tube.
5.4.4. Clean cable insulation with a dustless napkin watered in purified
petrol or isopropyl spirit. Direction of wiping is from insulation towards Figure 14 - Stress-
semiconducting layer. cone wiping
5.4.5. Wipe inner surface of the stress-cone with silicone grease, by using
clean rod with nonmetallic smooth surface without sharp corners, edges
and chips (Figure 14).
5.4.6. Wipe the insulation with silicone grease.
5.4. Place sliders for pulling between the stress-cone and the cable.
5.4.8. Pull the stress-cone to the line of the stress-cone installation
(Figure 15)
5.4.9. Remove sliders for pulling the stress-cone.
5.4.10. Remove extra silicone grease.
5.4.11. Remove PVC tape from the conductor of the cable and wipe the conductor with a
dustless napkin soaked in purified petrol (№3 Appendix 4).
Figure 15 Stress-cone installation.
1 – Stress-cone
2 – Centering insert
3 – Stud М10
4 – Nut М10
5 – Flat wash
6 – Spiral wash

Arkasil SK LLC 12
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.5. Tape winding and control.
5.5.1. Wind PVC tape in one layer at a distance 20mm from the top edge of the stress-cone.
Wait for about 20 minutes and control the dimension 20mm. In case of changing the
dimension, pull the stress-cone in previous place.
5.5.2. Wipe surfaces for winding with a Figure 16 Winding of tapes on the stress-cone
dustless napkin.
5.5.3. Wind «tape 13» (continuing
Cl.5.1.2.) with calling the stress-cone, at a
distance 35mm, towards the conductor of
the cable. Make a cone from tape for
smooth transition (Figure 16).
5.5.4. Wind copper gauze net (continuing
Cl.5.4.3.) with covering low part of the
stress-cone at a distance 25mm towards
the conductor (Figure 16).
5.5.5. Wind mastic tape at a distance
between stress-cone and shrink tube,
calling the shrink tube on 10mm and
calling the stress-cone on 45mm (Figure
16).
5.5.6. Wind 3 layers of «tape 33» starting
at a distance 50mm from the side of the
conductor. Stop winding over the earlier
winded tape 33 (see p.5.2.12) at the level
1- Tape 13 4- Tape 33
of the edge of the centering sleeve toward
2- Copper gauzed tape 5- Cable tie
the conductor. Fix the edge of «tape 33»
with a cable tie (Figure 16) 3- Mastic tape
5.5.7. Control the distance 20mm from the top of the stress-cone to the PVC control mark. In
case of changing the dimension, repeat from Cl.5.5.1.
5.5.8. Add the distance from the stress-cone to the control mark (20mm) to the checklist (Cl.14.
Appendix 1).

Arkasil SK LLC 13
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.6. Conductor connecting.
5.6.1. Check the connector for absence of Figure 17 Marking of the connector
any dirt and damage using bright light. In
case of absence of marking on the
connector, mark the connector according to
table 3 (Figure 17).
5.6.2. Pull the connector onto the conductor
until it stops and compress according to the
marking. Rotate the collar with matrix by
60° during each compression (Figure 17).
5.6.3. Wind the self-welded «tape 23» on
the rest of the conductor, for making smooth transition from the insulation to the connector.
5.6.4. Wind two layers of self-welded «tape 23», starting at a Figure 18
distance 50mm calling the insulation and not reaching 20mm the Connector assembly
edge of the compressed part of the connector (Figure 18).
5.6.4. Wind «tape 33» in two layers over «tape 23» calling the
insulation on 95mm, and stop on the edge of the compressed
part of the connector. Fix the edge of «tape 33» on the cable
with cable tie (Figure 18).
5.6.6. Measure the control dimension from the top of the
baseplate to the top of the connector (Figure 19).
5.6.7. Add the control dimension to the checklist (Cl.15. Annex 1)
Figure 19 - Control dimension

1 – Connector
2 – Self-welded tape 23
3 – Tape 33
4 – Cable tie

Arkasil SK LLC 14
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.7. Composite insulator installation.
Figure 20 - Composite insulator 5.7.1. Wipe all of the surfaces including the top of the
installation baseplate and inner surface of the external insulator with
a dustless napkin, soaked with purified petrol.
5.7.2. Lubricate an O-Ring with a silicone grease.
5.7.3. Install the O-Ring into the groove of the baseplate
(Figure 20).
5.7.4. Install the external insulator onto the baseplate
(Figure 20).
5.7.5. Fix the external insulator on the baseplate by M16
Allen screws, plane and spring washers. Tighten them up
to the 110 N*m torque in criss- Figure 21 –
cross pattern (Figure 20). Insulating
5.7.6. In case of oil plug, tighten it compound filling
up to the 160 N*m torque (Slightly
greasing it by silicon grease and
checking the perfectness of its O-Ring).

5.8. Insulating compound filling.


5.8.1. Insure that compound has no foreign inclusions.
5.8.2. Heat the compound to the temperature 120°С, than let it settle
down until the temperature drops to 80°С.
5.8.3. Compound must be heated with electric heaters, installed
outdoors, with constant control of the temperature (№51 Appendix 3).
5.8.4. In case of using open fire for heating the compound use a vessel
made of stainless steel with a constant control of temperature and
periodic mixing.
5.8.5. Fill the compound into the external insulator not reaching the end
face of upper flange by 350±30mm (Figure 21).

Arkasil SK LLC 15
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.9. Top cover installation.

Figure 22 – Top cover installation 5.9.1. Wipe the top flange of the insulator and
flange cap with a dustless napkin which is watered
in purified petrol.
5.9.2. Lubricate an O-Ring by silicone grease and
insert it into the groove on the top flange of the
insulator.
5.9.3. Lubricate O-Rings by silicone grease and
insert them into the flange cap (Figure 21).
5.9.4. Pull the flange cap onto the connector until
it stops.
5.9.5. Tighten the flange cap with M16 Allen
screws using spring washers up to the 110 N*m
torque (Figure 22).
5.9.6. In case of oil plug, tighten it up to the 160
1 – Top cover 4 – Spring washer N*m torque (Slightly greasing it by silicon grease
2 – O-Ring 5 – M16 Allen screw and checking the perfectness of its O-Ring).
3 – O-Ring 6 – Oil plug

5.10. Centering unit assembly. Figure 23 - Centering unit assembly


5.10.1. Wipe the surface of the glass and
O-Ring with dustless napkin soaked by
purified petrol.
5.10.2. Lubricate the O-Ring by silicon
grease and insert it into the groove
(Figure 23).
5.10.3. Fix the centering sleeve on the
top cover by M10 screws. Tightening
torque – 30 N*m.
5.10.4. Screw the bushing until it stops.
5.10.5. Fix semirings inside the groove of
the connector by M8 screws.
5.10.6. Unscrew the bushing until it stops
and make extra two turns.
5.10.7. Screw M5 screw into the bushing
for fixing. Use thread locking agent 1 – Centering sleeve 5 – Screw М5
2 – Bushing 6 – Allen screw М10х24
(Loctite® 222 or similar).
3 – Semiring 7 – Spring washer М8
4 – O-Ring 8 – Allen screw М8х10
9 – Spring washer

Arkasil SK LLC 16
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.11. Shielding of centering unit.
5.11.1. Wipe O-Ring with a dustless napkin soaked in Figure 24 - Shielding of centering
purified petrol. unit
5.11.2. Lubricate O-Ring by silicon grease. 1 – Shield
5.11.3. Insert O-Ring inside the groove on the top flange 2 – O-Ring
cover (Figure 24). 3 – Allen screw
5.11.4. Lubricate the connector end by silicon grease. М6х16
5.11.5. Pull the top cap onto the connector until it 4 – Spring
stops. washer
5.11.6. Fix the top cap by M6 screws and tighten them
up to the 7 N*m torque.

5.12. Screen wires soldering.


5.12.1. Install silicone profile on the conical part of the branch-pipe.
5.12.2. Fix screen wires over cable sheath by armored tape 27. Fixing position – 40 mm from
the branch pipe edge toward the cable.
Warning: Al screen wires are susceptible to fatigue failure. Al screen wires should be
bended/unbended as least as possible amount of times with extreme care.
5.12.3. Bend screen wires over the tape 27 winding.
5.12.4. Cut the screen wires overlapping the cylindrical part of the branch pipe for 30 mm.
5.12.5. In case of Al screen wires grind their 50 mm ends (at least) by sandpaper.
Figure 25 Soldering of screen’s wires to the 5.12.6. Clean and degrease screen wires by
branch-pipe dustless cloth soaked by purified petrol.
5.12.7. Fix the screen’s wires with a bandage
of tin plated copper wire d=1mm.
5.12.8. The part of cable which is lower than
place of soldering must be protected by a
glass tape.
5.12.9. In case of Al screen wires their
soldering zones should be coated by P200A
solder (Zn-Sn).
5.12.10. Solder the screen wires to the
branch pipe in near the copper bandage
using POS 30 solder. Solder in an «apple»
pattern.
5.12.11. Wipe the surface of cable and the
surface of the branch-pipe with a dustless
napkin which is watered in purified petrol.
5.12.12. Knock the screen wires in the place
of the bend with a rubber mallet (No. 25,
Appendix 3).
Attention! Repeated bending/unbending of the wires is not allowed - this may lead to wire
breaking.
5.12.13. Wind mastic tape on lower bending of screen wires.

Arkasil SK LLC 17
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
5.12.14. Wind «tape 33» in two layers on the place of soldering. Start winding on the branch-
pipe at a distance 20mm from the top edge of «apple» and stop on the cable at a distance
20mm from the bending of the screen’s wires.
5.12.15. Wind mastic tape on the cable sheath on place of heat-shrinkable tube.
5.12.16. Pull heat-shinkable tube onto the branch-pipe not reaching 15mm the lower surface of
the flange of the branch-pipe.
5.12.17. Shrink the tube with a «soft» fire of a gas burner.
5.12.18. Wait until heat-shrinkable tube cools down.

Arkasil SK LLC 18
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
Appendix 1
Checklist МКВ 252
Cable termination checklist
Customer Contract №
Project Termination type
Line name Phase
Site of assembly Insulator №
Cable type Stress-cone №
№ Description Cable Date
- Protective seals integrity (yes or no)
Before assembly
1. Temperature of heating of the cable, 0С 0С

2. Heating of the cable (time of start and finish)


3. Length of the insulator «L» , mm =
4. Stripping conductor from insulation «H», mm =
5. Environment temperature, 0С 0С

6. Cable cut L+110,mm =


7. Availability of semiconducting layer on the sheath (encircle) Yes No
Termination assembly
8. Removing of sheath L+155; (L+105)* mm =
9 D of cable over semiconducting layer, mm Min Max
10. Boundary of semiconducting layer from the conductor cut, mm =
11. Stress-cone size*, mm Min Max
12. Prepared ØА over the cable insulation, mm Min Max
13. D of the insulation over second step (ØА-3мм), mm Min Max
After pulling of stress-cone (control dimension)
14. Distance from top of stress-cone to control mark (20mm)*, mm =
15. Dimension L +315 (+10/-15 mm)
Start and finish of Start Finish
assembly
Additions, comments

Brigade members

Senior in the brigade


Surname Signature Date
Chief engineer
Surname Signature Date
*- Look through the instruction

After installation please sign and send back the original checklist to the address below for final approval:
«ARKASIL SK», LLC 111250,Moscow, Proesd zavoda Serp I Molot 6 bld1, Russian Federation
Tel. +7 495 933 57 23
Fax. +7 495 933 57 23

Arkasil SK LLC 19
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
Appendix 2
Interface dimensions

Arkasil SK LLC 20
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
Appendix 3
The list of required tools
Number Quantity Name
1 1 Tool for stretching
2 1 Chain tackle 1ton
3 2 Belt hand winch 1ton
4 2 Ring strap= 3m, loading to 3ton
5 1 Set of tools for cable cutting (Combination tool for cutting of MAS130 or similar)
6 1 Set for cable warming-up 1080 (heating tapes – 3, the device for temperature
control with the thermal sensor, the electronic thermometer – 3, a tee, a packing
box)
7 1 Band saw/saber saw/circular saw, a set with spare blades
8 1 Cable stripping knife
9 1 The tool for removal of ribs from a cable sheath
10 1 Set of a gas torch "Siever-Matic S" (the handle with a lighter, a reducer, a hose 5 m,
a crosspiece, 4 nozzles, a metal box)
11 1 Pliers
12 1 Side-cutting pliers
13 1 Pincers
14 1 Set of needle files
15 1 Beam trammel 0-150 with a depth finder GOST 166-80
16 1 Insulation measuring instrument
17 1 Flat blade screwdriver
18 1 Phillips screwdriver
19 2 Cable cutter
20 2 Zigzag folding rule
21 1 Half-round file H1, 300mm
22 1 Torque wrench 10-100 Н/м
23 1 Half-round rasp H2, 300mm
24 1 Hammer 0.4kg
25 1 Rubber mallet
26 1 Wire comb, steel brush
27 2 Hooks for laminated sheath
28 1 Sectoral cable cutter d=52mm
29 1 Removable highlighting
30 2 White marker
31 2 Aluminium L-bar 100х100х10 3 m
32 1 Gas propane cylinder 27-50l
33 1 Allen wrench 5 (Hex-nut wrench 7812-0374 GOST11737-93)
34 1 Allen wrench 6 (Hex-nut wrench 7812-0375 GOST11737-93)
35 1 Allen wrench 14 (Hex-nut wrench 7812-0379 GOST11737-93)
36 1 Hook wrench 16
37 1 Hook wrench 17
38 1 Hook wrench 18

Arkasil SK LLC 21
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019
39 1 Hook wrench 19
40 1 Hook wrench 24
41 1 Allen wrench kit up to 19 mm.
42 1 Set of hexagonal dies and punches for hydraulic press PO7000 (or for similar) cutting
from 400 to 2500 mm2
43 9 Ratchet strap (loading 500 kg, length 0,5 m)
44 1 Set of heads ( 16”;17”;18”;19”;24”)
45 1 String Ø5-6mm, length 20 m
46 1 Extender 25m
47 1 Ratchet wrench
48 3 Felt (thickness from 4 to 6 mm)(width 0,6 m, length 2,5 m)
49 6 Crepe paper 80mm х 10m
50 1 Capacity made of stainless steel

51 1 The thermometer for liquids 80°С-200°С

Appendix 4
The auxiliary (consumed) materials used for installation of one termination.
Number Quantity Name
1 0.5 liter Isopropyl spirit
2 1.5 liter Purified petrol
3 5 m2 Coarse calico
4 2g Thread fixing agent (Loctite® 222 or similar)

Arkasil SK LLC 22
www.arkasil.com
info@arkasil.com
Version: 1.00 Date: 24.12.2019

You might also like