TRANSFORMERS
A B C D E
1. CONSERVETOR
2. MEMBRANE
3. BREATHER
A CONSERVATOR TYPE WITH. SILICA GEL IN BREATHER. EXTERNAL AIR DRYED IN BREATHER.
• SUSCEPTABLE TO AIR BORNE CONTAMINATION, H2S ET
B CONSERVATOR TYPE WITH MEMBRANE SEAL IN CONSERVATOR. SEAL SEGREGATES EXTERNAL AIR FROM COOLING
LIQUID.
C HERMETICALLY SEALED, DRY GAS (OR AIR) ABOVE OIL TO ALLOW FOR LIQUID EXPANSION/CONTRACTION.
• USUALLY USED OFFSHORE, DEPENDANT ON SIZE.
• NO BREATHER, SEALED FOR LIFE.
E NON-CONSEVARTOR TANK WITH SILICA GEL BREATHER, NORMALLY ON SHORE AROUND 2MVA OR LESS.
• SAME POTENTIAL PROBLEM AS ‘A
TRANSFORMER PARAMETERS
• Voltage
• Rating
• Vector Group
• Impedance (Reactance)
• Losses
• In rush current
3a 3b 3c
2a 2b 2c
C
A B
VECTOR DIAGRAM
TRANSFORMER WINDING
INTERCONNECTION
Zy0 dy11
ALARM SWITCH
DEVICE OPERATED
LIQUID DIVERTED
DIELECTRIC LIQUIDS
BANNED SUBSTANCES
MATERIALS CONTAINING PCB’s, SUCH AS ASKERAL.
EVEN AFTER DRAINING AND REFILLING WITH A SUITABLE LIQUID, PCB’s ARE
STILL PRESENT DUE TO MIGRATION FROM INSULATION AND CORE
LAMINATIONS.
2) SILICON LIQUID
HIGH FLASH POINT , NON-BIODEGRADABLE.
THREE WINDING
TRANSFORMER
THYRISTOR
COMPRESSOR
RECTIFIER
12 PULSE
INVERTOR M GT
10MW
•DC COMPONENTS
•HIGH VOLTAGE SPIKES
•HARMONICS
THE SECONDARY WINDINGS ARE CONNECTED TO TWO THYRISTOR RECTIFIER BRIDGES CAUSING:
•HARMONICS
•INSULATION LEVEL TO WITHSTAND HIGH VOLTAGE “SPIKES” WITH FAST RISE TIMES
•THE CORE NEEDS TO BE ABLE TO WITHSTAND THE DC LEVELS AND HARMONIC CONTENT
WITHOUT OVER HEATING
CORE CORE
INTER-TURN INSULATION
INTER-LAYER
INSULATION
RECENT FAILURES
RECENTLY, THREE TRANSFORMERS HAVE FAILED AFTER ONLY AROUND TWO YEARS OPERATION. ALL THE
TRANSFORMERS WERE OF IDENTICAL DESIGN AND RATING. ALL THREE WERE FEEDING VSDS’s.
ALL THREE WERE OPERATING UNDER NORMAL OPERATING CONDITIONS.
ALL THREE FAILED WITH A SHORT CIRCUIT IN THE SECONDARY WINDINGS.
ALL THREE HAD FOIL WOUND SECONDARIES
AFTER ONE TRANSFORMER HAD BEEN STRIPPED DOWN AND INSPECTED AT THE MANUFACTURERS, THE
FOLLOWING WAS FOUND:
•A CONDUCTIVE COATING WAS FOUND ON THE INTER-TURN INSULATION
•A WHITE DEPOSIT WAS FOUND ON INTER-WINDING INSULATION BLOCKS
•A SEVERELY BURNED HOLE WAS FOUND IN THE INNERMOST SECTION OF THE
SECONDARY WINDINGS
CORE
A SECTION THROUGH THE WINDINGS SHOWING
DAMAGED AREA
DAMAGE LV HV
2
PRIMARY WDG.
CONDUCTIVE
COATING
NOTE OVERHEATING
CORE
SECONDARY INNER
SECTION
ALTHOUGH A FULL REPORT HAS NOT BEEN COMPLETED BY AN INDEPENDENT PARTY, THE FOLLOWING
HAS BEEN RECOMMENDED: