You are on page 1of 1

A B C D E F G H I J K L M N O P

0 TABLERO TAC-04 0
(TABLERO AREAS COMUNES 2 ) AC 2x16A
2x16A K1.TLF-T2
C1 30mA 1x4mm2 LSOH-80 + 1x4mm2 LSOH-80(N) + 1x4mm2/T - TUB. 20mmØ PVC SAP
TAB.EMPOTRADO 20A ALUMBRADO 1 NIVEL
AC-1
380/220V, 3Ø + N 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
C1a
LUCES DE EMERGENCIA
P.I. = 1.97 kW AC 2x16A
2x16A K2.TLF-T2
M.D. = 1.57 kW C2 30mA 1x4mm2 LSOH-80 + 1x4mm2 LSOH-80(N) + 1x4mm2/T - TUB. 20mmØ PVC SAP
20A ALUMBRADO 1 NIVEL
AC-1
C2a 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
1 LUCES DE EMERGENCIA 1
AC 2x16A
2x16A K3.TLF-T2
C3 30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
BARRA ALUMBRADO 2 NIVEL ESTACIONAMIENTO
20A
NEUTRO AC-1
C3a 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
LUCES DE EMERGENCIA
3x2A AC 2x16A
2x16A K3.TLF-T2
C4 30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
RST ALUMBRADO 2 NIVEL ESATACIONAMIENTO
20A
VIENE CIRCUITO C8 DEL TABLERO GENERAL AC-1
3x40A C4a 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
2 3-1x10mm2 N2XOH + 1x10mm2 N2XOH(N) + 1x10mm2/T LUCES DE EMERGENCIA 2
AC 2x16A
2x16A K3.TLF-T2
TUB. 40mmØ P.V.C PESADO. C5 30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
20A ALUMBRADO 2 NIVEL ESATACIONAMIENTO
AC-1
C5a 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
AC 2x16A LUCES DE EMERGENCIA
2x16A K3.TLF-T2
C6

380V, 10kA, 60HZ (60A, 20x3mm)


30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP ALUMBRADO 2 NIVEL ESATACIONAMIENTO

C5a 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
LUCES DE EMERGENCIA
3 3
AC 2x20A
C7 2x20A K3.TLF-T2
30mA 1x4mm2 LSOH-80 + 1x4mm2 LSOH-80(N) + 1x4mm2/T - TUB. 20mmØ PVC SAP
ALUMBRADO REFLECTORES CALLE JUNIN

AC 2x16A
C8 2x16A K3.TLF-T2
30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2.5mm2/T - TUB. 20mmØ PVC SAP
ALUMBRADO RAMPA VEHICULAR

AC 2x20A
C9 2x20A
4 30mA 1x4mm2 LSOH-80 + 1x4mm2 LSOH-80(N) + 1x4mm2/T - TUB. 20mmØ PVC SAP 4
CIRCUITO DE FUERZA SILLA DISCAPACITADO

AC 2x20A
C10 2x20A
30mA 1x4mm2 LSOH-80 + 1x4mm2 LSOH-80(N) + 1x4mm2/T - TUB. 20mmØ PVC SAP
CIRCUITO DE FUERZA CONTROL DE ACCESO A RAMPA
C5a 1x4mm2 LSOH-80 + 1x4mm2 LSOH-80(N) + 1x4mm2/T - TUB. 20mmØ PVC SAP
CIRCUITO DE FUERZA PUERTA ENRROLLABLE
AC 2x16A
C11 2x16A
30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2.5mm2/T - TUB. 20mmØ PVC SAP
ALUMBRADO ESCALERAS
5 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP 5
C5a
LUCES DE EMERGENCIA

AC 2x16A
C12 2x16A
30mA 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2.5mm2/T - TUB. 20mmØ PVC SAP
CIRCUITO DE FUERZA DE INTRUICION
C5a 1x2.5mm2 LSOH-80 + 1x2.5mm2 LSOH-80(N) + 1x2,5mm2/T - TUB. 20mmØ PVC SAP
AC 2x16A CIRCUITO DE FUERZA DE CAMARAS
C13 2x16A
30mA
ILUMINACION SUBESTACION
6 6
AC 2x16A
2x16A
C14 30mA
RESERVA

C15 2x16A
30mA
RESERVA
TIERRA

7 7

DIAGRAMA
8
UNIFILAR
INT. PRINCIPAL : CAJA MOLDEADA, 16kA
8

INT. DERIVADOS : PODER RUPTURA 10kA

PROCEDIMIENTO DE APROBACION
IMPORTANTE : TIPO Y DIMENSIONES TABLERO GRUPO ARAUJO

CCPB
(H x A x P) ADOSADO
800 x 600 x 200 RESPONSABLE FIRMA FECHA
"LA FABRICACION DE LOS TABLEROS Y/O PROYECTO :
CENTRO COMERCIAL PLAZA BOLOGNESI II
CELDAS SE REALIZAN CON LOS PLANOS GRADO HERMTC. IP55 DISEÑO D.CONTRERAS 17/08/20
ETAPA
APROBADOS POR EL CLIENTE. TODO GASTO
9 CANTIDAD: 01 DIBUJO 17/08/20
TITULO : N° DE PLANO 9
GENERADO DEBIDO A UNA MODIFICACION TABLERO TLF-T2
POSTERIOR A LA APROBACION DE LOS PLANOS ACABADO: RAL 7032 REVISO 17/08/20 Planta :
380/220-3F+N+T-60Hz 02-IIEE
SERAN ASUMIDOS POR EL CLIENTE". A 17/07/18 EMITIDO PARA MATERIAL: METALICO APROBO J.FORONDA 17/08/20
Telef. :
NOTAS Nº REV. FECHA
APROBACION REVISIONES VENDEDOR -- -- --
ESCALA: S/E Nº SOLIC: 001 Nº PROF: 1956 N° ORDEN: -- HOJA: 1/--
A B C D E F G H I J K L M N O P