The switch by itself is combined of two parts. The lever directly manipulates metal hook, that pulls on the black plastic part, which
in turn moves the actual contact. This is done so that if there is a short circuit (or overcurrent), the breaker trips even if you're holding the
lever up (so no, you can't tape the breaker in the ON position :-)).
The breaker can be operated by several means. Besides manually, it can be turned off by another breaker (only in three-phase
breakers). You might expect this is one due to the switches being joined together (often with a metal shaft), but this is not the case, as it
might not be that reliable.
There is small shaft linking the breakers, going into the black plastic part, into the circular hole. In case one switch goes down, this
shaft immediately pulls down the others. The force required to do this is much lower than on the manual lever, but I guess the main
reason is that it can't be influenced by the human holding the lever in the ON position (in case you're switching on the breaker and one
of the phase has short-circuit, all of them go down).
Short-circuit
There is a coil, which when short-circuit current flows through it, pulls out a metallic core outside, and turns off the switch. This is
the quick action for a huge currents, when you don't want to wait for the overcurrent protection to kick in.
Over-current
A bimetal strip heats up as the current rises, and it bends, eventually pulling the metal rod, joining the strip and, again, the black
part of the switch. This is the slow action, and required too large current to be present for some time before breaking the circuit. The
sensitivity can be adjusted by a small screw, that is pretensions the bimetal strip (although this is not always present in cheap household
breakers).
Arc suppressor
The last functional piece is the arc suppressor. An electric arc is formed when the switch is turned on or off, and needs to be
extinguished to limit the damage to the switch contacts. As the arc forms, it travels down to the grill-looking part, and eventually fades
along the way, when the AC passes through zero. Some higher voltage breakers would enclose the switch mechanism in a vacuum or
inert gas, but not the regular distribution grid ones.
I don't think either of these problems occurred in my breaker, although the temperature might have been a factor here. It seems
that in mine, only the spring that tensions the black part of the switch, to be able to join with the manual lever, is worn out. If I tension it
manually, the switch works just fine. Neither me, the electrician who replaced the breaker, of anyone else whom I asked never heard of
this kind of failure.