Professional Documents
Culture Documents
Pdvsa: Risk Engineering Manual
Pdvsa: Risk Engineering Manual
PDVSA N° TITULO
0 MAY.93 APPROVED 33 J. R. L. H. C. C.
APROB. Héctor Goodfellow FECHA FEB.01 APROB. Jesús Dávila FECHA FEB.01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 1
Menú Principal Indice manual Indice norma
Index
1 SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.1 PDVSA Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.2 International Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4 DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5 CLASSIFICATION OF PLATFORMS . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6 BASIC DESIGN CONCEPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6.1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6.2 Geographical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6.3 Inherent Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6.4 Equipment Layout Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6.5 Considerations About Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6.6 Fire and Explosion Protection Considerations . . . . . . . . . . . . . . . . . . . . . . . 9
7 GENERAL DESIGN CRITERIA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.1 Equipment Location and Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.2 Automatic Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.3 Fire Protection Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.4 Safety Instrumented Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.5 Vents, Flare and Depressuring Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.6 Classification of Hazardous Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.7 Drainage System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.8 Survival System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.9 Control Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 2
Menú Principal Indice manual Indice norma
1 SCOPE
This document contains the basic criteria applicable to the design of installations
located offshore. Existing standards were adapted and modified for the
development of this document, and new considerations based on past experience
of the petroleum industry were also included.
This document is based in the application of the most recent techniques and
design practices for offshore installations, as well as national and international
petroleum industry experience. The requirements established by laws,
regulations, decrees, or official standards in force, shall prevail over the criteria
set forth here, except when this document indicates a more stringent criteria. The
application of the criteria defined in this document is recommended for the design
of new offshore installations, and for changes and modifications to the existing
installations, as well as for those existing installations with a level of risk
incompatible with the corporate policies and objectives established by PDVSA.
2 APPLICATIONS
The present criteria have general application to fixed offshore installations that
process, handle or store flammable, combustible, and/or toxic substances.
Onshore installations are excluded from this standard.
3 REFERENCES
3.1 PDVSA Standards
HE–251–PRT Sistemas de Drenaje
IR–C–03 Revestimiento Contra Incendio
IR–E–01 Clasificación de Areas
IR–I–01 Sistema de Detección y Alarma de Incendio
IR–I–02 Sistemas de Detección de gases Inflamables / Tóxicos
IR–M–03 Sistema de Agua Contra Incendio
IR–M–04 Sistema de Espuma Contra Incendio
IR–M–05 Sistemas Especiales de Extinción y Alarma de Incendio
IR–P–01 Sistemas de Parada de Emergencia, Bloqueo, Despresurización
y Venteo de Equipos y Plantas
IR–S–01 Filosofía de Diseño Seguro
IR–S–02 Criterios para el Análisis Cuantitativo de Riesgos
K–331 Instrument Power Supplies
K–336 Safety Instrumented Systems
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 3
Menú Principal Indice manual Indice norma
4 DEFINITIONS
ABANDONMENT: Process of emergency escape from the installation when one
or all of the evacuation means have failed. The onboard personnel shall have
available several access routes to get to the water, including jumping.
EVACUATION: Planned method to abandon the installation without direct entry
to the sea but to transport means that will take the personnel onshore or to a
nearby but safe installation.
PRIMARY MEANS OF ESCAPE: Fixed vertical ladders and ladders with hand
railing of metallic construction.
SECONDARY MEANS OF ESCAPE: Fixed vertical ladders and ladders with
hand railing of metallic construction or flexible portable ladders, ropes or other
satisfactory means.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 4
Menú Principal Indice manual Indice norma
5 CLASSIFICATION OF PLATFORMS
CLASS 1: Platform for control and administrative uses and where there are
no facilities for handling and storage of hydrocarbon products.
The existence of a diesel tank for daily use, if its capacity does not
exceed 3780 liters (1000 gallons), should be allowed in this class
of platform.
CLASS 2: Platforms with facilities for handling, processing and storage of
hydrocarbon products, such as platforms that process or store
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 5
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 6
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 7
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 8
Menú Principal Indice manual Indice norma
6.4.3 Living quarters, control room and critical safety equipment shall be located in
non–hazardous areas (see 7.6 Classificatios of Hazardous Areas).
6.4.4 Risers shall be located and designed so that the consequences of accidental
releases can be minimal. External riser inlet areas shall be protected from fires
and explosions in the platform.
6.4.5 Flares or cold vents shall be located and designed so that the release of gas (flare
can be extinguished) or radiation levels does not increase the risk.
6.4.6 The piping in all areas shall be planned to minimize directional changes,
corrosion, erosion, and at the same time shall provide easy access and egress
from all functional parts on each equipment.
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 9
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 10
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 11
Menú Principal Indice manual Indice norma
ensure that they have adequate ventilation. Also, the equipment must be
distributed to take advantage of the prevailing winds minimizing the possibility that
hydrocarbon releases be transported towards ignition sources. Special care
should be taken when protective barriers are used, which shall be located such
that an optimum ventilation is guaranteed. Special considerations must be taken
for the ventilation of wellheads areas which should be as open as possible with
at least two open sides. The inside of the living quarters should have adequate
extraction systems to prevent accumulation of smoke and odors. For some typical
cases, criteria is presented to provide guidance in the design of similar
installations. These cases are shown in the following subsections.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 12
Menú Principal Indice manual Indice norma
S Pig traps
S Vessels for
water treatment
S Small petroleum
tanks (<<<100
barrels)
Auxiliary Equipment that may be located in common areas
S Lifting S Choke manifold S Pig traps S Product S Pig trap S Lifting equipment S Emergency
equipment collection generators
S Header S Gas equipment/ S Navigation S Navigation aids
S Fire fighting distribution vessels aids S Navigation aids
equipment S Lifting stations S Emergency
equipment S Fire fighting S Fire fighting generators S Living quarters
S Navigation aids S Water equipment
S Fire fighting treatment
equipment
S Fire water pumps
equipment vessels S Lifting
S Navigation aids S Lifting
equipment
equipment
S Air compressors
S Fire fighting
equipment
S Process
pumps
S Navigation
aids
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 13
Menú Principal Indice manual Indice norma
The piers and boats, ships, vessels, embarcation areas must be located in the
side of the structure that is against the wind. Cranes may be located on the
embarcation area for safe loading and unloading of equipment. Areas for the
storage of piping and voluminous materials should be located within the area
covered by the loading arm.
The living quarters shall be protected against external fires, explosions and noise.
The ventilation systems shall be designed to maintain fresh and breathable air
and prevent ingress of flammable/toxic vapors due to an external event and vent
smoke in case of a fire within the living quarters. The escape routes shall be
rapidly accessible from the living quarters through one of the primary means of
escape. The escape routes shall be designed to minimize the heat exposure
potential and the fire sources. Living quarters are ignition sources and they shall
be isolated from fuel sources by a reasonable distance. The windows and other
openings shall be eliminated from the sides facing the adjacent production
platform.
The living quarters shall be designed and protected to ensure that the functions
for which they are designed (including safe haven) can be maintained during a
release or fire situation. They shall be equipped with reliable smoke detection and
alarm systems.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 14
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 15
Menú Principal Indice manual Indice norma
S ESD valves shall be located in open naturally ventilated areas as close to the
sea as practical. Electric cables, pneumatic tubings and hydraulic systems
associates with this ESD valves shall be protected from explosions and fire
(fire–proofed) for a period of time sufficient to perform the shut down sequence.
7.1.8 Process Areas Without Flame or Heat Generating Equipment
The process equipment located in this area can have potential fuel sources and
should be separated or protected from the ignition sources. Process equipment
without flame or heat should not be located above or below equipment with flame
or heat without special protection.
The process vessels without flame/heat may be located closer to the wellheads
than any other equipment since the areas for both are potential fuel sources and
shall not contain ignition sources. The normal flow pattern is frequently from the
wellheads towards the process vessels without flame/heat, thus both areas shall
be located as close as possible in order to simplify the piping interconnections.
7.1.9 Hydrocarbon Storage Tanks Area
The hydrocarbon storage tanks may be potential hazards due to the liquid fuel that
they contain and the associated venting of gases. The storage tanks should be
distant or protected from the wellheads and potential ignition sources such as
vessels with flame/heat, machinery and living quarters. The petroleum storage
tanks should be located in the vicinity of the process equipment without
flame/heat, as both types of equipment represent potential fuel sources without
being potential ignition sources.
Precautions must be taken to prevent spills of liquids that may flow inside other
production equipment areas.
7.1.10 Process Areas With Flame or Heat Generating Equipment
The equipment located in process areas which generate flame/heat should be
considered as potential ignition sources, since some fuel sources will necessarily
be present. The process vessels which generate flame/heat should be distant or
protected from the wellheads, from vessels that do not generate flame/heat and
from petroleum storage tanks. If the vessels that generated flame/heat are
located in the same structure with other equipment and process vessels, the
potential ignition hazard should be minimized taking into account the precautions
addressed elsewhere in this document.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 16
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 17
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 18
Menú Principal Indice manual Indice norma
S Faults of the detection system shall result in a failure alarm at a control room.
7.2.1 Gas Detection and Alarm Initiation
The number, location and type of gas detectors shall be determined using the
guidelines set forth in this section, and also by taking into account the following
factors:
S Potential leaks within area.
S Borders between non–hazardous and hazardous areas.
S Gas density relative to air (light or heavy gas).
S Detection principles and voting logic.
S Ventilation air flow patterns.
S Prevailing wind directions and wind speeds.
S Size of the area.
S Criticality of the area.
a. Applications
Typical guidelines for location of gas detectors in the platform are given in Table
2. In addition, and based on the platform classification established in Section 5 of
this document and depending on whether or not personnel is present permanently
in the installation, the use of gas detection systems by platform type is
recommended as follows:
1. Manned Platforms
Platform Class 1: They shall be installed in the fresh air intakes of the
pressurization and conditioning system associated with the different
environments of this platform. At least two gas detectors are recommended
per fresh air intake.
Platform Class 2: It is necessary the installation of gas detection systems
in these areas due to the possibility of accumulation of gases or flammable
vapors as this classification includes the process areas of the platform.
Platform Class 3: Gas detectors shall be installed if these platforms have
electrical distribution systems (MCC, transformers, rectifiers, etc.) or diesel
motors for the fire fighting system.
Platform Class 4: The use of gas detectors in this platform is not
recommended because the open spaces and low capacity vessels make
gas or vapor accumulation improbable.
2. Unmanned Platforms
The installation of gas detectors in platforms Class 1, 2 and 3 is
recommended and the alarms that this system generates shall be
transmitted to the supervisory center for the installation.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 19
Menú Principal Indice manual Indice norma
b. Operational Philosophy
The interaction of the control module with systems such as (1) emergency
shutdown system, and (2) fire extinguishing system, shall depend on the
occupancy regime (routine, frequent, scheduled) in the installation. The following
criteria are recommended:
1. Manned Platforms
It is recommended that the interaction philosophy include the following
actions:
– Activation of the alarms in the control module
– Automatic activation of the emergency shutdown system for combustion
equipment (furnaces, gas generators, boilers, etc.) and fire extinguishing
system.
– Automatic activation of the emergency shutdown system for the entire
installation, fire extinguishing system, and alarms.
The designer shall select the most practical option for the installation, in
terms of the results of the risk analysis and the basic objectives of the
detection systems, which are listed below in order of importance:
– Personnel safety.
– Physical integrity and continuity of operations at the installation.
– Minimize the probability of contact between ignition sources and flammable
mixtures.
Additionally, it is recommended to establish a set point for the interaction of
the detection system with the systems mentioned above at a value of 20%
and 40% of the lower flammability limit of the substance under consideration
for alarm and for shutdown of equipment, respectively. (Refer to IR–I–01).
2. Unmanned Platforms
The gas detection system should activate the emergency shutdown system
and the fire extinguishing system in this type of platform. Additionally, a
mechanism shall be established in the system for sending or transmitting the
alarm signal (identification of the situation) to the control center.
c. Cabling and Routing
The cabling of the gas detection systems and alarms, for the electrical supply as
well as for signal transmission, should be made by means of cable conduits or
trays of the protection systems.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 20
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 21
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 22
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 23
Menú Principal Indice manual Indice norma
The installation of a barrier wall or a fire wall must be considered when the
designer judges there is not adequate spacing. However, barrier walls or fire walls
may prevent adequate ventilation in the area or hamper escape, and shall only
be used when it is impossible to provide adequate separation. Fire walls that may
reduce the consequence of fires and explosions, may indeed increase the
chances of an explosion due to increased confinement leading to accumulation
of gas. Typical uses of fire or barrier walls is to separate living quarters from
external fires, or to protect any section of the escape routes for a specified time,
or to separate process areas from storage tanks or wellheads from process areas.
The outer walls of the living quarters or fire walls shall be design to support the
heat flux determined by fire load calculation.
Passive fire protection shall not be the only means of fire protection because it is
normally effective only for a limited period of time, after which the protected area
is vulnerable to fire damage. The best fire protection for a platform is achieved
by a combination of passive and active fire mitigation systems.
7.3.3 Active Fire Protection
Active fire protection solutions require devices to monitor a process variable and
function to mitigate a hazard. Active fire protection is recommended on all
platforms with process equipment.
Examples of active fire mitigation systems are:
S water
S water with foaming additives
S chemical extinguishing
S combination of water, foam and chemical fire mitigation systems
S inert gas extinguishing agents for enclosed spaces.
Some fires may be controlled and extinguished effectively by isolating the fuel
source and thus preventing the fire propagation. The fuel sources may be isolated
by closure of an automatic or manual valve, by check valves, or with relief and/or
depressuring systems.
The active fire control systems in offshore platforms may use water, chemicals or
a combination of both. Many considerations influence the design of fire prevention
and control systems so the desired protection level is provided. These include the
size and complexity of the platform, the nature of the operation, the quantity and
experience of the operators to use the fire fighting equipment, the protected area,
the availability of additional fire fighting equipment not located in the platform, and
the consequences that could result from a major fire. However, an adequate
design of a fire control and extinguishing system will not comply with the overall
fire control objective if the personnel is not adequately trained and/or the fire
fighting equipment is not maintained in operable conditions.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 24
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 25
Menú Principal Indice manual Indice norma
necessary. The fire water piping network shall have fixed monitors installed in the
interconnection bridges between platforms, as well as around the platforms
containing flammable substances, and allow the isolation from adjacent
platforms.
The distribution network shall be kept pressurized and shall consist of a network
with a main loop and corresponding branches towards the different installations.
In cases where this is not possible, a single pipe may be installed as long as the
supply of water by independent sides is guaranteed.
Special attention must be place in the location of the fire water main and the supply
of water to a module to ensure that accidents or fires cannot damage it. For
example, the fire main should not be located in the same pipe rack as hydrocarbon
piping.
c. Pumping System.
The capacity, type, pressure requirements, components and start and stop
system for the fire water pumping systems in offshore installations shall be sized,
conceived and designed according to PDVSA standard IR–M–03 “Sistema de
Agua Contra Incendio”.
In any case, the pumping system shall be installed preferable in a platform Class
1 or 3. In those cases where this is not possible, the installation of systems that
will guarantee the integrity of the pumps in case of fire shall be required, such as
fire walls to protect the pumps, water curtains, etc.
Redundant and independent pump systems shall be provided for large integrated
installations to provide full protection if a unit is unavailable due to maintenance
or break down. Each system is to have 100% capacity for the largest fire water
demand. Each pump system should have two pump units of 50% capacity each.
d. Application Rate
The space limitations for the placement of equipment in offshore installation force
a decrease in the spacing between equipment, which results in more complex and
congested installations. This complexity and congestion of equipment facilitates
the propagation of fires between equipment. This consequence may be
minimized with the installation of pulverized water systems with discharge
densities in the range of 0,2 to 0,5 gpm x ft2.
Consequently, the determination of the discharge density for a specific installation
must be based on an evaluation of the complexity and degree of congestion of the
facility.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 26
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 27
Menú Principal Indice manual Indice norma
Blast relief and ventilation panels may be considered for controlling small
overpressure levels as they can provide adequate venting to allow unburnt gas
and combustion products out of a confinement before dangerously high
pressures develop. These measures are not effective for major overpressure
levels.
Blast barriers or walls may be considered to minimize the consequences of an
explosion, but generally, the avoidance of congestion and confinement in the
layout is the preferred option.
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 28
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 29
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 30
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 31
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 32
Menú Principal Indice manual Indice norma
Vents shall be designed and located to prevent accidental liquid carryover from
falling on hot surfaces or vulnerable areas.
The atmospheric vent final outlet pipe shall discharge outside the perimeter of the
platform to prevent accumulation of gases. The prevailing wind direction shall
move the vented gas away from the platform.
Atmospheric venting is usually used when excessive backpressure in the flare
system does not allow for routing to flare.
Venting systems for atmospheric and pressurized gas disposal shall be separated
as atmospheric tanks are susceptible to damage from very low backpressures.
Gas disposal systems shall not contain any low points where liquids could
accumulate and block the relief passages. In addition, the auto–refrigeration
effect of high pressure gas venting needs to be considered to assess the
possibility of hydrate formation in the system.
7.5.2 Flare Systems
The flare system is a system for discharging and incinerating during normal or
abnormal conditions the gas coming from a pressurized system through a control
valve. This discharge may be continuous or intermittent. The flare system shall
include the control valve, the collection piping, the gas–liquid separator and the
gas venting. Normally, the gases discharged inside the flare system are at a low
pressure and low flow rate.
The backpressures required are not defined in all codes and operation guides,
however, the flare system shall be designed ensuring that the vessels and/or
tanks will not be overpressurized and with capacity for the maximum volume that
may be vented.
Flare systems shall be designed to prevent liquid carryover. The location of the
flare shall minimize the possibility that accidental liquid carryover will fall on the
platform or on boats or barges.
Flare radiation calculations for critical flaring conditions shall be provided early on
in the design to estimate the radiation load on all areas of the platform. This
calculations shall also account for varying wind conditions and flaring rates. A gas
dispersion calculation shall also be performed for the case when the flame is
extinguished to ensure design provides for safe dispersion of gases.
The radiation levels in open areas of the platform where personnel may be present
or where structures and equipment are exposed must comply with PDVSA
permissible limits or international codes such as API RP 521. The following
guidelines shall apply:
S Heat loads on steel or aluminum structures shall not give temperatures that
results in loss of structural integrity.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 33
Menú Principal Indice manual Indice norma
S Heat loads on wires in drill tower and cranes shall be limited depending on type
of lubrication and inspection /replacement frequency.
S Flare radiation shall not cause in hazardous areas temperatures above 200 _C
or above the ignition temperature of the actual gas, whichever is the lowest.
S Heat loads on rated electrical equipment and instrumentation shall not give
temperatures exceeding 40 _C.
S In helidecks, the maximum radiation allowed to perform the necessary
helicopter operations is 1.9 kW/m2.
Local radiation shields may be provided as a last resource to protect personnel,
equipment and structures when radiation levels are deemed excessive, but
always taking into consideration that extra confinement and congestion may
increase the chances of an explosion in case of a gas release.
Depressuring systems reduce the release rate from failures in liquid filled parts
of the system by decreasing the system pressure and also reduce the duration
of jet fires.
Depressuring systems may also be required for systems unable to contain the
hazardous substances by passive means alone. The loss of active containment
mechanisms will require depressurization to prevent escape of the substances
such as in the case of loss of the seal oil in a centrifugal compressor.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 34
Menú Principal Indice manual Indice norma
A risk analysis taking into account the location of the equipment, the risk of it being
exposed to fire, the consequence of the rupture and any active or passive fire
protection available, should be performed in order to justify not providing a
depressuring system when required based on maximum containment during shut
down. Also, the benefits of depressuring systems need to be weighted against
the discharge of large volumes of gas in a short period of time during an
emergency condition, which may result in unacceptable high levels of radiation
or flammable or toxic gas. A sequence blowdown may be considered to limit peak
flowrates in vent or flare system. In this case, a failure of the timer should be
considered in the design of the depressuring system to ensure its adequacy.
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 35
Menú Principal Indice manual Indice norma
S The living quarters shall not be electrically classified, since the air intakes for
the pressurization or ventilation system come from a non–classified location.
S The helidecks and embarcation areas shall be located in non–classified areas.
The diesel (and gas) engines shall be located in non–hazardous areas since they
may provide a source of ignition for flammable gas releases and also may create
an overspeeding hazard through ingestion of flammable gas. Diesel engines for
essential safety systems should be provided with protection such that the diesel
engine can continue to operate even if gas is present in area during an
emergency. These protections may include isolation of electrical components,
overspeed protection and/or cooling of hot surfaces.
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 36
Menú Principal Indice manual Indice norma
The piping bends and flow restrictions shall be minimized in a gravity system. The
piping shall be installed with a negative gradient in the order of 1/8 inches per foot.
In some cases it may be necessary to install the piping in a horizontal manner, but
never with a positive slope.
Cleaning and purge connection shall also be provided in the drainage system.
Since liquid hydrocarbons may contain hydrocarbon gases, the gravity drain
systems shall include liquid seals to prevent gas from the sump from migrating into
the drain system. Buildings or enclosures shall not be located on top of drain
openings as gas may migrate throughout the drain piping into these spaces.
Similarly, the drainage system shall be designed to prevent burning fuel from
migrating to other areas. Special attention shall be given to minimizing the
probability of burning fuel spreading to the sea level where it can adversely affect
the integrity of the platform support structure and hinder evacuation.
Hazardous and non–hazardous open drains shall be separate with no
interconnections. The design of the drainage system shall limit the maximum
horizontal spread of the spill
In many instances, the release of liquid hydrocarbons may be associated to a fire
situation. In light of this, the capacity of the drainage system should be sufficient
to handle credible spills simultaneously with deluge system or fire fighting
activities.
The drainage system on the helideck should be designed for quick removal of
aviation fuel spills from the vicinity of the aircraft and without impairing escape
routes.
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 37
Menú Principal Indice manual Indice norma
Copy of these plans must be located in sites visible and accessible to all
personnel.
All platforms shall be provided with sufficient means of escape so the personnel
can escape or exit in a safe manner in case of fire or other emergencies.
The means of escape shall be located and arranged to facilitate the access by all
personnel. When there is more than one primary means of escape in the
platforms, at least two of them shall be located in opposite sides, arranged and
constructed to minimize the possibility that both can be blocked in case of fire or
emergency. When only one primary means of escape, and one or more
secondary means, at least one of the secondary means shall be located at the
opposite side and distant from the primary means of escape. Similarly, they must
be arranged and constructed to minimize the possibility that both can be blocked
in case of fire or other emergency condition.
All the platforms shall be provided with sufficient walkways so all personnel can
escape from the fire area or from the emergency condition and go to the means
of escape.
The walkways shall be distributed and maintained to provide adequate clearance
and be accessible to the platform personnel, and they shall be constructed and
distributed to allow escape in two different directions.
7.8.1 Alarm Systems
An alarm system, as well as a public address and communication system shall be
provided for all manned platforms to quickly warn and direct personnel during an
emergency situation.
In every manned offshore platform, audible alarms shall be installed in all areas.
The alarm shall be capable of sounding intermittently to indicate an emergency
situation and continuously to indicate a situation that requires platform
abandonment. In areas of high noise, a visual alarm signal shall also be provided.
In embarcations areas as well as helidecks a visual alarm signal shall be provided.
The alarm signals may be activated automatically by sensors detecting heat,
flame, smoke or gas; or manually by push buttons strategically located in the
different levels of the platform.
Location, number, type and effect of alarm systems and signals shall promote
easy identification of the alarm signal in the required areas.
After an audible alarm, an announcement on the public address systems is
required. Typically, for muster, general and toxic gas alarm conditions, the
personnel shall stop all work, follow the instructions given over the public address
system and carry out their emergency response duties. Personnel without
emergency response duties shall report to the mustering area immediately unless
other wise instructed.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 38
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 39
Menú Principal Indice manual Indice norma
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 40
Menú Principal Indice manual Indice norma
– Helideck.
– Flotel or other installations linked by bridge/walk way.
S Primary escape paths shall be located along the outer edge of the platform to
reduce smoke exposure.
S Escape routes shall preferably be part of the daily used transport and
passageways. Where appropriate, main escape routes shall be provided on
the outside along the periphery of the installation.
S Doors shall normally open in the direction of the escape routes, but shall not
block the outside escape route. Opening of doors should not require electric,
hydraulic or pneumatic power. If such power is required the power supply shall
be local.
S Any dining room or recreation room in the living quarter where more than 15
persons may be assembled shall have at least two exit doors. Internal room
arrangement shall be evaluated for possible blockage of exits following an
accident as well as external blockage. For all areas where there is a risk of
congestion and panic, the doors shall be provided with panic bars.
S All living quarters shall be provided with at least one path of escape to the sea
as well as two independent paths of escape. Walkways on the exterior sides
of the living quarters opposite to the operation area enhance safe egress from
the building.
S Escape routes leading to a higher or lower level shall be provided by stairways.
The number of these stairways shall be assessed based on the platform size,
configuration of areas and equipment layout. Vertical ladders can be used in
areas where the work is of such a nature that only a few persons (max. 3) are
in the area on short time basis.
S It shall be possible to escape from a drilling area without running through a
wellhead area.
S A dead end corridor of more than 5 meters length is not acceptable. Stairways
included in escape routes shall be designed to allow for transport of injured
personnel on stretcher.
S Escape routes and emergency stations shall be illuminated. Escape routes
shall be provided with adequate emergency lighting. Emergency stations
should have minimum 15 lux, escape routes minimum 4 lux.
S Escape routes in all areas outside the living quarters shall be marked by yellow
painting on the floor.
S The escape routes within the living quarter shall be provided with low level
directional lighting, showing correct escape direction. Other enclosed and
regularly manned utility and process areas shall be considered separately.
S Escape routes shall be arranged from the drill floor to adjacent modules and
also down the substructure. Protection of these escape routes from radiation
heat shall be considered.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 41
Menú Principal Indice manual Indice norma
If escape to the sea is difficult, the evacuation philosophy may include a temporary
mustering area. The designated temporary mustering area should be designed
to withstand the worst case fire or explosion scenario. All mustering areas shall
have at least two independent paths to the sea, and evacuation and survival gear
for all personnel shall be available at these locations.
b. Evacuation Means
The evacuation means which depend on the external conditions do not provide
safety under all circumstances. Therefore, offshore installations shall be provided
by other primary evacuation systems which shall be controlled from the
installation and do not depend on external intervention. They shall have sufficient
capacity to guarantee the complete evacuation of all personnel in a wide range
of possible emergencies. These evacuation systems may consist of totally
encapsulated, self propelled vessels (also called escape chutes). If for any
reason these primary systems are partially or totally unavailable, alternate
descent means to the water and means to rescue personnel from the water, within
a wide range of climatic conditions shall be provided. Appropriate survival
equipment shall be provided for all personnel onboard. The above mentioned
shall be based on a risk analysis.
Safety evaluations shall be performed to cover all aspects of personnel protection
in case of emergency. The evacuation, escape and rescue process shall be
evaluated to develop and revise the facility emergency plans.
The selection of the equipment that constitutes the evacuation systems shall be
based in a systematic analysis and shall be the equipment that is better adapted
for the installation. The systematic analysis shall cover the formal command
structure, helicopters, totally encapsulated, self–propelled vessels, life rafts and
other escape means towards the waters, available boats and other means for
rapid rescue of the escape equipment and survivors.
The helicopters shall be the preferred evacuation means from the offshore
installations as a precautionary measure in those cases in which helicopters can
be utilized during the development of the emergency. For these reason the use
of helicopters and the associated facilities shall be considered in the design of
offshore installations.
The helidecks shall be designed complying with the international standards for
civil aeronautics in offshore installations. Emphasis shall be made on the fire
fighting and extinguishing systems. Additionally, the access means to the
helicopter shall consist of safe ways for personnel so they can arrive easily to the
helideck from any point in the installation.
The quantity and location of these evacuation means shall be determined based
on a safety analysis, considering that they all be easily accessible from any area
of the platform.
RISK ENGINEERING MANUAL PDVSA IR–G–01
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 42
Menú Principal Indice manual Indice norma
If there is an independent platform for the control room, this shall be the meeting
point in case of emergency.
The availability, type and characteristics of backup rafts for rescue in the water
shall be studied during the development of the emergency plan.
7.8.4 Survival Equipment
Each offshore installation shall be provided with the survival equipment
mentioned below. The quantity of personal survival equipment shall be sufficient
for the maximum number of personnel on the platform at one time, including
visitors:
1. Life jackets
2. Smoke masks with single filter to provide protection for at least 10 minutes,
during the escape.
3. Flashlights
4. Fire proof gloves
5. Self contained breathing apparatus
6. First aid kit
7. Equipment for transporting injured personnel
8. Fire fighting equipment
9. H2S detection equipment where required
10. Storage bins for the life jackets
The quantity and location of these equipment shall be determined based on an
analysis in each particular platform. In any case, the lifesaving vests shall be
provided to each individual for continuous use, whereas an additional quantity of
lifesaving ring shall be provided in strategically located points.
PDVSA
REVISION FECHA
SAFETY CRITERIA FOR THE DESIGN OF
OFFSHORE INSTALLATIONS 1 FEB.01
Página 43
Menú Principal Indice manual Indice norma
7.9.3 The design of the control room shall be based in principles and concepts
established in the PDVSA Standard IR–C–02 “Diseño de Edificios de Control”,
introducing the modifications and/or additions required by the nature of the
installation. These modifications or additions are as stated below:
a. The platform where the control room is located shall be placed upwind to prevent
that releases of flammable and/or toxic gases travel towards the control room.
b. Due to the weight limitations, the control room in offshore installations shall be of
normal construction but using non combustible building materials.
c. The design of the control room shall be such that the side adjacent to the operation
platform has the smallest possible area.
d. The use of windows in the control room shall not be allowed, and if for any reason
a window must be installed, the material strength shall be equal to that of the walls.
e. The air conditioning systems shall not allow the entry of flammable and/or toxic
gases, smoke, etc., inside the room.
f. Two emergency exits shall be provided in opposite sides and exiting to a safe
area.
g. If due to space or design conditions the control room is located in the production
platform, a positive pressure (pressurization) shall be maintained inside the
control room to prevent the entry of gases and smoke through main and
emergency doors. Special care must be taken regarding the suction location for
the pressurization equipment and air conditioning to guarantee the suction of
fresh air. If the operational and design conditions warrant it, gas detectors shall
be placed in this area.