You are on page 1of 2

DSEGenset®

DSE7410/20
SPECIFICATIONS

DC SUPPLY
CONTINUOUS VOLTAGE RATING
AUTO START & AUTO MAINS FAILURE MODULES 8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries

MAXIMUM OPERATING CURRENT


260 mA at 12 V, 130 mA at 24 V

MAXIMUM STANDBY CURRENT


120 mA at 12 V, 65 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G,H,I & J


2 A DC at supply voltage

GENERATOR
VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz
KEY FEATURES • “Protections disabled” feature KEY BENEFITS MAINS (UTILITY) (DSE7420)
• Configurable power-up mode • kW protection • 132 x 64 pixel ratio display for VOLTAGE RANGE
• MPU fail delay • Reverse power (kW) protection clarity 15 V to 333 V AC (L-N)
• Enhanced graphical user interface • LED and LCD alarm indication • Real-time clock provides accurate
FREQUENCY RANGE
• Drag & drop advanced PLC editor • Power monitoring (kW h, kV Ar, kV event logging 3.5 Hz to 75 Hz
• MSC ID within PLC GenComm A h, kV Ar h) • Multiple date and time scheduler
override • Load switching (load shedding and • Set maintenance periods can be BUS (DSE7410)
VOLTAGE RANGE
• 4-Line back-lit LCD text display dummy load outputs) configured to maintain optimum 15 V to 333 V AC (L-N)
• Five key menu navigation • Automatic load transfer (DSE7420) engine performance
• Front panel editing with PIN • Unbalanced load protection • Built in ethernet communications FREQUENCY RANGE
3.5 Hz to 75 Hz
protection • Independent Earth Fault trip provides advanced remote
• Customisable status screens • USB connectivity monitoring MAGNETIC PICK UP
• Power save mode • Backed up real time clock • Modules can be integrated into VOLTAGE RANGE
• 11 configurable inputs • Fully configurable via DSE building management systems +/- 0.5 V to 70 V
• 8 configurable outputs Configuration Suite PC software (BMS) using MODBUS FREQUENCY RANGE
• Flexible sensor inputs • Configurable display languages • Increased input and output 10,000 Hz (max)
• Configurable timers and alarms • Remote SCADA monitoring via DSE expansion capability via DSENet®
DIMENSIONS
• 3 configurable maintenance alarms Configuration Suite PC software • Licence-free PC software OVERALL
• Multiple date and time scheduler • User selectable simultaneous • IP65 rating (with supplied gasket) 240 mm x 181 mm x 42 mm
• Configurable event log (250) RS232, RS485 & Ethernet offers increased resistance to water 9.4” x 6.8” x 1.6”
• Tier 4 CAN engine support communications ingress
PANEL CUTOUT
• Integral PLC editor • Configurable MODBUS pages • PLC editor allows user configurable 220 mm x 160 mm
• Easy access diagnostic page • MODBUS RTU & TCP support functions to meet specific 8.7” x 6.3”
• CAN and Magnetic Pick-up/Alt. • Advanced SMS messaging application requirements
MAXIMUM PANEL THICKNESS
sensing (additional external modem • Data logging to assist with fault 8 mm
• Fuel usage monitor and low fuel required) finding 0.3”
alarms • Additional display screens to help
STORAGE TEMPERATURE RANGE
• Charge alternator failure alarm with modem diagnostics
-40 °C to +85°C
• Manual speed control (on • Idle control for starting -40 °F to +185 °F
compatible CAN engines) • DSENet® expansion compatible
• Manual fuel pump control • 20 parameter data logging OPERATING TEMPERATURE RANGE
-30 °C to +70 °C
• Engine exerciser -22 °F to +158 °F

RELATED MATERIALS
TITLE PART NO.
DSE7410 Installation Instructions 053-085
DSE7420 Installation Instructions 053-088
DSE74xx Quick Start Guide 057-162
DSE74xx Operator Manual 057-161
DSE74xx PC Configuration Suite Manual 057-160

DEEP SEA ELECTRONICS LTD DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 TELEPHONE +1 (815) 316 8706
EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com EMAIL usasales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-108/12/20 (5)
DSEGenset®

DSE7410/20
ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2

AUTO START & AUTO MAINS FAILURE MODULES EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE7410 is an Auto Start Control The DSE7400 Series modules are
Module and the DSE7420 is an Auto compatible with electronic (CAN) and TEMPERATURE
Mains (Utility) Failure Control Module non-electronic (magnetic pick-up/ BS EN 60068-2-1
Ab/Ae Cold Test -30 ºC
suitable for a wide variety of single, alternator sensing) engines and offer BS EN 60068-2-2
diesel or gas, gen-set applications. a comprehensive number of flexible Bb/Be Dry Heat +70 ºC
inputs, outputs and extensive engine
VIBRATION
A sophisticated module monitoring protections so the system can be BS EN 60068-2-6
an extensive number of engine easily adapted to meet industry Ten sweeps in each of three
parameters, the DSE74xx will requirements. major axes
annunciate warnings, shutdown and 5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
engine status information on the The modules can be easily configured
back-lit LCD screen, illuminated LED, using the DSE Configuration Suite HUMIDITY
remote PC, and audible alarms. The Software. Selected front panel editing BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 ºC
module includes RS232, RS485 & is also available. @ 95% RH 48 Hours
Ethernet ports as well as dedicated BS EN 60068-2-78
terminals for system expansion. Cab Damp Heat Static 40 ºC
@ 93% RH 48 Hours

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
DSE2130 MODEM MODBUS PC
DSE2131
DSE2133
DSE2152 11 6 4
DSE2157
DSE2548 232 485

DSENET® RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V

ETHERNET
+

DEUTZ
DSE7410/20 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) SENSING (DSE7420) N/C VOLT FREE N/O VOLT FREE GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
BUS SENSING (DSE7410) OUTPUT OUTPUT ALTERNATOR OUTPUTS ENGINES OR
FLEXIBLE WITH CAN MAGNETIC PICK-UP
VOLTS CURRENT VOLTS
D+
W/ L +

1ph 1 1 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISO 9001
Registered
Quality
Managem
ent 015

You might also like