You are on page 1of 2

Product data sheet

Specifications

TRIHAL 1600kVA 13,2kV/420V 24


kV IP00 TIER2
TRI160024K2A3YEB1

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Product range Trihal

Product or component type Transformer

Transformer type Dry type transformer

Network type AC

Type of installation Indoor

Maximum altitude 1000 m

Cooling mode AN (air natural)

Winding material Aluminium

Insulation material Pre-impregnated (LV)


Cast resin (HV)

Degree of protection IP00

Mounting mode Ground mounted

Complementary
Phase 3 phases

Rated power 1600 kVA

Rated frequency 50 Hz

Rated primary voltage 13.2 kV

Secondary voltage ( at no-load) No load:


No load: 420 V

Insulation voltage to industrial 24 kV AC primary


frequency ( 50 Hz 1 mn) 1.1 kV AC secondary

Rated insulation level Primary circuit: 50 kV AC


Secondary circuit: 10 kV AC

Lighting impulse whistand 125 kV


voltage ( BIL) , 1.2/50 µs

Vector group Dyn11

HV tappings (off circuit) +/- 4 x 2.5 %

Short circuit impedance 6 %

No-load losses 1980 W

Load losses at 75°C/120 °C 13000 W at 120 °C

Temperature rise of windings 100 K

Mar 4, 2022 1
Thermal class F

Sound power level 53 dB at 1 m

Electrical connection Cable high voltage connection


Cable low voltage connection

Protective relay protection relay T-154

Height 2230 mm

Width 960 mm

Length 1820 mm

Total weight 3962 kg

Environment
Ambient air temperature for -25…40 °C for C4
operation

Ambient air temperature for -50…40 °C C4


storage

Environmental certification 0…95 % (E4)

Fire certificate F1

Standards UNE 21538-1:2018

Corrosion category C4

2
Mar 4, 2022

You might also like