EN Ultrasonic Probe KNX SO250 1

Dimensions Total diameter approx. 60 mm, Sensor


4.1. Standard display screen
total head height approx. 45 mm, thread 1½ Fig. 1
KNX SO250 inches The measuring track is aligned ver- Standard screen:
Connection cable RG 58 coax cable, length 10 m (not extenda- tical to the sensor surface. The mea-
Ultrasonic Probe ble*) 90° suring track has to meet the measu-
KNX SO250 Tank Sensor or KNX SO250 Tank Sensor
Tank content:
Total weight approx. 480 g ring surface vertically, too. Distance: 59.4cm 4885 Litre
Settings > Settings >
Ambient temperature +0…+40 °C
Technical specifications and installation instructions Measurement range 12…250 cm The display shows the currently measured distance and/or the tank content (ac-
Item number 70151 cording to the setting). If a measurement is not possible the message „No echo
*It is mandatory that the rail-mounted evaluation unit be mounted in the area of received!“ will be displayed.
the 10 metre RG 58 cable. The following settings can be made directly at the KNX SO250 Tank Sensor:

2. Installation and commissioning • Distance measurement


• Fill level measurement
• Relay set-up
2.1. Installation notes

Measuring track
• Acoustic alarm

90° The display will be dimmed after keys have not been operated for 60 seconds.
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician. 4.1.1. Function of the keys in the display menu
Measuring surface Confirm the selection, continue with next step.
DANGER!
Risk to life from live voltage (mains voltage)! To avoid wave formation in fluids, the measured area can be separated using a Go to previous step.
There are unprotected live components inside the device. measuring tube (Ø at least 50 mm).
• Comply with the locally applicable directives, regulations and provisions Note: The measuring surface is only quiet as long as the end of the measuring Change setting (select a setting or change a value). The cur-
for electrical installation. tube is below the surface. sor (flashing rectangle) indicates which menu item is selec-
ted.
• De-energise all cables to be mounted and take safety precautions against
unintentional switch-on. ok Confirm the setting and return to the standard display
1. Description • Inspect the device for damage before installation. Only put undamaged
RG 58
Fig. 2 screen.
devices into operation. The area must not be hermetically sealed
The Ultrasonic Probe KNX SO250 is used for measurement of the fill level of
• Immediately take the device or system out of service and secure it against so that the filling level in the pipe can
4.2. Distance measurement
liquids in tanks or for distance measurement. In addition to application areas like
rainwater cisterns or fuel tanks, also e. g. fish ponds or wells or the parking distan- unintentional switch-on if risk-free operation is no longer guaranteed. change. The Ultrasonic Probe KNX SO250 can measure distances. The following set-
ce of trucks can be monitored. Please follow the "Instructions for assembly and If air vents are provided, they must be tings are made in the menu „Distance measurement“:
operation" on page 4. Use the device exclusively for building automation and observe the operating ins- placed at the level of the probe (rubber
tructions. Improper use, modifications to the device or failure to observe the ope- part) (in the figure above the arrow). Ope- • Unit of the distance display
The display directly indicates the distance/fill level. The integrated key pad is used rating instructions will invalidate any warranty or guarantee claims. nings in the area of the measuring track • Time interval between measurements
for selection of the tank dimensions and setting of two relay switching outputs. Operate the device only as a fixed-site installation, i.e. only in assembled conditi- lead to incorrect measurements. Standard screen:
When the relays are switched an additional acoustic alarm can be emitted. on and after conclusion of all installation and operational start-up tasks, and only
in the surroundings designated for it. Loud surrounding noise (e.g. when filling metal tanks) may disrupt the measure- or
The KNX software ETS software allows individual parameterization of all bus func- KNX SO250 Tank Sensor KNX SO250 Tank Sensor
Tank content:
tions of the KNX SO250. Five switching outputs with adjustable threshold values Elsner Elektronik is not liable for any changes in norms and standards which may ment. Distance: 59.4cm 4885 Litre
are available. occur after publication of these operating instructions. Settings > Settings >
Please contact us with any questions regarding the area of application or installa-
tion.
Functions: 2.2. Instructions for assembly and operation Press key once to enter the "Settings" menu.
• Distance measurement
• Fill level measurement in spherical, rectangular and cylinder tanks. Note for recording the filling amount of tanks: 2.3. Connection Distance measurem.>™ Move the cursor (flashing rectangle on the
Several similar tanks as battery
Fill level meas. > right) using the keys and to the menu
When recording the filling amount, check if the entire tank content is available — 1 2 3 4
Relay set-up >
item “Distance measurement“ and press
• Setting of the two relays with the integrated display and keypad or if a residual part has to remain in the tank due to its design. For example, in oil
Acoustic alarm >

• Setting of bus functions by means of the KNX software ETS. 5 switching key .
tanks, the intake pipe does not typically reach the ground to prevent draining se-
outputs with adjustable threshold values (Threshold values can be set by diments. In such cases, approx. 5—10% of the tank content can be unavailable.
parameter or via communication objects) Display in mm >™ Move the cursor using the keys or to
Display in cm >
2.2.1. Evaluation device the required setting. You can display the
Configuration is made using the KNX software ETS. The product file can be dow- Display in m >
distance in millimetres (mm), centimetres
nloaded from the Elsner Elektronik website on www.elsner-elektronik.de in the
Must only be installed and operated in dry, indoor spaces. (cm) or meters (m). Confirm your selection
“Service” menu.
Avoid condensation. by pressing the key .
1.1. Scope of delivery
The evaluation unit of KNX SO250 s designed for series installation on mounting Measurement Use the keys and to set the required
• Evaluation unit in series installation housing rails and occupies 7 units. frequency?
time interval for the measurements.
Once every 8 sec.™
• Ultrasound sensor with 10 m power cable
After the operating voltage has been applied, the device will enter an initialisation
phase lasting a few seconds. During this phase no information can be received or
1.2. Technical Data Setting options: From 1 s to 9 s in increments of one second from 10 s to 50 s in
sent via the bus.
increments of ten seconds, from 1 min to 120 min in increments of 10 minutes.
1.2.1. Evaluation Unit 2.2.2. Ultrasonic probe Confirm your selection by pressing the key . You will automatically return to the
standard screen.
Housing Plastic material 5 6 7
Colour White Use only for level measurement of water or fuel oil! Fig. 3 5 Operating voltage input 4.3. Fill level measurement
Mounting Snap-on fitting on mounting rails Not suitable for aggressive media (acids, alkalis)! 1 Connection measurement pro- 230 V AC, L / N
Degree of protection IP 20 after installation in distributor according Not suitable for explosive media! be, +/screen 6 Relay output 1 (close-circuit The KNX SO250 Tank Sensor can measure the fill level of liquids in tanks. Possi-
to DIN 43880 2 Bus connection (KNX terminal contact), 13 / 14 ble tank designs are rectangular tanks, spherical tanks, vertical or horizontal tanks.
Dimensions approx. 123 x 89 x 61 (W x H x D, mm), 7 +/-) 7 Relay output 2 (close-circuit If more than one similar tank exist in a battery only one tank needs to be described
width units If you are unsure whether the probe is suitable for a certain medium, please con- 3 Programming LED and pro- contact), 23 / 24 for the KNX SO250 to calculate the content according to the specified tank num-
tact the technical service of Elsner Elektronik. gramming button Connections 1, 5, 6 and 7 suitable ber. The following settings are made in the „Fill level measurement“ menu:
Weight approx. 345 g
4 Bus connection (KNX terminal for solid conductors up to 1.5 mm²
Ambient temperature Operation 0…+45 °C, Storage -25…+70°C • Tank design
Do not cause any mechanical stress on the front part +/-) or fine-wire conductors
Ambient air humidity 5...95% R. H., avoid bedewing • Tank volume/capacity/fill height
(rubber)! • Probe distance to liquid for full tank
Operating voltage 230 V AC, 50 Hz
Power consumption max. 4 W 3. Addressing of the device at the bus • Number of tanks in a battery
• Unit of the fill level display
Outputs • KNX data • Time interval for measurements
The measuring head must be dry: The device is supplied with the bus address 15.15.255. You can program another
• 2 x Relay, potential-free NOC, max. 250 V
It must not be washed by liquids! address into the ETS by overwriting the 15.15.255 address or by teaching via the
AC / 7 A Standard screen:
No condensation, no droplet formation! programming button.
Data output KNX +/- bus terminal plug or
KNX SO250 Tank Sensor KNX SO250 Tank Sensor
Group addresses max. 254
4. Settings on the device Distance: 59.4cm
Tank content:
4885 Litre
Allocations max. 255 The measuring track must be free: Settings > Settings >
Communication 57 No steam, fog, etc. between the sensor and the measuring surface!
objects Steam is formed e.g. when a warm fluid is poured into a tank. The display of the KNX SO250 is only used for defining the
Press key once to enter the “Settings“ menu.
specifications for the two output relays. Additional parameterization
The product conforms with the provisions of EU directives. options can be found in the ETS programme file. Move the cursor (flashing rectangular at
The measured surface must be still: Distance measurem.>
Fill level meas. >™ the right side) using the keys and to
1.2.2. Air ultrasonic probe No waves, no vibrations! The bus allows blocking of a measurement and to request a repeated measure- Relay set-up >
Acoustic alarm > the menu item “Fill level measurement“
ment. The blocking and the measured value also apply for the relays. and press key .
Housing Plastic material
Colour Black
Degree of protection IP 52
Liquid resistance Water, fuel

Ultrasonic Probe KNX SO250 • Version: 04.05.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
Ultrasonic Probe KNX SO250 2

4.4.2. Relay 1 / 2 for fault warning


Rectangular tank >™ Move the cursor using the keys or to Please enter the number Use the keys and to select how many
Spherical tank > of tanks
Cylinder vertical > the required setting. The KNX SO250 can in a battery: of the described tanks exist in one battery If you want to output a fault warning via
R 1 settings >™
Cylinder horizont.> determine the fill level of rectangular 2 tanks ™ (1 to 100 tanks). Press key to confirm R 2 settings > the relay, use the keys or to move the
tanks, spherical tanks, vertical or horizon- your selection. R 1 fault warning >
cursor to the menu item "R 1 Fault war-
R 2 fault warning >
tal cylindrical tanks. ning" or "R 2 Fault warning".
Display in Litres >™ Move the cursor to the required setting
Press key to confirm your selection and continue as described for the relevant Display in m3 > using the keys or . The KNX SO250
Display in % > Confirm your selection with the key . You will automatically return to the basic
tank design. can indicate the tank fill volume in Litres
status.
(l), cubic metres (m³) or percent (%). Press
4.3.1. Rectangular tank key to confirm your selection. The selected relay now closes in the event of a fault, further settings are not pos-
sible. To switch off the fault message, select a function for the relay in the "R 1/2
Tank volume in l >™ Move the cursor (flashing rectangular at settings" menu item.
Tank volume in m3 > the right side) using the keys and to Measurement frequency? Use the keys and to specify the requi-
Please select unit! Once every 8 sec.™
the required setting. You can specify the red time interval for the measurements. 4.5. Acoustic alarm
capacity of a tank in Litres (l) or cubic me-
tres (m³). Press key to confirm your se- The KNX SO250 Tank Sensor can optionally emit an acoustic alarm if the actual
lection. Setting options: From 1 s to 9 s in increments of one second, from 10 s to 50 s in values are below or above the values specified for the relays.
increments of ten seconds, from1 min to120 min in increments of 10 minutes.
Standard screen:
Press key to confirm your selection. You will automatically return to the stan-
KNX SO250 Tank Sensor or KNX SO250 Tank Sensor
Please enter the or Please enter the dard screen. Tank content:
maximum capacity maximum capacity Distance: 59.4cm 4885 Litre
of one tank:
5000 Litres >™
of one tank:
5000 m3 >™ 4.4. Relay set-up Settings > Settings >

Standard screen: Press key once to enter the "Settings" menu.


Use the keys and to select the maximum capacity of a tank (in a later step the
number of existing tanks can be specified). KNX SO250 Tank Sensor or KNX SO250 Tank Sensor Distance measurem.> Move the cursor (flashing rectangular on
Setting options: Litres: 1 to 99 l in increments of one Litre, 100 to 900 l in incre-
Tank content: Fill level meas. >™ the right side) to the menu item “Acoustic
Distance: 59.4cm 4885 Litre Relay set-up >
ments of hundred Litres, 1000 to 100,000 l in increments of thousand Litres. Cubic Settings > Settings > Acoustic alarm > alarm“ using the keys or and press
metres: 1 to 99 m³ in increments of one cubic metre, 100 to 900 m³ in increments key .
of hundered cubic metres, 1000 to 100,000 m³ in increments of thousand cubic me- Press key once to enter the “Settings“ menu.
tres. Acoustic alarm off >™ Move the cursor to the required setting
Distance measurem.>™ Move the cursor (flashing rectangular at with relay 1 > using the keys or . The KNX SO250
Press key to confirm your selection. Fill level meas. > the right side) to the menu item “Relay set- with relay 2 >
can emit an acoustic alarm if relay 1 is
Relay set-up > with relay 1 & 2 >
Acoustic alarm > up” using the keys or and press key switched on, if relay 2 is switched on or if
Please enter the Use the keys and to select the maxi- . relay 1 or relay 2 is switched on.
maximum fill level of
the tank: mum fill level of the tank (1 to 254 cm).
230 cm ™ 4.4.1. Set relay 1 / 2
Press key to confirm your selection. You will automatically return to the stan-
If you want to use the relay for automatic dard screen.
Press key to confirm your selection and continue as described in “Settings for R 1 settings >™
all tank designs“. R 2 settings > filling/emptying or for overflow/empty
R
R
1
2
fault warning
fault warning
>
> warning, use the keys or to move the 4.6. Language
4.3.2. Spherical tank cursor to the "R 1 settings" or "R 2 settings"
menu item. Standard screen:
Please enter the inside Use the keys and to select the inside KNX SO250 Tank Sensor or KNX SO250 Tank Sensor
diameter
diameter of a tank (1 to 1000cm). The setting options are the same for both relays. Confirm your selection with the Tank content:
of the tank:
200 cm ™ key . Distance: 59.4cm 4885 litres
Settings > Settings >

Tank fill level >™ Use the buttons or to move the cur-
Press key to confirm your selection and continue as described in “Settings for Tank drainage > Press key once to enter the "Settings" menu.
sor to the desired setting. Confirm your se-
all tank designs“. Overfill warning >
Empty warning > lection with the key . Language > ™ Move the cursor (flashing rectangular on
4.3.3. Cylinder vertical the right side) to the menu item “Langua-
ge“ using the keys or and press key
Tank fill level:
Please enter the inside Use the keys and to select the inside .
diameter
of the tank: diameter of a tank (1 to 1000 cm). Press key Start tank filling use the keys and to set the minimum
200 cm ™ to confirm your selection. with R 1 when
level (in %) at which the filling of the tank Sprache :Deutsch ™ Move the cursor to the desired language
a minimum level of
15% is reached. is started. Confirm with the key . Language :English using the or keys (German, English,
Langue :Français
Lingua :Italiano v French, Italian or Spanish).
Please enter the Use the keys and to select the maxi-
maximum fill level
mum fill level of the tank (1 to 254 cm). Stop tank filling Use the keys and to set the maximum
of the tank: with R 1 when Press key to confirm your selection. You will automatically return to the stan-
230 cm ™ level (in %) at which the filling of the tank
a maximum level of dard screen.
90% is reached. is stopped. Confirm your setting with the
key . You will automatically return to the
Press key to confirm your selection and continue as described in “Settings for
initial position. 5. Disposal
all tank designs“.
Tank drainage: After use, the device must be disposed of or recycled in accordance with the legal
4.3.4. Cylinder horizontal regulations. Do not dispose of it with the household waste!
Start tank drainage Use the keys and to set the maximum
Please enter the tank Use the keys and to select the length with R 1 when
level (in %) at which the emptying of the
length: a maximum level of
200 cm > ™ of the tank. 90% is reached. tank is started. Confirm your setting with
the key .

Setting options: 1 to 99 cm in increments of one centimetre, 100 to 900 cm in in- Stop tank drainage Use the keys and to set the minimum
crements of hundred centimetres, 1000 to 100,000 cm in increments of thousand with R 1 when
level (in %) at which the emptying of the
a minimum level of
centimetres. 15% is reached. tank stops. Confirm your setting with the
Press key to confirm your selection. key . You will automatically return to the
initial position.
Please enter the Use the keys and to select the inside
inside diameter
of the tank: diameter of the tank (1 to 1000 cm). Overfill warning:
200cm ™
Warn "Tank is full" Use the keys and to set the maximum
with R 1 when
Press key to confirm your selection and continue as described in “Settings for a maximum level of level (in %) from which an overflow mes-
all tank designs“. 90% is reached. sage is output. Confirm your setting with
the key . You will automatically return to
4.3.5. Settings for all tank designs the basic status.

Please enter the probe Use the keys and to select the distan- Empty warning:
distance
ce of the probe to the liquid for full tank (12
to the liquid for Warn "Tank is empty" Use the keys and to set the minimum
a full tank: 15cm™ to 200 cm). Press key to confirm your se- with R 1 when
level (in %) from which an empty message
lection. a minimum level of
15% is reached. is output. Confirm your setting with the
key . You will automatically return to the
basic status.

Ultrasonic Probe KNX SO250 • Version: 04.05.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250