Professional Documents
Culture Documents
Hvac For Architects-E
Hvac For Architects-E
PART
PART USAGE VENDOR-1 VENDOR-2
LOAD
% % IKW/TR IKW/TR
100.00 A 1.00 1.13 0.01 1.25 0.01
75.00 B 42.00 1.28 0.54 1.33 0.56
50.00 C 45.00 1.60 0.72 1.50 0.68
25.00 D 12.00 2.55 0.31 2.00 0.24
IPLV 1.57 1.49
30 % 10 %
40 % MORE
HEAT
TRANSFER SIZE
HIGH PERFORMANCE PACKAGED AIR-CONDITIONERS
HIGH PERFORMANCE PACKAGED AIR-CONDITIONERS
DESCRIPTION STANDARD UNIT HIGH PERFORMANCE UNIT
REQUIREMENT 16,000 sq.ft of space- needs 126 TR of AC - 66000 CFM
UNIT CAPACITY 10 NOS X 16.5 TR UNITS 8 NOS X 16.5 TR UNIT
TOTAL OUTPUT 165 TR – 66000 CFM 132 TR – 72000 CFM
INVESTMENT Rs.2,40,000/- x 10 = Rs.3,25,000/- x 8 =
Rs.24,00,000/- Rs.26,00,000/-
PRICE DIFFERENCE Rs.2,00,000/-
CONNECTED POWER 20.6 KW X 10 = 206 KW 19.7 KW X 8 = 157.6 KW
POWER CONSUMPTION 206 KW X 250 DAYS X 0.75 157.6 KW X 250 DAYS X 0.75
DIVERSITY FACTOR X 10 DIVERSITY FACTOR X 10
HOURS/DAY X RS. 7/- = HOURS/DAY X RS. 7/- =
Rs.27,03,750/- Rs.20,68,500/-
ANNUAL POWER Rs.6,35,250/-
SAVING
RETURN ON
INVESTMENT
ACREX : BANGALORE : NET ZERO ENERGY BUILDING
AIR HANDLING UNITS
PLUG FAN VS CENTRIFUGAL FAN
PLUG FAN
CENTRIFUGAL FAN
ACOUSTIC INSULATION OF DUCTS
OPEN CELL NITRILE
RUBBER
FIBREGLASS
ALUMINIUM
PERFORATED
SHEET
THERMAL INSULATION OF DUCTS
CLOSED CELL
NITRILE RUBBER
FIBREGLASS
ACOUSTIC INSULATION OF DUCTS
ENERGY RECOVERY
VENTILATOR – 15 %
SAVING IN ENERGY
BUILDING MANAGEMENT SYSTEM
BUILDING MANAGEMENT SYSTEM
Scope for energy saving
is approx 20 %
INTEGRATED BUILDING MANAGEMENT SYSTEM
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
INFOSYS - GREEN INITIATIVES
INFOSYS SAVES HUGE POWER COST
THIS GUY SAVES POWER COST @ RS.50 CRORES PER YEAR TO INFOSYS
Guruprakash Sastry
Senior Manager – Green Initiatives | Infrastructure
Infosys Limited
Bangalore 560 100
Tel: +91 80 39148650
M: +91 97399 76191
Email: guruprakash_sastry@infosys.com
INFOSYS - POWER CONSUMPTION
1,30,000 employees
28 million sq.ft.
• Total built-up space of Infosys, India at the end of
2010-11
10 lakh units
• Consumption per working day @ Infosys, India in
2010-11 – 70 LAKHS
45
INFOSYS ANNUAL POWER COST
RS.185 CRORES @ 2010-11
INFOSYS - GREEN INITIATIVES
Building Envelope: High Performance glazing (5.8 X)
Solar Thermal
UV Visible Near Infra
NearRed
Infrared Far
FarInfra Red
Infrared
900 W
24 0C
24 0C
35 0C
810 W
360 W
540 W 90 W
35 0C
55 W
12 W
4
7
INFOSYS - GREEN INITIATIVES
Building Envelope: Insulation
Wall (5X) Roof (13X)
35 0 C 24 0 C
45 0C
RCC roof
22 Watts
24 0C
55 Watts
35 0C 24 0C
35 0C Insulated RCC roof
4.4 Watts
24 0C
4 Watts
4
8
INFOSYS - HYDERABAD
VARIABLE AIR VOLUME – VS – RADIANT COOLING
INFOSYS - POWER CONSUMPTION
Impact of Energy Efficiency Initiatives to the bottom line
23%
improvement
• 3X improvement in
efficiency compared
to 2007 design
• Radiant cooling at
no additional cost
52
INFOSYS - REDEFINING THE STANDARDS
➢Set unreasonable targets
➢Efficient buildings do not cost more, but need a little effort
at the right time.
➢All Infosys buildings exceed ECBC efficiency requirements.
➢Good design = job half done !
➢Question all assumptions and get the sizing right
➢Select right sized efficient equipments and smart controls
➢Measure, monitor……..Measure, monitor………..feedback….