ENERGY SAVING OPPORTUNITIES

ENERGY SAVING – ELEPHANT IN THE ROOM


C.O.P. – E.E.R – IKW/TR

COOLING OUT - WATTS 1 ( TON ) X 3500 - WATTS 3.5 COP


C.O.P. POWER INPUT - WATTS 1000 WATTS

COOLING OUT - BTU/HR 1 ( TON ) X 12000 - BTU/HR 12.0 EER


E.E.R
POWER INPUT - WATTS 1000 WATTS

POWER INPUT - KW 1 ( KW ) 1 IKW/TR


IKW / TR
COOLING OUT - TON 1 ( TON )

C.O.P. – CO-EFFICIENT OF PERFORMANCE

E.E.R – ENERGY EFFICIENCY RATIO

IKW / TR – INPUT KW AND TR RATIO


IPLV
INTEGRATED PART LOAD VALUE - IPLV

IPLV evaluates the weighted energy


performance based on load, energy
efficiency and corresponding operating
time.
Vendor-1 : 1.13 INPUT KW / TON

Vendor-2 : 1.25 INPUT KW / TON

CONCLUSION : VENDOR-1 IS MORE EFFICIENT THAN VENDOR-2


IPLV
INTEGRATED PART LOAD VALUE - IPLV

PART
PART USAGE VENDOR-1 VENDOR-2
LOAD

% % IKW/TR IKW/TR
100.00 A 1.00 1.13 0.01 1.25 0.01
75.00 B 42.00 1.28 0.54 1.33 0.56
50.00 C 45.00 1.60 0.72 1.50 0.68
25.00 D 12.00 2.55 0.31 2.00 0.24
IPLV 1.57 1.49

CONCLUSION : VENDOR-2 IS MORE EFFICIENT THAN VENDOR-1 !!!!


ENERGY SAVING OPPORTUNITIES
www.savenergy.co.in
PACKAGED AIR-CONDITIONERS
EFFECT OF HIGH SENSIBLE HEAT

30 % 10 %

CONVENTIONAL LOAD PATTERN CONTEMPRORY LOAD PATTERN


HIGH PERFORMANCE PACKAGED AIR-CONDITIONERS

40 % MORE
HEAT
TRANSFER SIZE
HIGH PERFORMANCE PACKAGED AIR-CONDITIONERS
HIGH PERFORMANCE PACKAGED AIR-CONDITIONERS
DESCRIPTION STANDARD UNIT HIGH PERFORMANCE UNIT
REQUIREMENT 16,000 sq.ft of space- needs 126 TR of AC - 66000 CFM
UNIT CAPACITY 10 NOS X 16.5 TR UNITS 8 NOS X 16.5 TR UNIT
TOTAL OUTPUT 165 TR – 66000 CFM 132 TR – 72000 CFM
INVESTMENT Rs.2,40,000/- x 10 = Rs.3,25,000/- x 8 =
Rs.24,00,000/- Rs.26,00,000/-
PRICE DIFFERENCE Rs.2,00,000/-
CONNECTED POWER 20.6 KW X 10 = 206 KW 19.7 KW X 8 = 157.6 KW
POWER CONSUMPTION 206 KW X 250 DAYS X 0.75 157.6 KW X 250 DAYS X 0.75
DIVERSITY FACTOR X 10 DIVERSITY FACTOR X 10
HOURS/DAY X RS. 7/- = HOURS/DAY X RS. 7/- =
Rs.27,03,750/- Rs.20,68,500/-
ANNUAL POWER Rs.6,35,250/-
SAVING
RETURN ON
INVESTMENT
ACREX : BANGALORE : NET ZERO ENERGY BUILDING
AIR HANDLING UNITS
PLUG FAN VS CENTRIFUGAL FAN
PLUG FAN

CENTRIFUGAL FAN
ACOUSTIC INSULATION OF DUCTS
OPEN CELL NITRILE
RUBBER

FIBREGLASS

ALUMINIUM
PERFORATED
SHEET
THERMAL INSULATION OF DUCTS
CLOSED CELL
NITRILE RUBBER

FIBREGLASS
ACOUSTIC INSULATION OF DUCTS

METAL DUCTS WITH RIGID POLYURETHANE


ACOUSTIC INSULATION FOAM DUCTS – RPUF DUCTS

RPUF DUCTS OFFERES EXCELLENT SOUND REDUCTION CAPABILITIES


-FASTER COMPLETION – LOWER COST – LIGHT WEIGHT – COMBINES
THE FUNCTIONS OF METAL DUCT, ACOUSTIC AND THERMAL
INSULATION.
ENERGY SAVING DEVICES FOR PART LOAD

Scope for energy


saving is approx
25 %

VARIABLE AIR VOLUME

VARIABLE SPEED DRIVE

VARIABLE PUMPING SYSTEM


Scope for energy saving
is approx 10 %
AIR-CONDITIONING FOR ART GALLERY WITH HOTEL
FACTORS TO BE CONSIDERED
✓INDOOR AIR QUALITY
oPROVIDE FRESH AIR AS PER ASHRAE STD 62.1
oINSTALL ENERGY RECOVERY VENTILATOR - ERV
ASHRAE STD 62.1 FOR GALLERIES
– 7.5 CFM PER PERSON AND 0.06
CFM PER SQ.FT

ENERGY RECOVERY
VENTILATOR – 15 %
SAVING IN ENERGY
BUILDING MANAGEMENT SYSTEM
BUILDING MANAGEMENT SYSTEM
Scope for energy saving
is approx 20 %
INTEGRATED BUILDING MANAGEMENT SYSTEM
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
NET ZERO ENERGY BUILDING
INFOSYS - GREEN INITIATIVES
INFOSYS SAVES HUGE POWER COST
THIS GUY SAVES POWER COST @ RS.50 CRORES PER YEAR TO INFOSYS
Guruprakash Sastry
Senior Manager – Green Initiatives | Infrastructure
Infosys Limited
Bangalore 560 100
Tel: +91 80 39148650
M: +91 97399 76191
Email: guruprakash_sastry@infosys.com
INFOSYS - POWER CONSUMPTION
1,30,000 employees

28 million sq.ft.
• Total built-up space of Infosys, India at the end of
2010-11

26.5 crore units


• Annual electricity consumption @ Infosys, India in
2010-11 – 185 CRORES

10 lakh units
• Consumption per working day @ Infosys, India in
2010-11 – 70 LAKHS
45
INFOSYS ANNUAL POWER COST
RS.185 CRORES @ 2010-11
INFOSYS - GREEN INITIATIVES
Building Envelope: High Performance glazing (5.8 X)
Solar Thermal
UV Visible Near Infra
NearRed
Infrared Far
FarInfra Red
Infrared

.25 .38 .78 2.1 2.60 50 microns

Single glass Spectrally selective double wall


900 W glass with Argon filling

900 W
24 0C
24 0C
35 0C
810 W
360 W
540 W 90 W
35 0C

55 W
12 W

4
7
INFOSYS - GREEN INITIATIVES
Building Envelope: Insulation
Wall (5X) Roof (13X)

35 0 C 24 0 C
45 0C
RCC roof

22 Watts
24 0C
55 Watts

Plain Brick wall

35 0C 24 0C
35 0C Insulated RCC roof

4.4 Watts

24 0C
4 Watts

Double brick wall with insulation

4
8
INFOSYS - HYDERABAD
VARIABLE AIR VOLUME – VS – RADIANT COOLING
INFOSYS - POWER CONSUMPTION
Impact of Energy Efficiency Initiatives to the bottom line

23%
improvement

Energy consumption for 2011-12 is estimated at 205


units/emp/month
INFOSYS - POWER CONSUMPTION
300% Improvement in air-conditioning design
• Figures based on
actual measured
data in Hyderabad
climate for Apr
2011 – Feb 2012

• 3X improvement in
efficiency compared
to 2007 design

• Radiant cooling at
no additional cost

52
INFOSYS - REDEFINING THE STANDARDS
➢Set unreasonable targets
➢Efficient buildings do not cost more, but need a little effort
at the right time.
➢All Infosys buildings exceed ECBC efficiency requirements.
➢Good design = job half done !
➢Question all assumptions and get the sizing right
➢Select right sized efficient equipments and smart controls
➢Measure, monitor……..Measure, monitor………..feedback….

➢Breaking the barrier…………..


➢> 550 sqft per TR of AC area
➢< 0.5 kW/TR for chiller plant design