1.Power off and take off the inverter 12 terminal (Wire number is ENA) and the original wire connection of the coil of
output side contector 4KM1 and 4KM2. (Wire number is 478,119; 475,119). Use rubber insulation for protection.
2.Make the Enable (12 port) and +24V (19 port) of inverter be in short circuit. Connect 220VAC terminal (Wire number
3.Power on to make the communication between inverter and computer normal. And then output side contector 4KM1
and 4KM2 close. Namely, making the main curcuit be powered on.
Open the menu of STARTUP/Startup config/Enter Setup Mode Br.Then set the parameters of MOTOR DADA or
Drive DATA.
6.Open the menu of STARTUP/Startup config/Enter Setup Mode As. Push the complete still autotune button.
8.When the operation board of inverter display “End”, self learning end up.
(1)Power off and take off the inverter 12 terminal (Wire number is ENA) , 13 terminal (Wire number is FWD), 15
terminal (Wire number is V0)and the original wire connection of the coil of output side contector 4KM1 and
(2) Make the Enable (12 port) and +24V (19 port) of inverter be in short circuit. Connect 220VAC terminal (Wire
(3)Connect the part of transformer 110VAC with brake coil part respectively, as picture 1 show.
14-1
(4)Power on to make the communication between inverter and computer normal. And then output side contector 4KM1
and 4KM2 close. Namely, making the main curcuit be powered on.
(6)Open the menu Service/Brushless, click Autophasing button , connect the 13 port and 15 port of inverter with
24VDC(19 port), then, traction machine begin to circumrotate slowly .the panel display the learning progress,
(7)Operate Load setup at the path of menus/Startup/ SaveConfig, save the parameters of learning .
(9) When the learning is end up , power off renew the connecting wire of interver and contactor.
14-2