15 adjustment of parallel connection elevator

1.Standard parallel connection elevator


.Standard parallel connection elevator : the amount of elevator floor is the same .
Adjustment:
(1) locale connect wire
1)Connect the communication wire of 1# and 2#, as the piture 6.

picture6

2)Set parameters

Set in menu CONFIG :ADDRESS:one elevator is 1#, the other one is 2#

2.excursion parallel connection elevator :


(1) Locale connect wire
Connecting wire of main controller is the same with Standard parallel connection elevator
2) Set parameters
Set in menu CONFIG :
a)ADDRESS:one elevator is 1#, the other one is 2#
b)DIFERFLOOR:(00)set the amount of excursion floor
3 set dial number
Dial number setting of outer calling board , excursion floor display panel of dial number setting is the complete
amount of the two elevator floors.
Such as:
1# is:1,2,3,4…10
2# is:-1,1,2,3,4…10
So:
1#the dial setting of outer calling display panel: 2,3,4…11;
2# the dial setting of outer calling display panel is standard setting:1,2,3,4,…11
DIFFERFLOOR: Set 1.