4-Power-On and Inspection

1. After the examination and confirmation in Part III, carry out the following steps:

(1) Take away the connector assembly of the brake cable;

(2) Confirm the open status for all circuit breakers;

(3) Confirm no people within the well and car, being suitable to the conditions for elevator’s safety

operation;

(4) Confirm that the construction outside the well has no influence on elevator’s safety operation;

(5) Set the emergency stop button on control cabinet.

2. Examine the main power voltage according to 3-phase and 5-wire at the site:

Measure the main power voltage at the leading end of 1QF1 power control box, keeping

230±7%VAC and deviation not over 15VAC. Via main transformer’s voltage regulating so that the

relevant voltage is 380±7%VAC.

3. Examine the specification of main wire and capacity of main circuit breaker in accordance with

the requirements of design drawings.

4. After the confirmation of regular operation on above examination items, carry out power on

adjustment.

5. Examination after power on:

(1) Close the main power circuit breaker 1QF1, then examine the voltage between L1, L2 and L3.

(2) examine the power supply of 1TC1 and 1TC2 transformer in control cabinet and measure the

voltage as below:

Control transformer 1TC2:

Input (wire marking: L2, 110): 380±7%VAC;

Output (wire marking: 111,115): 220±7%VAC;

Output (wire marking: 113,117-): 110±7%VDC (or other voltage class)

Output(wire making:118、119):110±7%VAC
Lighting transformer 1TC1:
Input: 220±7%VAC

Output (wire marking: 105,107): 24±5%VAC;

As any problems, please check the failure immediately!

(3) As under normal operation, then close corresponding control switch 1QF6 1QF8 of control

cabinet, examine the output voltage of transformer and regulated power supply, measure the voltage

as below:

output(wire marking:114, 115): 220±7%VAC;

output ( wire marking : 116+ 、 117- ) : 110±7%VAC(or other voltage

class)

output(wire marking:105、104): 24±5%VAC;

Regulated power supply G1:

Input (wire marking: 114, 115): 230±7%VAC;

Output (wire marking: 24V, 0V): 24VDC;

Regulated power supply G2:Input is same with that of G1;

Output(Wire makeing:5V、0V1):5VDC;

1、 At the same time , the state of insulation between 0V1 and 0V can be

measured。If there are problems,please check the fault at once!

2、 The operating voltage of main controller MPK708A is Direct Current

voltagestabilizing 24V and 5V. Ifthe alternating current 220V is switched

in as the operating votage, it will be damaged.

6、The display of main controller and the setting of menu :

(1)、Display

If the output of the regulated power supply G1、G2 is correct。Close the power switch 1QF7 of

control cabinet, Main controller will display the operation homepage:

Push the key Enter,it will enter the main interface of main controller :
The following is the corresponding explanation of the bottom left corner state:
Automatic(AUTO)

Test(TEST)

Fire control(FIRE)

Driver (MANUAL)

Fulload(FULLY)

Overload(OVER)

Open door(OPEN)

Close door(CLOSE)

Self-learning(LEARN)

Leveling (LEVELL)

Lock the elevator(LOCK)

The following is the corresponding explanation of the bottom right corner state:
Open door (open)
Close door (close)

(2)、Menu

In the main interface , push the Enter key, it will enter the selection of mode of main
menu,for example:

In the menu:the first digit figure indicates the main menu,the second digit figure indicates

the corresponding submenu below the main menu.


At this time ,push “↑” and“↓”key to choose main menu item , Esc key will exit from the

selection of main menu and return to main interface,Enter key will enter the selection of submenu

item.

(3) The setting of powerup

main controller has 10 main menus totally,push“↑”、“↓”key to alter theoptions of main

menu. After the option is confirm, pushEnterkeyto enterthe submenu of this menu. The operation

after entering submenu is the same as that at main menu. In the edit pattern,push“↑”、“↓”key

to alterparameter value. After the parameter value is confirmed, push Enter key to save parameter

value. Esckey to quit modification. The defaulting have been set initially for all the parameters in

controller before ex works. But some parameters must be set anew as per the on site situation.

Main menu:

Configuration (CONFIG)

Time setting(TIME)

Setting of station(landing)(STATION)

Call menu(CALL)

Input and output(IO)

Door (DOOR)

Error history(ERROR HISTORY)

password(PASSWORD)

pulse monitor(PULSE MONITOR)

Input select(INPUT SELECT)

The following is the description of the function and setting of some menus.

A、 Configuration of menu(CONFIG)

 Push Enter key,it will enter the submenu of CONFIG menu:

ADDRESS:The scope for selection is 0-15. it is mainly used for setting the address of elevators

during the paralleling 、group control or remote monitoring of elevators(when two elevators are in

parallel, if only one is set as 1、the elevator can be set as 2).

CONNECT : OFF-LINE is the normal work module of elevator ; ON-LINE is the automatic
calling work module.

SPEED : Select the speed output of main controller , select V<1.5m/S , microprocessor only

output one speed signal V1; if V>1.6m/s,microprocessor will output two speed signals V1、V2;

if V>2.0m/s,microprocessor will output three speed signals V1、V2、V3.(The speed value that

needs outputting on site has nothing to do with rated speed.)

FLOOR DISPLAY:Set the display mode of each floor,push key ENTER to enter the following

interface:

When the display mode is modified, only need to push key ENTER,the modifying cursor “>”

sign will arise,then use “↑”、“↓”key to modify the value. After the modification is finished,

push Ente key to save the modified result. If the Esc key is pushed, it will exit from the

modification state.

DATE:by means of the year/month/day display、modify the current date.

TIME:display the current time microprocessor by hour minute second.


Note :the two items above are selective item.

LEARNING:Set the self-learning function.

MANUAL DOOR:Set clsoig door state under the driver state. OFF mode:need to push button

for long time to close door; ON mode:close the door by jog-driving.

MANUAL DIRECTION:Set if driver state external call can stop the elevator or not。OFF mode:

external can’t stop the elevator; ON mode:external call can stop the elevator.

CONVERIVE SELECT: NOT KNOW (need not to set )


DIFERFLOOR: 00 excursion landing paralleling, floor of excursion landing.

SOFTWARE VERSION: V 1.2

PULSES PR : 00128 display curve of run .

B, Time setting menu(TIME)

STOP:release time of direction/enable,the acquiescent value is 3.5s.

START:1)unused ,the the acquiescent value is 0.

2) set the time of lighting , by this setting when there is no one to call the lift the light in car is

off.(this function is fit in with Singapore)

BRAKE: unused.

DOOR OPEN:set the time of opening door , the acquiescent value is 2.1s.

DOOR CLOSE:Set the time of automatic closing door. the acquiescent value is 5s.

OPEN PROTECT:Set time of opening door protection.when opening door limit cannotbreak off

because of fault,this protection time value can be set ,door machine will stop opening door so

the danger of door machine being damaged for long time’s Power ON can be prevented, the

acquiescent value is 8s.

CLOSE PROTECT:Set the time of closing door protection. When door lock or closing door limit

can’t be connected or break off because of fault,set this protection time value so that door machine

stops closing door,and opening door anew, the acquiescent value is 8s.

RINGING : Under the driver state , set the sounding time of buzzer when there is external call

signal, the acquiescent value is 1s.

GONG : The endurance period of arrival gong signal, the acquiescent

value is 1s.

SPEED STOP:the parking protection, the acquiescent value is 0.9s.

FLOOR PROTECT:the floor protection time, the acquiescent value is 13s

TIME1 : the safety touching plate is acting, the ring time of buzzer , the

acquiescent value is 10s.

TIME2:The run time of elevator, the acquiescent value is 60s.

TIME3:1)backup

2) set the time of button locking , the setting value of parameter is more than 180s. (this
function is fit in with Singapore)

RUN TIME:Times number of operation.

C、 Setting of main stop(STATION)

BASE:Set the main stop and locking elevator landing of paralleled elevator. The floor value of this

main stop should be set as per absolute floor.

FIRE HOUSE : Set it return to that landing , this value is set according to absolute floor when

elevator is under fire control state,set.

HIGHEST:This value is acquired through self-learning. It doesn’t need setting.

WAIT(1): When the group control or paralleling of elevator is set, at ordinary times it waits on

that floor.

WAIT(2): When the group control or paralleling of elevator is set, at ordinary times it waits on

that floor.

REPLY STATION:Set the floor number of responding floors.

Denoted by binary digit,“ 1”denotes responding,:“ 0”denotes not responding.

D、Call menu(CALL)

This menu can be used for directly observing or registering the call signals of each floor,and being

able to monitor and modify the signals registered by external call of elevator. After call signal is

registered,this call signal will be erased after elevator run to this landing.

Submenu:( UP CALL)

(DOWN CALL)

(CAR CALL)

E、Input output menu(IO menu)

This menu can monitor main controller I/O state, which can’t be modified.

F、Opening door menu(DOOR)

DOOR 1:Set the floors where 1# door can be opened. “1”:can open the door,“ 0”:can’t

open the door.


DOOR 2:Set the floors where 2# door(if there is such door) can be opened. “1”:can open

the door,“ 0”:can’t open the door.

G、(ERROR HISTORY)

When error arises,the error code and failure reason will be scrolled and displayed on the lower of

the LCD screen,as follows。

MPK708n main controller can record 50 history errors. Through this menu, the time when the error

arises and the reason of the error can be checked:

H、PASSWORD

MPK708 has set maintenance and upkeep、commissioning、company three-level password menu,

it can carry out concerned commissioning work under concerned password level.

After entering operation state,power is on anew or there is no any key press after 15 minutes ,it

can be operated again when password is input again.

L、(PULSE MONITOR)

CURRENT:only read parameters,display current pulse number.

RUN_IN : record 1/4the length of magnetism-insulating board. ( see the back for the

commissioning method)。

DEL.1DISTANCE:the deceleration distance of V1 speed.

DEL.2DISTANCE:the deceleration distance of V2 speed.

DEL.3DISTANCE: the deceleration distance of V3 speed.

FLOOR :pulse number of each landing.

After key Enter is pushed, enter the the mode of examing pulse number:
When key“↑” or “↓”is pushed, the pulse number of each landing can be examined. In order to alter

pulse number, push key Enter to enter(see the back for the commissioning method):

DEL.V2 PERMIT(×DL): keep the defaulting.

DEL.V3 PERMIT(×DL): keep the defaulting.

RUN V2 Dis(×DL):the landing height of running V2 speed.

DOOR LENGTH (MM):

M (INPUT SELECTIVE MENU):

GOING BACK: OFF (seeting of back to base floor automatically.)

BRAKE: OFF (used for check switch of brake)

DISTURB PRO: light load and disturb proof

DISTURB NUM: setting of disturb number 1-8.

FIRE MODE: 01 (display of firefight ,fire ); 02 (display of firefight, F)

SAFEEDGE: select NO: safety touching plate ; OFF: light curtain

CONTROL MODE : 00 : mainland of china 01 : Russia

RE-LEVELLING : Acquiescent value is OFF; re-leveling function selective ON.

PRE-OPEN: Acquiescent value is OFF; re-open function selective ON.

PMCARD : Acquiescent value is OFF; enlargement card selective ON

OPEN-METHOD: selection of open method .

0 Means single door operator and sigle control box

Means double door operators and double control boxes or single door operator, need

1 two door operators action at the same time, if only one door operator ,the second

safety touching plate I3.0 in the condition of close.

2 Means double door operators and double control boxes , the operators be controlled
respectively

REPAIR OPEN :

0 The doors couble be opened at all floors

1 The doors couble be opened at levelling area

2 Could not open door when repair

GROUP : OFF, no group control . ON, have group control

MONITOR: OFF no group control . ON, have group control

ARRIVE LAMP : OFF no arrive lamp function .ON ,have arrive lamp.

ERROR OPEN TIMES : Times of erroe open , the function is cancelled when the value is 0.the

setting value is above 0,the auto close door will be stopped when the failing times of close door is

above the setted value .push the close button ,the door will try to close again.

TIMES4: 0S . spare item

FORCE CLOSE :OFF, no force close function. ON, have force close function.

7.Confirmation of safety circuit:

After controller is powered on , confirmation of commissioning of safety circuit is conducted.

When car top inspection is on the ‘inspection’ , the safty circuit commissioning is

conducted,confirm the following condition:

a、 The phasesequence of three phase input power source is correct. The

indicator light of phase sequence relay will shine. (if there is phase relay)

b、 Machine room 5SB5、pit 5SB6、car 5SB4、car top 5SB3 emergency stop

don’t act.

c、 The other safety circuits don’t act.

When the above conditions are met,safety circuit relay 5KA1 will act.

At the same time,in the main controller menu option(IO), open the input (I)dot-monitor

page layout.when 3.3 is highly bright, safety circuit is valid.

If normal display is not correct or there is error display ,the following commissioning can only be

conducted until the error is treated in time.

8、Confirm the normal working state of inverter after power-up:


(1) Keyboard sign

Inverter keyboard is composed of LCD monitor、7 indicator lights and function keys.

The state of the inverter’s driving signalcan be discern,its contens are as follows:

Name Color Function

-Torque Yellow The inverter output torque is minus.

+Torque Yellow The inverter output torque is positive.

ALARM Red Inverter fault

ENABLE Green Inverter enable

Zero speed Yellow The rotation speed of motor is zero.

Limit Yellow The inverter is under the current limiting .

Shift Yellow Activate the function of option 2 of the key press.

Note : For the concrete operation instruction of inverter, see the 《 SIEI inverter operation

instruction》

(2)、 the powerup display is normal.

R: 0 S: 0
MONITOR

Or after push key SHIFT, push key HOME , the above page layout will arise 。 The above page

layout is the inverter’s page layout of monitoring.

9、Initial setting of parameters of inverter:

The transducer and the corresponding traction machine have been adjusted before leaved factory , so

the adjuster only need use the following menus to adjust the elevator.

A、Monitor

Function:Monitor the operation parameter of inverter

The list of the main contents monitored:

Monitor:
Name Content Unit /note

Output current Output current A

Output power Output power KW/KVA

Norm Speed Operation speed rpm


I/O status:

Name Content Unit /note

E:enable

1、2:direction
DI 7654321E Input state
4、5、6:speed

corresponding to the drawing.

0:operation contactor

1:braking contactor
DO 3210 Output state
2:Inverter failure

corresponding to the drawing.

Advanced status:other monitor parameters.

Driver ID status:inverter ID.

Alarm log:This function provides 30 inverter errors or sytem error information,display time and

data information at the same time.

Alarm log clear:the elimination of error.

B、Travel(operation menu)

Startup config:
—Enter setup mode—Drive data(drive parameter)
According to motor parameter,
—Motor data(motor parameter) drive is set at this time.
—Autotune (slef-adjustment) used during the autotune of motor.
—Load setup:After the motor、drive parameter are altered,load system will inquire
if choose Load,choose Yes/No.
—Mechanical data:traction parameter is set at this time.
—Weights:The parameters of car、counterweight and so on are set at this time.
—Encoders config : The configuration and setting of encoder.(standard parameter
setting )
—Motor protection:Motor protection setting (standard parameter setting )
—BU protection:BU protection. (standard parameter setting )

—Load default:All the parameters of inverter are restored to the ex works defaulting.

—Load saved:call the parameter value saved last time.

Regulation mode:Field oriented.(standard parameter setting )

Save config: After parameters are altered,the results must be saved

C Travel(operation menu)

Speed profile—Smooth start spd:1mm/s

—Multi speed 0—7:Set corresponding speed value during on site commissioning as

per the drawing..

—Max linear speed : This parameter is read-only parameter, shows the maximum

linear speed(mm/s).

Ramp profile—MR0 : This parameter is set for operating slope. This manual use the defaulted
parameter group MRO. See the posterior chapters for the concrete commissioning method.

Lift sequence:
See The setting of elevator run standard
Speed threshold: parameter

Ramp function:

Save parameters:

Speed reg gains:

D Regulation Param:This menu doesn’t need specific adjustment.

E I/O config:Inverter I/O dot configurating. (See The setting of elevator run standard parameter
)