Professional Documents
Culture Documents
AJ-How Chillers React To Building Loads
AJ-How Chillers React To Building Loads
How
Chillers
React to
Building
Loads
By Kwok Tai Chan, Ph.D., Member ASHRAE, and Fu Wing Yu detailed features of the building: materi-
als, orientation, construction, ventilation
and air-conditioning requirements, occu-
Table 1: Number and size of chillers for options OP1 to OP4. Figure 1: Weather load profile.
25 3
Building Load Ratio < 0.5 for 59.9% Outdoor
0
<0.1 0.1– 0.2– 0.3– 0.4– 0.5– 0.6– 0.7– 0.8– 0.9– 0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 0.2 0.4 0.6 0.8 1.0
Building Load Ratio Chiller Part-Load Ratio
sequencing when the building load ratio reached a certain eight, the total operating hours within the full-load range rose
level. The number inside each column in the figures indi- slightly to 36.6%. For OP3 and OP4 where the chilled water
cates the number of staged chillers with a given nominal ca- plant contained six chillers with two or three different capaci-
pacity. Under options OP1 and OP2, the chilled water plant ties respectively, the full load range constituted 63.6% or 72.8%
contained equally sized chillers, and one more chiller would of total operating hours, respectively.
be staged when the building load exceeded the total capacity Based on the schedules of staging chillers at different build-
of the staged chillers. Based on this, the step of total cooling ing load ratios and on the weather-load profiles of the office
capacity corresponded to the total number of chillers installed. building, it was possible to establish the weather-load profiles
More steps meant that there was more chance the chillers of chillers for different options (Figure 6). These profiles in-
were operating with maximum efficiency at full load to meet cluded all combinations of chiller loads and outdoor tempera-
various building cooling loads. OP3 and OP4 presented the tures for determining the annual power consumption of the
opportunity to use unequally sized chillers in the chiller plant chillers. Figure 6 illustrates that with chiller sequencing, all
to allow the chillers to operate more frequently at full load. the chillers operated at a part-load ratio of at least 0.3. If free
With regard to OP3, where the air-cooled chiller plant con- cooling was applied, the lowest part-load ratio rose to 0.4 or
tained four large and two small chillers, 14 steps of total cool- even higher. There was a wide range of outdoor temperatures
ing capacity existed. When six chillers in OP4 were split into (18.4°C to 33.7°C [65.1°F to 92.7°F] for OP1; 13.9°C to 33.7°C
three different capacities, the number of steps of total cool- [57°F to 92.7°F] for OP2 to OP4) at which the chillers oper-
ing capacity further increased to 26. ated near full load with a part load ratio of 0.9 to 1. Given that
This study assessed the distribution of chiller load frequency different options provided different steps of total cooling ca-
as represented by a percentage of total operating hours at dif- pacity, the chillers could operate at a higher part-load ratio for
ferent ranges of chiller part-load ratios. Figure 5 shows that six more of the time for a given outdoor temperature when the
identical chillers under OP1 operated at the full-load range (a number of steps of total cooling capacity increased. When the
part-load ratio of 0.9 to 1) for 26.1% of total operating hours. outdoor temperature increased, the part-load ratio of the chill-
For OP2 where the number of identical chillers increased to ers rose while its extent of variation tended to decrease. Very
54 ASHRAE Journal ashrae.org August 2004
Option OP1 Option OP2
Total Cooling Capacity, kW
Option OP3
Total Cooling Capacity, kW
Option OP4
Total Cooling Capacity, kW
few chiller load data in terms of part-load ratios corresponded consumption of the chillers in kWh over the annual total build-
to the regression line of the ARI condition given by the ARI ing cooling energy in kWh (or ton-hours). The normalized
Standard 5904 that relates chiller part-load ratios ranging from annual electricity use of chillers is the annual electricity con-
1 to 0.33 with decreasing outdoor temperatures ranging from sumption in kWh per unit floor area of the building in square
35°C to 12.5°C (95°F to 54.5°F). meters. The annual electricity consumption of the chillers could
Annual energy consumption of chillers with different be reduced by 9.2% when the number of steps of total cooling
options. After identifying the weather load profiles and the capacity increased from six to 26.
schedules of their staging, it was possible to calculate how much Pump energy was not considered in this analysis. However,
electricity would be consumed by chillers in the alternative if the pumping system is assumed to be primary-secondary
options of air-cooled chiller plants. Table 2 summarizes the (P-S), then running chillers at or near full load minimizes the
seasonal efficiency of the chillers and their annual electricity pumping energy. This is because in a P-S system, any time the
consumption for each option. chiller is operating, the pump also must run. Since the pump is
Seasonal chiller efficiency means the annual total electricity a constant speed device and assuming pumping efficiency is
August 2004 ASHRAE Journal 55
constant for each pump selection, the pump’s energy consump- 80
tion is constant—regardless of the chiller load. Therefore, if Design
0.8 0.8
Chiller Part-Load Ratio
0.4 0.4
0.2 0.2
Internal Load Internal Load
Weather Dependent Load Weather Dependent Load
0.0 0.0
10°C 15°C 20°C 25°C 30°C 35°C 10°C 15°C 20°C 25°C 30°C 35°C
Outdoor Temperature Outdoor Temperature
0.8 0.8
Chiller Part-Load Ratio
Chiller Part-Load Ratio
0.6 0.6
ARI Condition ARI Condition
0.4 0.4
0.2 0.2
Internal Load Internal Load
Weather Dependent Load Weather Dependent Load
0.0 0.0
10°C 15°C 20°C 25°C 30°C 35°C 10°C 15°C 20°C 25°C 30°C 35°C
Outdoor Temperature Outdoor Temperature
ratio of 0.9 to 1. The length of this operating period depends if the energy savings are worth the increased capital and main-
on the number of steps of total cooling capacity. Figure 5 tenance costs for multiple chillers of different sizes.
shows that at least 10 steps of total cooling capacity could
enable chillers to operate near full load for more than 50% of Acknowledgments
total operating hours. With 26 steps, this percentage of total The work described in this paper was supported by a grant
operating hours increased to 72.8%, and the weather-load pro- from the Research Grants Council of the Hong Kong SAR,
file of the chillers indicated that there was a wide range of China (Project No. PolyU 5018/00E) and the central research
outdoor temperatures when the chillers were operating near grant of the Hong Kong Polytechnic University.
full load.
Considering that very few chiller load data correspond to References
the condition given by ARI Standard 590, it is inadequate to 1. Chan, K.T. and F.W. Yu. 2002. “Part load efficiency of air-cooled
use the ARI part-load condition (IPLV or NPLV) alone to multiple-chiller plant.” Building Services Engineering Research &
describe the operating conditions of chillers and to specify Technology 23(1):29–39.
chiller efficiency. Chillers generally operate at part load with 2. Solar Energy Laboratory. 2000. TRNSYS: A transient system simu-
lation program (reference manual). Madison, Wis.: University of
various outdoor temperatures.6
Wisconsin-Madison Press.
When the number of steps of total cooling capacity increases 3. Chan, K.T. and F.W. Yu. 2004. “Optimum set point of condens-
from six to 26, the annual electricity consumption of chillers ing temperature for air-cooled chillers.” International Journal of
could be reduced by 9.2%. The benefits of energy savings HVAC&R Research 10(2):113–127.
can be larger if chillers use primary pumping energy. Un- 4. Air-conditioning and Refrigeration Institute. 1998. ARI Standard
equally sized chillers can be put into effect to enable them to 550/590, Water chilling packages using the vapor compression cycle.
5. 2001 ASHRAE Handbook—Fundamentals (SI ed.), chap. 24.
operate with high efficiencies and to lower overall electricity 6. Landman, W.J. 1996. “Off-design chiller performance.” Trane
consumption. It remains to be seen how overall engineering Engineers Newsletter, 25(5). www.trane.com/commercial/library/
economics (i.e., life-cycle cost analysis) can help determine vol255/25-05pdf.pdf.