NON metallic
cable enclosures & fittings
technical data
clipsal.com
NON METALLIC CABLE EN
x
NON metallic
cable enclosures & fittings
15 YEAR PRODUCT
WARRANTY
To protect the customer's best
interests, Clipsal has extended its
product warranty to a full 15 years.
NON METALLIC
CONDUIT AND
FITTINGS
Manufacturing Bending Recommendations
Specifications Installation Conduit Minimum
All Clipsal Rigid Non Metallic When installing rigid Non Outside Diameter Radius
NON METALLIC CONDUIT AND FITTINGS
Conduit and Fittings are manufac- Metallic Conduit, support saddles or 16mm 96mm
tured in strict accordance with clips should be located at intervals 20mm 120mm
relevant sections of AS/NZS 2053 of not more than one metre. 25mm 150mm
Conduit and Fittings for For more information regarding 32mm 200mm
Electrical Installations. these points see relevant sections 40mm 240mm
Operative temperature range of AS/NZS 3000. 50mm 300mm
-15°C to +65°C. It is not recommended to use 63mm 380mm
Most Clipsal Conduit Fittings are Rigid Non Metallic Conduit and
suitable for use underground and Fittings where they are likely to be
are marked HD (Heavy Duty). subjected to severe mechanical
Note: Screw threads of nominal abuse without providing additional Jointing - Recommended
sizes of conduit 16 to 63mm are protection. Method
metric conduit threads with a 1.5mm
pitch, complying with AS 1721. The following is a simple, quick
Bending Conduit method using Clipsal Jointing
Sizes 80 to 150 are BSP threads
complying with AS 1722. Circular conduit not exceeding Cement.
Unless specified otherwise all 25mm in diameter can be bent ‘cold’ 1 Cut conduit to length and
dimensions are nominal. using the appropriate Clipsal remove all burrs.
Bending Spring (Cat. No. 266 2 Remove any dirt or grease
Series). Please refer to page 9. with a clean cloth dipped in
Chemical Resistance
Where heat is required on small methylated spirits.
Resistance to most common conduit, the area to be bent may be 3 Coat both surfaces to be
corroding agents, including the heated by brisk rubbing. On larger joined and within one minute
majority of oils and fats, inorganic conduit, heat can be supplied by push together. Give a quarter
acids, alkalis and salts, is a feature careful application of an L.P.G. turn to spread cement evenly
of Clipsal Rigid Non Metallic gas flame. and wipe off excess
Conduit and Fittings. However, they When bending Non Metallic immediately.
are not recommended for use with conduit, a minimum radius six times 4 Do not handle joint for five
Ketones, Esters or Aromatic or the conduit diameter is recommended. minutes and allow 24 hours
Chlorinated Hydrocarbons. To maintain a good bend and to drying time before testing
reduce ‘creep’, it is necessary to or rough handling.
Effects of Temperature over bend, then allow the tube to
ease to the desired position. Please refer to page 8 for
Rigid Non Metallic Conduit has Fix conduit with saddles, or complete details on Clipsal
a relatively high co-efficient of other supports, as soon as possible Jointing Cement.
expansion (approximately 0.1 metre after bending.
per 100 metres per 10°C). In long
runs likely to be subjected to wide
temperature variations, expansion
couplings should be provided in
each standard length.
4
RIGID NON
METALLIC CONDUIT
Light Duty Oval Rigid Non Metallic Conduit - Light Duty Oval
Light Duty Oval Conduit prod- Catalogue Width Height Wall Thickness
ucts offer a range of low profile Number (A) (B) (C)
conduit specifically for use in
chased walls. The low profile allows 9016LOV 20mm 12mm 1.2mm
a minimum depth chase to be made 9020LOV 24mm 14mm 1.2mm
yet still allows adequate space and
protection for the cables. Available Rigid Non Metallic Conduit - Medium Duty
Oval Conduit
MD & HD Conduit
5
TELECOMMUNICATIONS
CONDUIT
SECURITY CONDUIT