Professional Documents
Culture Documents
41 - 178s SOQ
41 - 178s SOQ
Descriptive Bulletin
Power Automation & Protection Division 41-178S
Coral Springs, FL
Allentown, PA Page 1
APPLICATION chine being monitored. This feature can be 40. The relay has per unit adjustment allow-
set from 0.03 to 0.20 per unit. ing it to be related to the full load current of
The SOQ negative sequence time the machine. The I2 trip pickup can be inde-
overcurrent relay is used to protect rotating The relay is also equipped with the provision pendently adjusted from 0.1 to 1.0 per unit,
machinery against excessive heating dam- for remote indication of per unit I2 level flow- thus allowing time delayed tripping to occur
age because of prolonged current unbalance. ing in the machine. Using this option an op- at any I2_ level above this point.
erator can estimate the severity of the un-
The relay is suitable for use with directly or balanced loading and take appropriate ac- The exponential resetting action of the SOQ
indirectly-cooled turbine generators, syn- tion. relay's timer has been made compatible with
chronous condensers, or any rotating ma- that of air-cooled and hydrogen turbine gen-
chinery having a known I2_2t limit. Settings of the SOQ relay are compatible with erators.
ANSI standard requirements for I2_2t limits
An alarm feature in the SOQ relay alerts an for generators, covering the range from 2 to
operator to an abnormal I_2 level in the ma-
Rotating Machine
April, 1998
Descriptive Bulletin
41-178S
Page 3
CONSTRUCTION
Current
Selection
Timer On
Indicator
Pick-up Trip
Adjustment Indicator
Alarm
K-Setting Indicator
Timer Reset T2
T1
Input
ICS Transformer
Trip Unit
Printed Circuit Boards - slide into position utilized to reset the timer and its associate trip circuit. Also during this operation two fin-
and engage into a terminal block at the rear LED. This function is used primarily for rou- gers on the armature deflect a spring located
of the relay. The boards and terminal blocks tine relay testing. on the front of the switch, which allows the
are notched preventing insertion into the operation indicator target to drop. The front
wrong position. Each board may be removed Output Contacts - A telephone type relay is spring, in addition to holding the target, pro-
and used in conjunction with an extender provided with two Type A contacts. One of vides restraint for the armature and thus con-
board (Style No. 644B315G02) permitting the normally open contacts is used with the trols the pickup value of the switch.
access to test points and terminals while the target seal in unit when tripping. There are
relay is energized. also two normally open contact (N.O.C.) reed Remote Readout Instrument (Optional)-
(A) Input Board relays, one mounted on the Power Supply may be provided to allow monitoring the
(B) Timer Board Board and the other on the Control Board, negative sequence current (I2) level at a re-
(C) Control Board sued for the alarm and oscillograph start mote location. The instrument provided is a
(D) Power Supply Board function respectively. Weshler switchboard type KX-241 (4 1/ 2",
250° scale, 1% accuracy). It is a 1 mA dc
Panel & Dial Plate - contains the ten-turn Indicating Contactor Switch - The dc indi- instrument marked to represent 0.2 per unit
potentiometer used for the K-setting and the cating contactor switch is a small clapper at full scale.
single-turn potentiometer to set the trip type device. A magnetic armature, to which
pickup level. The panel also contains three leaf-spring mounted contacts are attached,
(3) light-emitting diodes for timer-on, trip and is attracted to the magnetic core upon
alarm condition indication. A pushbutton is energization of the switch. When the switch
closes the moving contacts, completing the
April, 1998
Descriptive Bulletin
41-178S
Page 4
April, 1998
Descriptive Bulletin
41-178S
Page 5
Component Description
T1 TRANSFORMER
T2 TRANSFORMER
R1 RESISTOR (500 40W)
P1 POT (10K)
P2 POT (10K)
LED RED
PB PUSH BUTTON
SOQ TELEPHONE RELAY
ICS ICS (0.2 -2.0 A)
METER METER (IMA)
April, 1998
Descriptive Bulletin
41-178S
Page 6
Settings
B) K-Setting-chosen to correspond to
the I 2 2t limit for the particular machine
being protected. These are typically:
C) Trip-pickup level- should the lowest I 2 Type of Machine Permissible Two conservative values are available
level at which tripping will be permitted. I 2 (%) and may be chose by a "link" on the
A2 reasonable level to consider would Timer Board.
Salient Pole
be that level of sustained I 2 to produce
with connected The cooling time constant for hydrogen-
tripping at 250 seconds.
amortisseir windings..........10 cooled turbine generators is typically
k with nonconnected less than 40 seconds, for air-cooled
This would be For example
250 amortisseir windings..........5 machines it is typically less than 80
if K were 10 for the protected machine, Cylindrical Rotor seconds.
the level would be adjusted for Indirectly cooled.................10
Directly cooled By leaving the link "in" a time constant of
10 0 to 960 MVA................. 8 38 seconds is applied. With the link "out",
I2 = = 0.2 per unit.
250 961 to 1200 MVA........... 6 a constant of 80 seconds is chosen.
1201 to 1500 MVA.........5
D) Alarm Level- should be set at the In the absence of specific information,
lowest level consistent with normal load For a machine with a continuous I 2 capability the link should be removed, suing the
unbalance but in no case greater than of 10%, a reasonable alarm level setting is 80 second time constant. Where the
the maximum continuous I 2 level for the 0.05 (that is, 5%). actual cooling time constant is known,
machine. Typical values for generators the lowest value that is higher than the
are: E) Timer- within the SOQ has an inverse machine time constant should be
resetting characteristic similar to that of selected.
typical generators to allow for any
Remove the link where reclosing is not
cumulative effects which may, for
applied.
example, take place during reclosing.
April, 1998
Descriptive Bulletin
41-178S
Page 7
Fig. 5. Reset Time Curve for Time Constant 80 Seconds Fig. 6. Reset Time Curve for Time Constant 38 Seconds
➂ ICS Indicating contactor Switch (dc current operated) Rating of ICS unit used in specific types of relays is shown
having seal-in contacts and indicating target which are in price tables. All other ratings must be negotiated.
actuated when the ICS coil is energized at or above
When ac current is necessary in a control trip circuit, the
pickup current setting. Suitable for dc control voltages up
ICS unit can be replaced by an ACS unit.
to and including 250 volts dc. Two current ranges
available: The ACS unit may be supplied in place of an ICS unit at
(1) 0.2/2.0 amps dc, with tapped coil no additional cost. Specify system voltage rating on order.
(2) 1.0 amp dc, without taps
➃ Includes remote monitor negative sequence current type
KX241.
April, 1998
Descriptive Bulletin
41-178S
Page 8
ABB Power T&D Company Inc. ABB Power T&D Company Inc.
Power Automation and Protection Division Power Automation and Protection Division
4300 Coral Ridge Drive
Coral Springs, FL 33065
❖ 7036 N. Snowdrift Road, Suite 2
Allentown, PA 18106
800 523-2620 800 634-6005
April, 1998