Transformer Fault Gas Analysis

Results
Sample
Equipment ID: 0003 Serial Number: X
Apparatus Type: TRN Sampling Point: Samp Pt 1
Designation: X Syringe ID: 1
Sampled By: Operator B Date Sampled: 2022/01/05
Oil Temperature: 1 °C Tank Pressure: 1 psig
Comment: Oil type: ASTM D3612

Analysis Files Measurement Results


Method: 20220105 Daily Method.prm H2 (Hydrogen) 9 ppm
Calgas: 20220105191622 Calibration.prs CH4 (Methane) 0 ppm
Air: 20220105100224 Air.prs CO (Carbon Monoxide) 87 ppm
Oil: 20220105193612 Oil.prs CO2 (Carbon Dioxide) 3400 ppm
Calgas O2N2: 20220105191622 Calibration.prs C2H4 (Ethylene) 1 ppm
Air O2N2: 20220105100224 Air.prs C2H6 (Ethane) 0 ppm
Oil O2N2: C2H2 (Acetylene) 4 ppm
O2 (Oxygen) - ppm
Analysis Identification
Analyzed By: Operator A N2 (Nitrogen) - ppm
Date Acquired: 2022/01/05 TDG: - %
Instrument ID: 11201003 TDCG: 0.01 %
Version: PPMreport 3.7.0 THCG (O2N2): - %
THCG (Pressure): 0.08 %

Graphs

www.morganschaffer.com Printed on 2022/01/05 19:37:08