FTHF-V Series
EDTVN042127
Split Type
Air Conditioners
FTHF-V Series
FTHF25VAVMV RHF25VAVMV
FTHF35VAVMV RHF35VAVMV
Heat Pump FTHF50VVMV RHF50VVMV
FTHF60VVMV RHF60VVMV
FTHF71VVMV RHF71VVMV
1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTHF25VAVMV RHF25VAVMV
FTHF35VAVMV RHF35VAVMV
1 phase, 220 - 230 - 240 V, 50 Hz
FTHF50VVMV RHF50VVMV 1 phase, 220 - 230 V, 60 Hz
FTHF60VVMV RHF60VVMV
FTHF71VVMV RHF71VVMV
2. Functions
FTHF50/60/71VVMV
FTHF50/60/71VVMV
RHF50/60/71VVMV
RHF50/60/71VVMV
FTHF25/35VAVMV
FTHF25/35VAVMV
RHF25/35VAVMV
RHF25/35VAVMV
Category Functions Category Functions
Basic Functions Inverter (with inverter power control) Health & Deodorizing filter (enzyme blue)
Cleanliness
Operation limit for cooling Refer to Titanium apatite deodorizing filter
Operation limit for heating P. 22 (option)
PAM control — Dust collection filter (PM2.5) (option)
Standby electricity saving Mould proof air filter (prefilter)
Compressor Oval scroll compressor — — Wipe-clean panel
Swing compressor Washable panel — —
Rotary compressor — — Removable drain-pan
Reluctance DC motor Mould proof operation
Comfortable Power-airflow flap — Heating dry operation — —
Airflow
Power-airflow dual flaps — Good-sleep cooling operation — —
Wide-angle louvres Odour removing
Auto-swing (up and down) Timer Weekly timer — —
Auto-swing (left and right) — — 24-hour ON/OFF timer — —
3D airflow — — Count up-down ON/OFF timer
Comfort airflow mode Night set mode
(COANDA panel)
Worry Free Auto-restart after power failure
(Reliability &
Comfort Control Auto fan speed Durability) Self-diagnosis with remo-con
Indoor unit quiet operation Wiring error check — —
Outdoor unit quiet operation Anti-corrosion treatment of outdoor
Intelligent eye (auto energy saving) heat exchanger fins
3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTHF25VAVMV FTHF35VAVMV
Model RHF25VAVMV RHF35VAVMV
Outdoor Unit
Cooling Heating Cooling Heating
kW 2.5 (1.0 ~ 3.4) / 1.25 2.5 (1.0 ~ 3.4) / — 3.5 (1.2 ~ 3.8) / 1.75 3.5 (1.2 ~ 3.8) / —
8,500 (3,400 ~ 11,600) / 11,900 (4,100 ~ 13,000) /
Capacity Btu/h 8,500 (3,400 ~ 11,600) / — 11,900 (4,100 ~ 13,000) / —
4,300 6,000
Rated (Min. ~ Max.) / Half
3,010 (1,030 ~ 3,270) /
kcal/h 2,150 (860 ~ 2,920) / 1,070 2,150 (860 ~ 2,920) / — 3,010 (1,030 ~ 3,270) / —
1,500
Moisture Removal L/h 1.0 — 1.5 —
Running Current (Rated) A 2.9 2.8 4.6 4.6
Power Consumption W 555 (160 ~ 950) / 227 555 (160 ~ 980) / — 980 (160 ~1,070) / 360 980 (160 ~ 1,070) / —
Rated (Min. ~ Max.) / Half
Power Factor (Rated) % 87.0 90.1 96.8 96.8
COP (Rated) W/W 4.50 4.50 3.57 3.57
kWh/
CSPF 6.30 — 5.50 —
kWh
Liquid mm 6.4 6.4
Piping
Gas mm 9.5 9.5
Connections
Drain mm 16.0 16.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15 15
Max. Interunit Height Difference m 12 12
Chargeless m 10 10
Amount of Additional Charge of
g/m 20 20
Refrigerant
Indoor Unit FTHF25VAVMV FTHF35VAVMV
Front Panel Colour (Munsell No.) White (N9.5) White (N9.5)
H 9.9 (349) 10.4 (367) 11.5 (406) 12.1 (427)
M m³/min 7.5 (265) 8.9 (314) 7.5 (265) 8.9 (314)
Airflow Rate
L (cfm) 6.5 (228) 7.5 (265) 6.5 (228) 7.5 (265)
SL 5.4 (191) 6.7 (237) 5.4 (191) 6.7 (237)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 27 27
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof
Running Current (Rated) A 0.22 0.22 0.25 0.25
Power Consumption (Rated) W 14 14 21 21
Power Factor (Rated) % 28.9 28.9 38.2 38.2
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 285 × 770 × 242 285 × 770 × 242
Packaged Dimensions (H × W × D) mm 339 × 830 × 360 339 × 830 × 360
Weight (Mass) kg 9 9
Gross Weight (Gross Mass) kg 12 12
Sound Pressure H / M / L / SL
dB(A) 40 / 35 / 29 / 25 40 / 35 / 30 / 27 41 / 36 / 30 / 26 41 / 36 / 31 / 28
Level
Outdoor Unit RHF25VAVMV RHF35VAVMV
Casing Colour Ivory White Ivory White
Heat Exchanger Fin / Spec. Tube Waffle Fin / 7 Hi-XD Tube Waffle Fin / 7 Hi-XD Tube
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC20HXD 1YC20HXD
Motor Output W 650 650
Type FW50DA FW50DA
Refrigerant Oil
Charge L 0.275 0.275
Type R-32 R-32
Refrigerant
Charge kg 0.70 0.70
H m³/min 27.3 (964) 26.5 (936) 27.3 (964) 26.5 (936)
Airflow Rate
L (cfm) 23.4 (826) 22.3 (787) 23.4 (826) 22.3 (787)
Type Propeller Propeller
Fan
Motor Output W 28 28
Running Current (Rated) A 2.70 2.60 4.40 4.40
Power Consumption (Rated) W 541 541 959 959
Power Factor (Rated) % 91.1 94.6 99.1 99.1
Starting Current A 2.9 4.6
Dimensions (H × W × D) mm 550 × 675 × 284 550 × 675 × 284
Packaged Dimensions (H × W × D) mm 615 × 798 × 373 615 × 798 × 373
Weight (Mass) kg 26 26
Gross Weight (Gross Mass) kg 30 30
Sound Pressure H / SL
dB(A) 48 / 44 48 / 44 48 / 45 48 / 45
Level
Drawing No. 3D133306 3D133307
Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Heating Piping Length kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB / 15°CWB Btu/h = kW × 3412
7.5 m
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Heating Piping Length kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB / 15°CWB Btu/h = kW × 3412
7.5 m
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Heating Piping Length kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB / 15°CWB Btu/h = kW × 3412
7.5 m
Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB cfm = m³/min × 35.3
4. Dimensions
4.1 Indoor Unit
FTHF25/35VAVMV
3D131883
FTHF50/60/71VVMV
3D131945
RHF25/35VAVMV
C: 3D132040
RHF50/60/71VVMV
C: 3D098640G
5. Wiring Diagrams
5.1 Indoor Unit
FTHF25/35VAVMV
3D121600
FTHF50/60/71VVMV
3D121823
RHF25/35VAVMV
3D130783
RHF50/60VVMV
3D098689A
RHF71VVMV
3D130799
6. Piping Diagrams
6.1 Indoor Unit
FTHF25/35VAVMV FTHF50/60VVMV
4D130819 4D100132B
FTHF71VVMV
4D100147A
RHF25/35VAVMV
3D130779
RHF50/60VVMV
3D099372D
RHF71VVMV
3D102968B
7. Capacity Tables
7.1 Heat Pump
FTHF25VAVMV + RHF25VAVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 9.9
BF 0.08
Heating
AFR 10.4
OUTDOOR TEMPERATURE
INDOOR (°CDB/°CWB)
EDB 2/1 7/6 11/10
°C TC PI TC PI TC PI
15.0 3.42 1.63 2.59 0.54 2.81 0.56
20.0 3.29 1.67 2.50 0.56 2.73 0.57
22.0 3.24 1.68 2.47 0.56 2.69 0.58
24.0 3.19 1.70 2.43 0.57 2.66 0.58
25.0 3.16 1.71 2.41 0.57 2.64 0.59
27.0 3.11 1.72 2.38 0.57 2.61 0.59
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133319
FTHF35VAVMV + RHF35VAVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 11.5
BF 0.08
Heating
AFR 12.1
OUTDOOR TEMPERATURE
INDOOR (°CDB/°CWB)
EDB 2/1 7/6 11/10
°C TC PI TC PI TC PI
15.0 3.42 1.63 3.62 0.96 3.94 0.99
20.0 3.29 1.67 3.50 0.98 3.82 1.01
22.0 3.24 1.68 3.45 0.99 3.77 1.02
24.0 3.19 1.70 3.40 1.00 3.72 1.03
25.0 3.16 1.71 3.38 1.00 3.70 1.03
27.0 3.11 1.72 3.33 1.01 3.65 1.04
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133320
FTHF50VVMV + RHF50VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 17.1
BF 0.07
Heating
AFR 18.0
OUTDOOR TEMPERATURE
INDOOR (°CDB/°CWB)
EDB 2/1 7/6 11/10
°C TC PI TC PI TC PI
15.0 3.42 1.63 5.17 1.29 5.62 1.33
20.0 3.29 1.67 5.00 1.32 5.45 1.36
22.0 3.24 1.68 4.93 1.33 5.38 1.37
24.0 3.19 1.70 4.86 1.34 5.31 1.38
25.0 3.16 1.71 4.83 1.34 5.28 1.39
27.0 3.11 1.72 4.76 1.36 5.21 1.40
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133321
FTHF60VVMV + RHF60VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 17.1
BF 0.07
Heating
AFR 18.0
OUTDOOR TEMPERATURE
INDOOR (°CDB/°CWB)
EDB 2/1 7/6 11/10
°C TC PI TC PI TC PI
15.0 3.42 1.63 6.21 1.70 6.75 1.76
20.0 3.29 1.67 6.00 1.74 6.54 1.80
22.0 3.24 1.68 5.92 1.76 6.46 1.81
24.0 3.19 1.70 5.83 1.77 6.38 1.83
25.0 3.16 1.71 5.79 1.78 6.33 1.84
27.0 3.11 1.72 5.71 1.79 6.25 1.85
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133322
FTHF71VVMV + RHF71VVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 18.7
BF 0.07
Heating
AFR 19.7
OUTDOOR TEMPERATURE
INDOOR (°CDB/°CWB)
EDB 2/1 7/6 11/10
°C TC PI TC PI TC PI
15.0 3.42 1.63 7.35 2.32 7.99 2.39
20.0 3.29 1.67 7.10 2.37 7.74 2.45
22.0 3.24 1.68 7.00 2.39 7.64 2.47
24.0 3.19 1.70 6.90 2.41 7.55 2.49
25.0 3.16 1.71 6.85 2.42 7.50 2.50
27.0 3.11 1.72 6.76 2.44 7.40 2.52
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D133323
90
Range of the
refrigerant
80 additional
charge
5 10 15 (m)
Piping length
7.2.2 50/60 Class
(R-32)
(%)
100
Capacity correction factor
90
80
Range of the refrigerant additional charge
5 10 15 20 25 30 (m)
Piping length
7.2.3 71 Class
(R-32)
(%)
100
Capacity correction factor
90
80
Range of the refrigerant additional charge
5 10 15 20 25 30 (m)
Piping length
Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.
8. Operation Limit
RHF25/35VAVMV, RHF50/60/71VVMV
3D132983
9. Sound Level
9.1 Measuring Location
1m 1m
0.8 m
MICROPHONE
MICROPHONE
FTHF25VAVMV
3D133311
FTHF35VAVMV
3D133312
FTHF50VVMV
3D133313
FTHF60VVMV
3D133314
FTHF71VVMV
3D133315
RHF25VAVMV
3D133317
RHF35VAVMV
3D133318
RHF50VVMV
3D100686A
RHF60VVMV
3D100687A
RHF71VVMV
3D102902B
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB.
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)
3D133316
3P536679-2A
3P536679-3A
EN_3P512730-5D
EN_3P512730-6D
12.2 Vietnamese
12.2.1 25/35 Class
VN_3P512730-5D
VN_3P512730-6D
Manual No.
Option Name 25/35 Class 50/60/71 Class
Installation Manual Operation Manual
1 Wireless LAN connecting adaptor BRP072C42 1 BRP072C42 2 4P518835-2G —
BRP067A42 — 1P518834-1 —
2 Remote control PC-board set
— BRP980B42 1P518836-1 —
Wiring adaptor for timer clock / remote controller 4
3 (normal open pulse contact / normal open contact)
KRP413BB1S 1 KRP413BB1S 2 3P248024-2H —
Notes: 1 Remote control PC-board set (BRP067A42) is also required for each indoor unit.
2 Remote control PC-board set (BRP980B42) is also required for each indoor unit.
3 Standard accessory
4 Timer clock and other devices ; obtained locally.
5 An interface adaptor (KRP928BB2S) is also required for each indoor unit.
Manual No.
Option Name Model Name
Installation Manual Operation Manual
1 Air direction adjustment grille KPW937F4 3P561128-1 —
2 Drain plug KKP937A4 — —
Specifications, designs and other content appearing in this brochure are current as of February 2021 but subject to change without notice.