You are on page 1of 12

UNDERGROUND/SUBMARINE CABLE

PROTECTION USING A NEGATIVE-


SEQUENCE DIRECTIONAL
COMPARISON SCHEME
Jesús Vargas Armando Guzmán Jorge Robles
INELAP-PQE. Schweitzer Engineering Laboratories Comision Federal de Electricidad
Guadalajara, Jal. Mexico Pullman, WA USA Mexico, D.F. Mexico

Abstract—Protective relaying requirements for underground and submarine Power cables require protection for overload and short-
cables are different from those for overhead lines. This paper analyzes the circuit current conditions. Power cable protection
application of directional comparison schemes to protect two 34.5 kV applications must consider different cable impedance
submarine cables. These cables are 24-km long and connect Cozumel characteristics and configurations.
Island to Mexico’s mainland network. The paper discusses cable modeling
using symmetrical components and analyzes the performance of a negative- A. Cable Types [2]
sequence directional element during cable fault conditions.
1) Pipe–Type: This cable consists of three conductor-
I. INTRODUCTION shielded cables, each with a copper conductor, impregnated
paper-wrapped insulation, semiconductive tape, and skid
Traditionally, current-differential relays have protected wires. The cables are installed in a steel pipe, which is
cables in transmission and distribution applications. These coated on the outside to prevent corrosion.
applications also require directional overcurrent or distance
relays to provide protection when the communications 2) Self-Contained Fluid Filled (SCFF): These cables
channel is out-of-service. consist of three single-phase cables, each having a copper
conductor with a hollow core. The hollow core permits
This paper proposes an alternative solution for unbalanced fluid pressurization with a dielectric fluid at pressures of
fault protection. The solution is based on negative-sequence between 15 to 40 psi (pounds per square inch) or at a high
directional relays in a directional comparison scheme. This pressure of about 200 psi, depending on the application.
solution provides excellent fault resistance coverage and Cables are typically insulated with impregnated paper and
does not require additional backup protection. The paper have a lead or aluminum sheath to prevent the intrusion of
also analyzes the performance of the directional relay in moisture and to withstand fluid pressure.
cable applications when the cable admittance is not
negligible. 3) Solid Dielectric: These cables consist of either three
single-phase cables or three single conductors, each with its
own insulation installed in a common armor.
II. UNDERGROUND AND SUBMARINE
CABLE PROTECTION The cable is made of copper or aluminum conductors with
XLPE or Ethylene Propylene Rubber (EPR) insulation and a
Power cables are the most reliable means of connecting moisture-impervious outer sheath. XLPE cables, such as
different equipment in an electric system [1]. They can be the one shown in Fig. 1, are preferred for both transmission
used as transmission or distribution links. We expect more and distribution lines. Medium-voltage cables are protected
power cable applications in electric systems because of with an outer sheath of polyvinyl chloride (PVC) or XLPE.
advances in cross-linked polyethylene (XLPE) cable
technology, environmental restrictions, and right-of-way Moisturized atmosphere (water, salt, pollution, etc.) under
availability. high electrical stress causes the recognized water tree
phenomenon in insulation. Because this phenomenon
breaks down insulation in a relatively short operating
This frame provides a blank space 2 inches high in the period, high-voltage XLPE cables need metallic sheath
lower left hand corner of the first page (for use by IEEE moisture barriers under outer sheaths. Metallic sheaths can
Headquarters). be aluminum (Al), stainless steel, lead (Pb), Al-laminated
tape, or Pb-laminated tape.

1
Outer Insulation Insulation characteristics. Following are the main characteristics of the
Sheath Screen Conductor
Screen
current differential scheme:
• It does not provide backup protection.
Conductor
• Its availability depends upon communications channel
performance.
• It only requires current signals.
• It needs a communications channel with adequate
bandwidth to transmit and receive current
information.
Metallic
Sheath 6094: 001 • It requires minimum settings; the settings must
consider the effect of line charging currents.
Fig. 1: XLPE Cable Construction.
• The segregated-phase scheme has limited fault
resistance coverage.
B. Short-Circuit Current Protection of Cables
• It is immune to out-of-step conditions and current
A cable must be protected against overheating caused by reversals.
excessive short-circuit current flowing in its conductor. The
fault point may be on the cable itself or on any other part of • It requires special security logic for external fault
the electric system. conditions with current transformer (CT) saturation.
During a phase fault, the I2R losses in the phase conductor 5) Phase Comparison: This scheme compares the phase
raise the temperature of the conductor and then of the angle between the currents at both ends of the cable. One
insulation materials, screens, and surroundings. During a phase comparison approach uses a combined signal that
ground fault, the I2R losses in both the phase conductor and provides information for all fault types. In this scheme the
sheath elevate the temperature in a manner similar to that composed signal is passed through a squaring amplifier to
for phase faults. obtain a square wave signal that contains phase angle
information. The relay compares the local squared signal
During the flow of short-circuit current, the conductor against the remote squared signals; if the coincidence of the
temperature should not be permitted to rise to the point two signals is greater than a certain value, e.g., 90°, the
where it may damage the insulating materials. Cable scheme declares an internal fault condition.
protection during short-circuit conditions limits cable
damage, if the fault is in the cable, and/or limits the amount This scheme has been very popular in the past because it has
of heat transferred from the metallic conductors to the minimal communications channel requirements. Because
insulation and other materials. the current signals contain phase angle information, this
scheme is more secure than the current differential scheme
The high cost of power cables justifies the use of for external fault conditions with CT saturation. All other
communications-assisted schemes. In general, schemes for characteristics are the same as in the current differential
overhead line protection and underground cable protection scheme.
are the same. However, we must analyze and understand
the differences between the two applications to properly 6) Directional Comparison: Directional comparison
protect power cables. schemes use different types of measuring units (directional
elements, distance elements) at each end of the cable. These
The three basic pilot cable protection relay schemes are: measuring units determine the fault direction. This scheme
Current Differential, Phase Comparison, and Directional compares the fault direction information at each end of the
Comparison. cable to determine if there is a cable fault.
4) Current Differential: The current differential Frequently, these schemes use distance elements in power
protection scheme may consist of three segregated-phase cable applications. This approach must consider the
restraint differential elements or one restraint differential following facts:
element that combines information from the three phases.
These differential elements use operating and restraint • The power cable impedance is less than the overhead
quantities obtained from the local and remote-end currents. line impedance because the phase conductor spacing
The operating quantity is the magnitude of the vectorial sum in cables is less than the spacing in overhead lines.
of these currents. The restraint quantity is usually the scalar In some cases, the impedance may be less than the
sum of the same currents. The current differential relay uses minimum distance relay setting value.
the operating and restraint quantities to form a restraint-type • The cable zero-sequence impedance angle is less than
characteristic. The relay characteristic defines an internal the zero-sequence impedance angle for overhead
fault region. If the values of the operating and restraint lines. The zero-sequence angle compensation
quantities lie inside the internal fault region, the relay requires a large setting range that accommodates all
declares a tripping condition. possible cable angles.
The differential scheme frequently is used for cable Directional elements that operate with sequence-component
protection because this scheme is less dependent on cable quantities provide another possibility for a directional

2
comparison scheme implementation. We will analyze the Fig. 2 shows a group of three single-conductor cables, one
application of a negative-sequence directional element for for each phase. The voltage drop due to the current flowing
power cable protection later in this paper. Following are the through the conductor is:
main characteristics of a directional comparison scheme:
• The measuring units provide main and backup V = I c ⋅ Zc − j⋅ I s ⋅ X m (1)
protection. The voltage drop along the sheath is zero with the sheath
• Loss of the communications channel only disables grounded:
directional comparison functions, but does not
disable directional protection functions for local and 0 = (rs + j ⋅ X s ) ⋅ I s − j ⋅ I c ⋅ X m (2)
remote backup.
where:
• It requires voltage and current signals in both ends of
the line. Zc = Conductor impedance (Ω)
• Permissive Overreaching Transfer Trip (POTT) rs = Sheath AC resistance (Ω)
schemes normally operate with Frequency Shift Xs = Self-reactance of the sheath (Ω)
Keying (FSK) communications channels.
Xm = Mutual reactance between the
• In the case of pipe-type cables or cables in magnetic conductor and the sheath (Ω)
conduit, zero-sequence impedance is not constant and
depends on the current flowing through the cable. Is = Sheath current (A)
• Charging current must be considered when setting the Ic = Conductor current (A)
phase elements, to avoid a relay misoperation.
Sheath reactance, Xs, and mutual reactance, Xm, are equal
• Negative-sequence component directional elements when the conductor is concentric within the sheath. Solving
provide excellent fault resistance coverage [3]. (2) for Is, and replacing Xm for Xs:
These elements do not need to be desensitized to the
effects of charging current. + j ⋅ Ic ⋅ X m
Is = (3)
rs + j ⋅ X m
III. CABLE CHARACTERISTICS
Cable characteristics are an important factor in evaluating Substitution of Is in (1) gives:
protective schemes for power cable applications.
Additionally, we need to calculate the positive-, negative-,  j ⋅ Ic ⋅ Xm 
and zero-sequence inductive impedances and capacitance V = I c ⋅ Z c − j ⋅   ⋅ X m (4)
admittances to determine scheme settings [4], [5], [6]. In  rs + j ⋅ X m 
three-conductor cable applications, we can neglect cable The conductor impedance, Zc, is equal to rc + jXc.
asymmetries, but we must consider these asymmetries when Substitution of the conductor resistance, rc, and the
applying sequence directional elements to protect single- conductor reactance, Xc, in (4) gives:
conductor cables [7]. Let us next focus our attention on
single-conductor cables.
 r ⋅Xm2   3 
V =  rc + 2s  + j⋅  X − X m  ⋅ I (5)
    c
A. Single-Conductor Cables c
rs + X m 2   rs 2 + X m 2 
Conductor
V = [(rc + rsh ) + j ⋅ (X c + X sh )] ⋅ I c
Is Zc = rc + jXc
ri (6)
ro Sheath
r s, Xs where rsh in (6) represents sheath losses caused by voltages
the conductor current induced in the sheath. These voltages
create sheath currents that increase the conductor resistance.
Xsh in (6) represents a reactance correction because of the
presence of sheath currents. It has a negative sign because
Ic the sheath current direction is opposite to the conductor
current direction.
Sab
1) Resistance Components: From (5), the ac resistance
of a single conductor in a group of three conductors is:
Sbc
rs ⋅ X m 2
Sca r = rc + (7)
rs 2 + X m 2
3
GMD = Sab Sbc Sca 6094: 002

Fig. 2: Group of Three Single-Conductor Cables.

3
The mutual reactance, Xm, for a single conductor is [7]: 2) Reactance Components: From (5) the reactance of a
single conductor in a group of three conductors is:
2 ⋅ GMD
X m = 0.002893 ⋅ f ⋅ log Ω / phase / km (8)
ro + ri Xm3
X = Xc − = X c + X sh (10)
where: rs + X m 2
2

f = System frequency (Hz) The conductor reactance, Xc, for a single conductor is [7]:
GMD = Geometric Mean Distance (m)
GMD
ro = Sheath outer radius (m) X c = 0.002893 ⋅ f ⋅ log Ω / phase / km (11)
GMR cond
ri = Sheath inner radius (m) where:
The sheath resistance is [6]: GMRcond = Geometric Mean Radius (m)
k The most important characteristics of the reactance
rs =
(ro + ri ) ⋅ (ro − ri ) (9) components are:
• The cable reactance, X, is smaller than the simple
where: conductor reactance, Xc, due to sheath mutual coupling.
k = Function (sheath material) • The closer the phase conductors are to each other, the
The most important characteristics of the resistance smaller the conductor reactance, Xc.
components are: • The cable reactance reduction, Xsh, depends on the
• Cable resistance is greater than the conductor mutual reactance, Xm, which is a function of GMD. Xsh
resistance itself. also depends on the sheath resistance, rs, which is a
function of the sheath geometry and material.
• Cable resistance depends on GMD.
• If the sheath is insulated, as in Option • in Fig. 3, or
• Cable resistance depends on the sheath geometry and discontinuous, as in Option ‚ in the same figure, the
material. sheath currents are negligible. In these cases X = Xc
because rsh has a large value.
• If the sheath is solidly bonded, as in Option ƒ in Fig.
3 [9], its resistance may be 50–90 percent of the
conductor resistance. Sheath insulation in one or two 3) Zero-Sequence Impedance: Cable sheaths commonly
places reduces resistance, but produces high sheath have connections to ground at several points. The way the
voltages that may increase electrolysis or present sheaths are connected and the connection resistance
hazardous conditions. The bonding method of cable determine the zero-sequence path impedance. Fig. 4 shows
shielding is also related to the cable current-carrying an equivalent circuit of the zero-sequence path.
capacity.
I0 Conductor Z 0s - Z 0m

Z 0c - Z 0m
I 0s
1 Z 0c
Induced Shield

Z 0m
Sheath I0 Z 0m
Voltage

Z 0s I0s I 0G
2
I0G
3
6094: 004

1 Single Point
Bonding NJ N J = Noninsulated Joint
Fig. 4: Zero-Sequence Return Currents and Equivalent Circuit.
Cross Bonding IJ I J = Insulated Joint
2
Let us determine the zero-sequence impedance, Z0, for three
zero-sequence current return possibilities:
1. Current return in the sheath only, I0s:

NJ NJ
Z 0 = Z 0c − Z 0m + Z 0s − Z 0m (12)
3 Solid Bonding

Z 0 = Z 0c + Z 0s − 2Z 0 m (13)
Current Carrying Capacity : I 1 > I 2 > I 3 6094: 003

2. Current return in the ground only, I0g:


Fig. 3: Bonding Method of Cable Shielding.
Z 0 = Z 0c − Z 0m + Z 0m = Z 0c (14)

4
3. Current return in sheath and ground in parallel, I0s
and I0g:

(Z 0s − Z 0 m ) ⋅ Z 0 m
Z 0 = Z 0c − Z 0m + (15) rdi
Z 0s
rdi
Z 0 m2
Z 0 = Z 0c − (16) rdo rdo
Z 0s
where:
Z0c = Zero-sequence conductor impedance (Ω) 6094: 005

Fig. 5: Capacitance of Shielded Conductors.


Z0s = Zero-sequence sheath impedance (Ω)
Z0m = Zero-sequence mutual impedance (Ω) The positive-, negative-, and zero-sequence shunt
capacitances for single conductors with metallic sheaths are
The most important characteristics of zero-sequence all equal. This is also true for three conductor-shielded
impedance are: cables having round conductors and their own shielding
layer. Fig. 5 shows the cross sections of a single-conductor
• The impedance depends on the method of bonding and and a three-conductor cable. Three conductor-belted cables
grounding the cable sheath. without conductor shielding have smaller zero-sequence
• Its angle may vary from small angles (return current in capacitance than positive- and negative-sequence
sheath only) to angles close to the cable Z0c angle capacitances.
(return current in ground only). The most important characteristics of the shunt capacitive
• The presence of parallel paths (cables, ground reactance are:
conductors) and the earth’s resistivity must be • For a single conductor with a metallic sheath, the
considered in determining the zero-sequence positive-, negative-, and zero-sequence capacitances are
impedance. the same as the capacitance of one of the conductors to
• In the case of magnetic ducts, zero-sequence impedance its sheath (C1 = C2 = C0).
varies with the zero-sequence current. • Cable capacitance depends mostly on single-conductor
Based on the characteristics listed above, zero-sequence geometry.
quantities are not suitable for cable protection. Similarly, • There is no relation between S (distance between single
this same reasoning reveals the difficulty in applying ground conductors) and the cable shunt capacitance.
distance protection to cables.
• As the dielectric strength of insulation increases (new
4) Shunt Capacitive Reactance: The capacitance, C, materials or process), cable capacitance increases while
between an insulated conductor within a concentric sheath the required thickness of insulation decreases.
and the sheath itself is [4]:
• The zero-sequence, x0, positive-sequence, x1, and
0.024127 ⋅ ε R negative-sequence, x2, shunt capacitance reactances are
C= µF / km equal to, 1/ω⋅C0, 1/ω⋅C1, and 1/ω⋅C2 respectively. C0,
r (17) C1, and C2 are the zero-, positive-, and negative-
log do
rdi sequence capacitances per unit length. Equation (18)
converts capacitance-per-kilometer to total ohms-per-
where: phase reactance, where λ is the length in kilometers:
εR = Relative permittivity of the insulation
material x C012 1
X C012 = = (18)
λ λ⋅ 2⋅ π⋅ f ⋅ C 012
rdo = Inside radius of the sheath or outside radius of
the insulation, if shielding tape is used (m)
rdi = Radius of the conductor (m) B. Submarine Cable

If the sheath is grounded, (17) gives the capacitance to Submarine cables are located at a considerable depth from
ground. surface level; thus the return current path consists not only
of sheath and ground but also of seawater.
The current distribution among paths varies inversely to the
path resistivities. Because seawater resistivity varies from
0.01 to 0.000025 times ground resistivity, practically all the
return current goes through seawater. For this reason, we
also need to consider seawater resistivity when calculating
the cable zero-sequence impedance.

5
C. Playa del Carmen – Chankanaab Cable Parameters Table 2: Cable Equivalent Sequence Impedances and Admittances

The power cable in our application connects Playa del Sequence Ω)


Impedance (Ω Admittance (S)
Carmen Substation (PCA) on the Yucatan Peninsula
mainland with Chankanaab II (CHS) Substation at Cozumel Zero Z0 = 13.39 ∠ 24° Y0 = 0.0019 ∠ 89.9°
Island. Connection is through two 34.5 kV circuits (CI1,
CI2). Each circuit consists of three single-phase conductors, Positive Z1 = 10.56 ∠ 54° Y1 = 0.0019 ∠ 89.9°
and each circuit has three sections. Table 1 lists the length Negative Z2 = 10.56 ∠ 54° Y2 = 0.0019 ∠ 89.9°
and type of each section. Appendix 1 includes cable
geometry and configuration.
IV. NEGATIVE SEQUENCE DIRECTIONAL ELEMENT
Table 1. Circuit Sections
A. Negative-Sequence Impedance Measurement
Section From To Length (m) Type
for Forward and Reverse Faults
Playa del Sea Shore at
We can measure the negative-sequence system impedance
Carmen Playa del
1 5,500 Underground using the negative-sequence voltage and current, V2 and I2,
Substation Carmen
at the relay location for a given system. We call this
(PCA)
impedance Z2Measured. Fig. 6 shows a two-source system and
Sea Shore Sea Shore at the negative-sequence network for ground faults.
at Playa Cozumel Island ES ER
2 18,000 Submarine S R
del ZS ZL ZR
Carmen
Z2
Sea Shore Chankanaab II Reverse Forward
Fault Fault
at (CHS)
3 500 Underground
Cozumel Substation
Island S R
Z S2 Z L2 Z R2

Calculate the cable sequence impedances by completing the I2


following steps: IS2 V2 IR2

1. Obtain cable impedance and admittance matrices


for each cable section.
2. Obtain per-phase PI equivalent circuits. 6094: 006

3. Calculate per-phase ABCD constant networks for Fig. 6: Negative-Sequence Impedance Measurement
each cable section [6]. for Forward and Reverse Faults.
4. Obtain the series equivalent of the three sections. Table 3 shows the negative-sequence impedance
5. Obtain the PI equivalent circuit of the three measurement for forward and reverse single-line-to-ground,
sections. SLG, faults.
6. Calculate sequence impedance and admittance Table 3: Negative-Sequence Impedance Measurement
from the phase impedance and admittance for Forward and Reverse Faults.
matrices, ZABC and YABC.
Condition V2 I2 Z2Measured
Equations (19) and (20) transform the phase matrices to
sequence matrices. SLG Forward Fault -IS2·ZS2 IS2 -Zs2

Z 012 = T −1 ⋅ Z ABC ⋅ T
SLG Reverse Fault -IR2·(ZR2+ZL2) -IR2 ZR2 +ZL2
(19)
where:
Y012 = T −1 ⋅ YABC ⋅ T (20)
ZS2 = Negative-sequence source impedance at S (Ω)
where: ZR2 = Negative-sequence source impedance at R (Ω)
T = Symmetrical Component Transformation [5]. ZL2 = Negative-sequence line impedance (Ω)
Table 2 shows the total cable sequence impedances and Schweitzer and Roberts [10] describe a negative-sequence
admittances that include the three cable sections. directional element that measures the negative-sequence
impedance, Z2, and compares the result against forward and
reverse thresholds to make a fault direction declaration. The
directional element uses (21) for Z2 measurement.

6
The impedance measurement differences between forward

Z2 =
[
Re V2 ⋅ (I 2 ⋅1∠θ)* ] (21)
and reverse faults at both cable ends are:
2
I2 Directional Element at S:
(22)
where: Z2 = ZL2 + ZR 2 − (− ZS2 ) = ZS2 + ZL 2 + ZR 2
Z2Measured = Measured negative-sequence
impedance (Ω) Directional Element at R:
(23)
∠θ = Negative-sequence line impedance Z2 = Z L 2 + Z S2 − (−Z R 2 ) = Z R 2 + Z L2 + Z S 2
angle (degrees)
We set Z2F = ZL2/2 and Z2R = Z2F + 0.1, at both ends of
The negative-sequence directional element declares a the cable; with these settings, the directional elements make
forward fault condition if Z2Measured is less than the forward the correct fault direction declaration without forward and
threshold, Z2F. The element declares a reverse fault reverse region overlap.
condition if Z2Measured is greater than the reverse threshold,
Z2R. Z2F must be less than Z2R to avoid any overlap Enable Z2F +
Forward Fault
between the forward and reverse regions. _

Z2Measured = -ZS2 for forward faults and Z2Measured = Z2L + Z2R


V2
for reverse faults. The impedance measurement difference Z2
for forward and reverse faults is: ZS2 + Z2L + Z2R. We need I2
to set the Z2F and Z2R thresholds between the forward and
reverse Z2 measurements. If we assume infinite sources, +
Reverse Fault
_
Z2L is the impedance measurement difference between Z2R
6094: 008
forward and reverse faults.
Fig. 8: Negative-Sequence Directional Element
ES ER
S R With Forward and Reverse Thresholds
ZS ZL ZR
for Fault Direction Declaration [12].

RX
67S TX 67R V. Z2 IMPEDANCE LOCUS IN CABLE APPLICATIONS
RX TX

TX = Transmitter; RX = Receiver 6094: 007


A. Negative-Sequence Impedance Locus Considering Cable
Admittance
Fig. 7: Negative-Sequence Directional Elements,
The line model in the previous section only included the line
67, at Both Cable Ends for Unbalanced Fault Protection.
series impedance, ZL. This model is appropriate for
We can implement a directional comparison scheme to overhead line applications where line admittance is
detect unbalanced cable faults with these directional negligible because its relative value is small compared to the
elements at both cable ends. Fig. 7 shows these directional series impedance of the line. This model is not valid for
elements, 67S and 67R, in a POTT scheme implemented cable applications, because of the following facts:
using relay-to-relay communications [11]. • As phase conductors get closer to each other, the line
Table 4 shows the negative-sequence impedance series impedance gets smaller.
measurement of both directional elements for single line-to- • As the distance between the phase conductor and the
ground, SLG, faults. sheath decreases, the cable capacitance increases. As
capacitance increases, shunt capacitive reactance
Table 4: Negative-Sequence Impedance Measurements at Both Cable Ends
decreases.
SLG Fault Z2Measurement at S Z2Measurement at R • Series impedance is proportional to cable length;
Location shunt capacitance reactance is inversely proportional
S ZL2 + ZR2 -ZR2
to cable length.

in-line -ZS2 -ZR2


Let us analyze the effect of adding the cable admittance to
the cable model in the directional element Z2 measurement.
R -ZS2 ZL2 + ZS2
Fig. 9 shows a negative-sequence network for a two-source
system with a cable interconnection. The cable model
includes shunt capacitive admittance at both cable ends.

7
ES
ZS
S
ZL
R
ZR
ER When the admittance is zero, the Z2 measurement is at point
B; this point corresponds to the simplified series impedance
Reverse
Z2

Forward
model case. As the admittance increases, the measurement
Fault Fault point moves upward to the right and the distance to the
origin increases. We will have a point between B and C for
S R different cable types.
Z S2 Z L2 Z R2

I2
To properly apply the negative-sequence directional
I S2 V2
YL2 YL2
IR2
element, the forward and reverse fault regions should not
2 2
overlap.

6094:009 B. Z2 Locus in Submarine Cable Applications


Fig. 11 shows the negative-sequence impedance locus for a
Fig. 9: Two-Source System With a Cable Interconnection. The Negative-
Sequence Network Includes the Cable Admittance. submarine cable that has the same characteristics and
configuration as the one in Section 2 of our application.
For a forward fault, V2 =-IS2 ⋅ ZS2 and I2 = IS2, then: The figure shows two traces for reverse SLG faults: one of
the traces corresponds to the impedance locus without
−I S2 ⋅ Z S2 (24) considering the cable capacitance in the line model; the
Z2 Measured Forward = = − Z S2 other one includes it. Each point in the graph corresponds
I S2
to a different cable length, 1, 2, 4, 8, 16, 32, 64, and 128 km.
For a reverse fault Z2Measured Reverse is expressed in terms of
the network elements as follows: We start to notice the cable capacitance effect on the
impedance locus for distances of 32 km and greater. The
Z2 Measured Re verse = angle of the negative-sequence impedance varies from 78º
to 39º. The first angle corresponds to 1 km and the second
4 ⋅ Z L 2 + 2 ⋅ YL 2 ⋅ Z L 2 ⋅ Z R 2 + 4 ⋅ Z R 2 (25) one to 128 km.
4 + 4 ⋅ YL 2 ⋅ Z R 2 + 2 ⋅ YL 2 ⋅ Z L 2 + YL 2 2 ⋅ Z L 2 ⋅ Z R 2
80
where:
70
YL2 = Negative-sequence cable admittance (S)
Fig. 10 shows the negative-sequence impedance locus in the 60 Capacitance
negative-sequence impedance plane for a reverse fault for Not Included
different YL2 values while all other impedances are constant. 50
X2
X2 (Ω)

40
Capacitance
Included
30

ZR2 + ZL2 C 20
B
10
Reverse Faults
0
R2 0 10 20 30 40 50 60 70 80
R2 (Ω)

Fig. 11: Negative-Sequence Impedance Locus for Reverse Faults in


A Submarine Cable Application.

-Z2 6094:010

Forward Faults
Fig. 10: Negative-Sequence Impedance Locus for Reverse
and Forward Faults in Cable Application.

8
VI. CONCLUSIONS [8] J. Lewis Blackburn, “Symmetrical Components for Power Systems
Engineering,” Marcel Dekker Inc., 1993.
1. Cable zero-sequence impedance depends on the current
return paths, while the negative-sequence impedance [9] Sumitomo Electric Industries, LTD, “Development of Optical Fibers
does not. For this reason, negative-sequence quantities Incorporated Single-Core Submarine Power Cable,” Sumitomo
are more suitable than zero-sequence quantities for Electrical Review, 1994.
cable protection. [10] E. O. Schweitzer III and J. Roberts, “Distance Relay Element
Design,” 19th Annual Western Protective Relay Conference, Spokane,
2. Negative-sequence directional elements, with the aid of WA, October 1992.
communications, provide reliable and sensitive cable
protection against unbalanced faults. [11] Behrendt, K. C. “Relay-to-Relay Digital Logic Communication for
Line Protection, Monitoring, and Control,” 23rd Annual Western
3. The cable negative-sequence admittance modifies the Protective Relay Conference, Spokane, WA, October 1996.
Z2 measurement for reverse faults. This admittance
must be included in the cable model to properly [12] Armando Guzmán, J. Roberts, and D. Hou, “New Ground Directional
determine the negative-sequence directional element Elements Operate Reliably for Changing System Conditions,” 23rd
relay setting. Annual Western Protective Relay Conference, Spokane, WA, October
1996.
4. The negative-sequence impedance measurement defines
forward and reverse regions in the negative-sequence VIII. BIOGRAPHIES
impedance plane that do not overlap.
Jesús Vargas received his BSEE with honors from Guadalajara
5. Distance elements require special setting ranges to Autonomous University (UAG), Mexico, in 1986. He served as a relay
properly compensate for the cable zero-sequence protection engineer from 1986 to 1996 at the Federal Electricity
impedance. Commission mainly dedicated to fault analysis, new technology evaluation,
and commissioning. In 1996 he joined INELAP as a director of the
VII. REFERENCES protective relaying division. INELAP provides design, consultant, and
support services in protective relaying, control, integration and automation
[1] IEEE Standards Board, “IEEE Recommended Practice for Protection
for both utility and industry. He has been a lecturer at UAG in power
and Coordination of Industrial and Commercial Power Systems,” the
system protection. He is a member of the IEEE and served as IEEE official
Institute of Electric and Electronics Engineers, Inc., 1986.
for the Guadalajara, Jal. Mexico section.
[2] Working Group D12 of the Line Protection Subcommittee, PSRC,
Armando Guzmán received his BSEE with honors from Guadalajara
“Protective Relaying Considerations for Transmission Lines with
Autonomous University (UAG), Mexico, in 1979. He received a diploma
High Voltage AC Cables,” IEEE Transactions on Power Delivery,
in fiber-optics engineering from Monterrey Institute of Technology and
Vol. 12, No. 1, January 1997.
Advanced Studies (ITESM), Mexico, in 1990. He served as regional
[3] Roberts, J., Schweitzer, E. O. III, Arora, R., and Poggi, E., “Limits to supervisor of the Protection Department in the Western Transmission
the Sensitivity of Ground Directional and Distance Protection,” 50th Region of the Federal Electricity Commission (the electrical utility
Annual Georgia Tech Protective Relaying Conference, Atlanta, GA, company of Mexico) for 13 years. He lectured at UAG in power system
May 1996. protection. Since 1993 he has been with Schweitzer Engineering
[4] E. Clarke, “Circuit Analysis of A-C Power Systems Volume II,” Laboratories, Pullman, Washington, where he is presently a research
General Electric Company, 1950. engineer. He is a member of IEEE and has authored and coauthored
several technical papers.
[5] C. F. Wagner and R. D. Evans, “Symmetrical Components,”
McGraw-Hill Book Company, Inc., 1933. Jorge Robles received his BSEE from the National Polytechnic Institute
(IPN), Mexico, in 1976. He joined the Federal Electricity Commission in
[6] Central Station Engineers, “Electrical Transmission and Distribution 1978 as a protective relaying engineer. Since 1988 he has been chief of the
Reference Book,” 4th Edition, Westinghouse Electric Corporation, Distribution Substations Office, in charge of the national distribution and
1964. subtransmission networks’ protective relaying systems. He is an IEEE
[7] J. Roberts and A. Guzmán, “Directional Element Design and member and a member of the protective relaying subcommittee of
Evaluation,” 21st Annual Western Protective Relay Conference, Mexico’s IEEE section and has authored and coauthored technical papers.
Spokane, WA, October 1994.

9
IX. APPENDIX 1: CABLE GEOMETRY AND CONFIGURATION

A. Cable Sections 1 and 3


Underground Cable Voltage: 34.5 kV Conductor Material: Copper Cu
Conductor Area: 400 mm2
Insulation: XLPE Section 1 Length: 5,500 m
Section 3 Length: 500 m
Ampacity: 566 A

Table 5: Cable Geometry and Material Characteristics of Sections 1 and 3

Section Material Thickness Resistivity Permeability Permittivity


(mm) Ω ⋅ m)
(Ω µR εR
1. Conductor Copper 23.5 1.72 x 10-8 1 -
2. Insulator 1 XLPE 10.25 - 1 2.35
3. Sheath Copper 0.2 1.72 x 10-8 1 -
4. Insulator 2 PVC 4 - 1 4.55

rc = 11.75 mm ∆1 = 10.25 mm
ri1 = 22 mm ∆2 = 0.2 mm
ri2 = 22.2 mm ∆3 = 4 mm
r0 = 26.2 mm

Cable Transverse Section Cable Configuration

4
3
2
1 rC 1 2 3
2.00 Meters
ri1
r0 ri2

Not to Scale 0.25 0.25 0.25 0.25 0.25 Meters

6094: 011

Figure 12: Cable Geometry and Configuration of Sections 1 and 3.999

10
B. Cable Section 2
Submarine Cable Voltage: 34.5 kV Conductor Material: Copper Cu
Conductor Area: 300 mm2
Insulation: XLPE Sheath: Lead
Length: 18,000 m Ampacity: 500 A
Table 6: Cable Geometry and Material Characteristics of Section 2

Section Material Thickness Resistivity Permeability Permittivity


(mm) V . m)
(V mR eR
1. Conductor Copper 21.6 1.72 x 10-8 1 -
2. Insulator 1 XLPE 9.56 - 1 2.35
3. Sheath Lead 2.20 20.10-8 1 -
4. Insulator 2 Polyethylene 9.1 - 1 2.35
5. Armor Steel 10.26 9.70 x 10-8 300 -
6. Insulator 3 PVC 3.6 - 1 4.55

Cable Transverse Section


Cable Configuration
6 Sea

5
r0 4
3
2
rC 1 2 3 4 5 1 rC
300.00 Meters
ri4 ri1

ri2
ri3

20 20 20 20 20 Meters
Not to Scale

Playa del
Carmen Cozumel

0 0
Deep
L = 17,800 Meters
Meters
100 100

200 200

300. 300.

L F = 17,918.93 Meters
400 400

500 500
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Kilometers 6094: 012

Figure 13: Cable Geometry and Configuration of Section 2.

11
rc = 10.8 mm ∆1 = 9.56 mm
ri1 = 20.36 mm ∆2 = 2.20 mm
ri2 = 22.56 mm ∆3 = 9.1 mm
ri3 = 31.66 mm ∆4 = 10.26 mm
ri4 = 41.92 mm ∆5 = 3.6 mm
r0 = 45.52 mm

Copyright © SEL 1999


(All rights reserved)
Printed in USA
991028

12

You might also like