High Impedance has more Stability than Low Impedance Relay. But,
CT switching / CT mismatch problems, which is not there in case of
low Impedance Relays.
The high impedance type differential protection is stable for all types of
faults outside the zone of protection. The stabilization is obtained by a
resistor in the differential circuit.
In SPAE 010 and SPAE 011 the stabilizing resistor is included in the
relay and is in series with the measuring transformer. This gives the
name of the protection system, i.e. a high impedance type protection.
What is the difference in the Interpretation of FRLS and Fire Resistant Cable?
Fire Resistant: - Low Oxygen index may allow having flames, but
will not allow cables to continue with FIRE. This is more Stringent,
used for Major Life Saving Electrically Driven Emergency Loads i.e.
EDG Sets, Fire Water Pumps, LUB –Oil Pumps, etc.
FRLS: - IEC-331 – It will retard the Flames, but may continue to be damaged under fire,
but low smokes – which can be suffocating to choke the operators.