PROJECT: LOREAL CATEGORY DESCRIPTION

REF: IEC 60079 A To be completed before operation


SUBJECT: Inspection Punch List Warehouse and Sampling Area B To be completed before documentation
UPDATED: 16th January, 2019
EQUIPMENT:
DOC No:

CATEGO RAISED DATE


No. DESCRIPTION AREA ITEM/TAG PICTURE
RY BY RAISED

WAREHOUSE / ALL LIGTHING WAWAN


1 Equipment and cable identification shall be installed B 18-Jan
SAMPLING FIXTURE (BVI)

WAREHOUSE / ALL LIGTHING WAWAN


2 Certified blanking element shall be installed for spare entry cable A 18-Jan
SAMPLING FIXTURE (BVI)

MCT (Roxtec) shall be install for cable penetration in order to protect from multiple hazards
WAREHOUSE / ALL LIGTHING WAWAN
3 including fire, water, gas, dust, vibrations, electro-magnetic disturbances, vermin, and the risk of A 18-Jan
SAMPLING FIXTURE (BVI)
explosion

WAREHOUSE / ALL LIGTHING WAWAN


4 Cable core connection shall be installed with ferrule ( Y type insulated) , sleeve and core name A 18-Jan
SAMPLING FIXTURE (BVI)

Page 1 of 5
PROJECT: LOREAL CATEGORY DESCRIPTION
REF: IEC 60079 A To be completed before operation
SUBJECT: Inspection Punch List Warehouse and Sampling Area B To be completed before documentation
UPDATED: 16th January, 2019
EQUIPMENT:
DOC No:

CATEGO RAISED DATE


No. DESCRIPTION AREA ITEM/TAG PICTURE
RY BY RAISED

Need correct
Equipment andcertificate to analise Special
cable identification shall beconditions
installed of use for ligthing installed are complied with WAREHOUSE / ALL LIGTHING WAWAN
5 A 18-Jan
( LCIE 06 ATEX 3045X the sign X is for special condition for safe use ) SAMPLING FIXTURE (BVI)

Wrong certificate number for Ex lighting fixture refer to actual certificate number installed LCIE 06 WAREHOUSE / ALL LIGTHING WAWAN
6 A 18-Jan
ATEX 3045X ( Available certicate LCIE 06 ATEX 6035X ) SAMPLING FIXTURE (BVI)

CENTRIFUGAL WAWAN
7 Motor installed found uncertify Explosion proof WAREHOUSE B 18-Jan
FAN (BVI)

CENTRIFUGAL WAWAN
8 Certified Gland and blanking element shall be installed WAREHOUSE A 18-Jan
FAN (BVI)

Page 2 of 5
PROJECT: LOREAL CATEGORY DESCRIPTION
REF: IEC 60079 A To be completed before operation
SUBJECT: Inspection Punch List Warehouse and Sampling Area B To be completed before documentation
UPDATED: 16th January, 2019
EQUIPMENT:
DOC No:

CATEGO RAISED DATE


No. DESCRIPTION AREA ITEM/TAG PICTURE
RY BY RAISED

Cable core and


Equipment connection shall be installed
cable identification shall with ferrule (Copper Ring Type Terminal End (Insulated)),
be installed CENTRIFUGAL WAWAN
9 WAREHOUSE A 18-Jan
sleeve and core name FAN (BVI)

CENTRIFUGAL WAWAN
10 Motor identification and cable identification shall be installed WAREHOUSE B 18-Jan
FAN (BVI)

CENTRIFUGAL WAWAN
11 Earthing bonding jumper shall be installed WAREHOUSE A 18-Jan
FAN (BVI)

CENTRIFUGAL WAWAN
12 Sealing of ducts is not satisfactory. WAREHOUSE A 18-Jan
FAN (BVI)

Page 3 of 5
PROJECT: LOREAL CATEGORY DESCRIPTION
REF: IEC 60079 A To be completed before operation
SUBJECT: Inspection Punch List Warehouse and Sampling Area B To be completed before documentation
UPDATED: 16th January, 2019
EQUIPMENT:
DOC No:

CATEGO RAISED DATE


No. DESCRIPTION AREA ITEM/TAG PICTURE
RY BY RAISED

Loose ground
Equipment andcable
cableconnection andshall
identification incomplete installation (tighten ground connection and ensure to
be installed WAWAN
13 WAREHOUSE - A 18-Jan
complete installation with serrated, flat and spring washer) (BVI)

CENTRIFUGAL WAWAN
14 Motor installed found uncertify Explosion proof SAMPLING A 18-Jan
FAN (BVI)

CENTRIFUGAL WAWAN
15 Cable gland installed found uncertify Explosion proof SAMPLING A 18-Jan
FAN (BVI)

Cable core connection shall be installed with ferrule (Copper Ring Type Terminal End (Insulated)), CENTRIFUGAL WAWAN
16 SAMPLING A 18-Jan
sleeve and core name FAN (BVI)

Page 4 of 5
PROJECT: LOREAL CATEGORY DESCRIPTION
REF: IEC 60079 A To be completed before operation
SUBJECT: Inspection Punch List Warehouse and Sampling Area B To be completed before documentation
UPDATED: 16th January, 2019
EQUIPMENT:
DOC No:

CATEGO RAISED DATE


No. DESCRIPTION AREA ITEM/TAG PICTURE
RY BY RAISED

Equipment and cable identification shall be shall


installed CENTRIFUGAL WAWAN
17 Motor identification and cable identification be installed SAMPLING B 18-Jan
FAN (BVI)

CENTRIFUGAL WAWAN
18 Cable not properly seal on penetration SAMPLING A 18-Jan
FAN (BVI)

Ground cable found loose on gland at wall penetration, Ground cable shall be properly sealed WAWAN
19 SAMPLING - A 18-Jan
(ensure to remove gland from wall penetration and use MCT (Roxtec) for cable penetration) (BVI)

Page 5 of 5