Professional Documents
Culture Documents
S11 Final 2021
S11 Final 2021
By
1. Bruktayt Dagne
2. Buze Assefa
3. Fantaye Ketemaw
4. Hana H/Mariam
5. Semira Dejene
6. Zinash Bedru
Supervised by
Mr. Mekuria M.
We certify that the project titled “Structural Analysis and Design of G+5 mixed-used
building using ES EN 2015” is our own work. The work has not been presented elsewhere
for assessment. Where material has been used from other sources it has been properly
acknowledged/referred.
i
ACKNOWLEDGMENTS
First of all, we would like to thank the almighty God for his unconditional love and his
protection in every aspect of our life.
We want also to give our deepest heartfelt gratitude to our Advisor Mr. Mekuria M.
Secondly it is our honor to thank all civil engineering department staff members who
encourage us.
Finally, we would like to express our heartfelt appreciation and gratitude to our parents
and friends for providing us with unfailing support and continuous encouragement
throughout our years of study and the process of our thesis.
ii
ABSTRACT
This project consists of the overall structural analysis and design procedures of G+5
mixed-use buildings based on ES EN 2015 (Ethiopian standard based on European
Norms). The structural design of this building involves the design of floor slabs, stairs,
beams, columns, foundation, and analysis of roof. The building has a flat roof slab system
and a one-way ribbed slab system for each floor. Live load and dead load analyses are
made according to ES EN 2015. After the minimum depth of slab for serviceability limit
state of deflection was determined, the slab was designed for different loads including self-
weight and live loads. Stairs and landings were designed as a one-way slab. Loads acting
on beams from slab reactions and walls directly resting on beams were added to the self-
weight of beams to find total load acting on beams. These were inserted and analyzed using
ETABS 2019.V19.6.2. To simplify the design procedure calculation is done using Excel
spreadsheets. Also, the size of the footing was determined from the bearing capacity of the
soil.
iii
TABLE OF CONTENTS
ACKNOWLEDGMENTS ............................................................................................... II
ABSTRACT.................................................................................................................... III
iv
3.2.1 Analysis of Girders ..................................................................................... 35
v
CHAPTER 9 CONCLUSIONS AND RECOMMENDATIONS .......................... 96
APPENDIX A .................................................................................................................. 99
vi
LIST OF TABLES
vii
LIST OF FIGURES
viii
List of Abbreviation and Symbols
ix
Structural analysis and design of G+5 mixed used building
CHAPTER 1 INTRODUCTION
1.1 General
A mixed-use building aims to combine three or more uses into one structure such as
residential, hotel, bank, shopping, and entertainment whatever the combination, it brings
together several uses within either one building or a small area. This project is dedicated
to the structural analysis and design of a G+5 mixed-used building that includes a cafeteria,
bank, shop, and is located at Haramaya.
The structure is executed in such a way that the building will remain fit with appropriate
degrees of reliability and in an economic way. It should sustain all the actions and
influences during execution and use. Therefore, the structural design focuses on structural
safety and serviceability with due durability. It must also optimize the cost expended in
building the structure and maintenance.
The design method employed was the limit state design according to the Ethiopian building
code of standard ES EN 2015.
1.2 Objective
The general objective of this project paper is the analysis and design of a G+5 building for
the purpose of mixed-use. The structural design of the building is based on the theoretical
knowledge we have gained throughout our academic years. The project consists of
Design of stair
Design of footing
A structure shall be designed and executed in such a way that it will, during its intended
life with appropriate degrees of reliability and in an economical way. [ES EN 1990-2015
section 2.1]
Sustain all actions and influences likely to occur during execution and use, and
Remain fit for the use which it is required
Structural resistance
Serviceability
Durability
Durability: The structure shall be designed such that deterioration over its design working
life does not impair the performance of the structure below that intended, having due
regards to its environment and the anticipated level of maintenance.
Safety: implies the likelihood of partial or total collapse of the structure is acceptably low
not only under normally expected loads (service loads) but also under abnormal but
probable overloads (such as due to an earthquake or extreme wind). Collapse may occur
due to various possibilities such as exceeding the load-bearing capacity, overturning,
sliding, buckling, fatigue and fracture, etc.
Serviceability: The structure must be able to carry the design load safely without excessive
material distress and with deformations within an acceptable range. This is achieved by
using safety factors in the design of the element.
Costs: is an influential factor in the choice of most structures. The cost criterion cannot be
separated from the criteria of efficiency and construction. A highly efficient structure that
is not difficult to construct will probably be an economical one.
Limit States: -the relevant design situations shall be selected taking into account the
circumstances under which the structure is required to fulfill its function. In our case, we
take a persistent design situation which refers to the condition of normal use [ES EN
1990:2015 section 3].
1. Ultimate limit states: - the limit state that concerns the safety of people and the
structures.
2. Serviceability limit states: - Which deal with discomfort to occupancy or
malfunction, caused by excessive deflection, crack-width, vibration, leakage and
loss of durability, etc. It concerns the functioning of the structure or structural
members under normal use, the comfort of people, and the appearance of the
construction work.
Concrete: - The main measure of the structural quality of concrete is its characteristic
compressive cylinder strength. It is denoted by concrete strength classes which relate to
the characteristic (5%) cylinder strength fck , or the cube strength fck ,cube determined at 28
cc = is the coefficient taking account of long term effects on the compressive strength
and of unfavorable effects resulting from the way the load is applied. The recommended
value is 0.85.
c =1.5for persistent & transient and 1.2 for accidental [ES EN 1992: 2015 Table 2.1]
Characteristic tensile strength: - refers to the axial tensile strength determined by tests
in accordance with a standard issued from the characteristic cylinder compressive strength
with an empirical relation The value of tensile design strength is f ctd , is defined as
𝟎.𝟎𝟓𝒇𝒄𝒌
𝒇𝒄𝒕𝒅 = 𝜶𝒄𝒕 𝜸𝒄
Equation 1-2
ct is the coefficient taking account of long term effects on the tensile strength and of
unfavorable effects resulting from the way the load is applied. The recommended value is
0.85. [ES EN 1992:2015 Table 3.1]
𝟐
( )
𝒇𝒄𝒕𝒎 = 𝟎. 𝟑𝟎𝒇𝒄𝒌 𝟑 ≤ 𝑪𝟓𝟎/𝟔𝟎 Equation 1-3
𝒇𝒄𝒕𝒎 = 𝟐. 𝟏𝟐𝒍𝒏(𝟏 + (𝒇𝒄𝒎 /𝟏𝟎)) > 𝑪𝟓𝟎/𝟔𝟎 Equation 1-4
𝒇𝒄𝒎 = 𝒇𝒄𝒌 + 𝟖 (𝑴𝒑𝒂) Equation 1-5
𝑬𝒄𝒎 = 𝟐𝟐[(𝒇𝒄𝒎 )/𝟏𝟎]𝟎.𝟑 Equation 1-6
𝒇𝒄𝒕𝒌, 𝟎. 𝟎𝟓 = 𝟎. 𝟕 × 𝒇𝒄𝒕𝒎 𝟓% 𝒐𝒇 𝒇𝒓𝒂𝒄𝒕𝒊𝒍𝒆 Equation 1-7
Where:
f yk
f yd
s Equation 1-8
s =1.15 for persistent & transient condition &1.0 for accidental condition in [ES EN
1992: 2015 Table 2.1]
𝑓𝑐𝑘,𝑐𝑢𝑏𝑒 (𝑀𝑝𝑎) 30 37
𝑓𝑐𝑚 (Mpa) 33 38
𝑓𝑐𝑡𝑚 (Mpa) 2.6 2.9
𝐸𝑐𝑚 (Gpa) 31 33
𝑓𝑐𝑡𝑘, 0.05 𝑀𝑝𝑎 1.8 2.0
For beam, floor slab, column elements concrete grade of C25/30 is used.
Floor Finish 27
Plastering 25
Cement screed 23
HCB 14
RC 25
This paper outlines the static calculation of the structural design of a G+5 mixed-use
building. The building is architecturally designed to give service mainly for shopping,
guest houses, and other function. The building has two main entrances at the front and a
stairway is located on both sides of the building. The Foundation of the building is laid on
a 979.09m² plot area.
Location
Geometry
The building has different geometrical and structural arrangements consisting of 7 bays in
the x-direction and 6 bays in the y-direction. It consists of a flat slab roof, beams, and
columns, and ribbed slabs are adopted for the floor system. It has also a staircase to provide
a vertical circulation between floors. The building is regular in elevation having different
story heights.
The wind is a moving air which in turn possesses energy and this kinetic energy should be
resisted by using appropriate design for different kinds of structural elements like roofs,
walls Wind actions are fluctuating with time.
They act directly on the external surfaces of enclosed structures and also act indirectly on
the internal surfaces. They must also directly affect the internal surface of open structures.
These effects are more magnified for structures with more openings and large surface area.
The mean wind velocity vm ( z ) at a height z above the terrain depends on the terrain
roughness and orthography and on the basic wind velocity, vb, and should be determined
using [ES EN 1991-1-4 2015 expression (4.3)]
vm ( z ) cr ( z ) co ( z ) vb Equation 2-1
Where:
Basic wind velocity, vb is the characteristics 10 minutes mean wind velocity, irrespective
of wind direction and time of year, at 10m above ground level in open country terrain with
a regular cover of vegetation or buildings or with isolated obstacles with separation of a
maximum 20 obstacle heights (such as villages, suburban terrain, permanent forests) [ES
EN 1991-1-4: 2015 Table 4.1]
Where :
Use the following formula for the calculation of the roughness coefficient
z
cr ( z ) kr ln( ) for zmin ≤Z≤ zmax Equation 2-3
zo
Where:
zo is the roughness length
Since the actual height of the building, Z= 19.2m, is between zmin and 200m, we use the
following formula for the calculation of the roughness coefficient
z
cr ( z ) kr ln( )
zo
Terrain factor depending on the roughness length zo calculated using the formula given
below
0.07
𝑍0
𝑘𝑟 = 0.19 [ ]
𝑍𝑜,∏
Where:
zo, 0.05m [Terrain category Ш, ES EN 1991-1-4: 2015 Table 4.1)]
The site is assumed to fall under category Ш because Haramaya town is classified under
suburban. Then from [ES EN 1991-1.4: 2015 table 4.1 for category Ш]
zo = 0.3m
zmin = 5m
zo, = 0.05m
0.3 0.07
𝑘𝑟 = 0.19 [ ] = 0.215
0.05
For 2047m above mean see level according to [ES EN1991:2015 sec1.4 table 4.1]
cr ( z ) = 0.215𝑙𝑛(19.2/0.3) = 0.894
2.1.4 Orography factor
co = 1.0
vm ( z ) cr ( z ) co ( z ) vb
vm ( z ) = 0.894*1*22=19.668m/s
kr vb kl Equation 2-5
Where:
kl is the turbulence factor. The recommended value kl is = 1.0.
𝜎𝑣 𝑘𝑙
𝑙𝑣 (𝑧) = 𝑣 =𝑐 𝑧 for 𝑧𝑚𝑖𝑛 ≤z ≤ 𝑧𝑚𝑎𝑥
𝑚 (𝑧) 0 (𝑧)∙ln( ⁄𝑧𝑜 )
lv ( z ) 1/(1×ln(19.2/0.3)=0.24
The peak velocity pressure q p ( z ) at height z, which includes mean and short-term velocity
fluctuations, should be determined.
1
𝑞𝑝 (𝑧) = [1 + 7𝑙𝑣 (𝑧)] ∙ 𝜌𝑣𝑚 2 (𝑧)
2
q p ( z ) =[1+7×0.24]×0.5×0.94×19.6682=487.25kN
1, The wind pressure acting on the external surfaces, we should be obtained from
2, The wind pressure acting on the internal surface of a structure, wi , should be obtained
[ES EN 1991-1-4: 2015 Expression 5.2]
wi q p ( zi )* c pi Equation 2-7
Where :
External wind pressure coefficient ( c pe ) this coefficient depends on the size of the
Values of c pe,1 are intended for the design of small elements and fixing with an area per
Values of c pe,10 may be used for the design of the overall load-bearing structure of buildings
2h=2×19.2=38.4
So use e=b=13.8m
Area of G=e/2×e/10=6.9×1.38=9.522m2
Area 0f I=e/2×e=13.8/2×13.8=95.22m2
The reference height (ze), for flat roofs with parapets should be taken as h+ hp [ES EN
1991-1-4:2015 section 7.2.3]
(ze)= h+ hp=19.2+0.5=19.7m0
hp/h= 0.5/19.7=0.0253
Zone F G H I
Area(m2) 4.761 9.522 76.176 95.22
c pe,10 c pe,1 c pe,10 c pe,1 c pe,10 c pe,1
c pe,10 c pe,1
-1.597 -2.197 -1.097 -1.797 -0.7 -1.2 ±0.2
c pe -1.896 -2.444 -0.7 0.2 -0.2
Sample calculation
Cpe for zone F since the area is 1m2<A<10m2
c pe = -2.197-(-2.197-(-1.597))log 4.761=-1.896
The reference heights, ze for windward walls of rectangular plan buildings (zone D),
depend on the aspect ratio h/b and are always the upper heights of the different parts of
the walls.
𝑏 37.37
𝑒 = 𝑚𝑖𝑛 { = 𝑚𝑖𝑛 {
2ℎ 38.4
Take e=37.37 m and d=26.20m e >d
A B
e /5 d-e/5
Mean velocity
The mean wind velocity vm z at a height z above the terrain depends on the terrain
roughness and orography and on the basic wind velocity v b and should be determined
vm z cr z co z vb
Terrain factor ( k f )
Terrain factor depending on the roughness length zo calculated using the formula given
below
0.07
z
kr 0.19 o
zo
The site is assumed to fall under category III because Haramaya is classified under
suburban.
Then from ES EN 1991 1-4 2015 table 4.1 pages 13 for category III
0.07
0.3
kr 0.19 = 0.22
0.05
Since the actual height of the building, Z = 19.2m, is between Z min and 200m, we use the
following formula for the calculation of the roughness coefficient.
z
cr kr ln = 0.22*ln*(19.2/0.3)= 0.915
zo
b
cr b 0.22 ln =0.22ln (37.37/0.3) =1.061
zo
vm h =1.061*1*22m/s2=23.35m/s2
Wind turbulence
The turbulence intensity lv (z) at height z is defined as the standard deviation of the
turbulence divided by the mean wind velocity.
The turbulent component of wind velocity has a mean value of 0 and a standard deviation
σv.
The standard deviation of the turbulence σv may be determined using Expression (4.6)
from ES EN 1991: 2015 sec 1.4
𝛿 = 𝑘𝑟 ∙ 𝑣𝑏 ∙ 𝑘𝑙
Where KI is the turbulence factor. The value of KI may be given in the National Annex.
The recommended value is KI = 1.0.
v kl
lv ( z ) For z min ≤z ≤ z max
vm ( z ) co ( z ) ln( z zo )
z=b
v kl
lv ( z ) For z min ≤z ≤ z max
vm ( z ) co ( z ) ln( z zo )
z=h
The peak velocity pressure q p z at height z, which includes mean and short term velocity
Air density, which depends on the altitude, temperature and barometric pressure to be
expected in the region during wind storms. Which is 1.25 Kg/m3.
For flat terrain where C0 (z) = 1.0, the exposure factor Ce (z) is illustrated in Figure 4.2
from [EN ES 1991-1-4: 2015] as a function of height above terrain and a function of terrain
category.
So for the terrain category III and z= 19.2 m the exposure factor
Internal pressure wi
For a building with a dominant face, the internal pressure should be taken as a fraction
of the external pressure at the openings of the dominant face. The values are given
by expressions 7.2 from [ES EN 1991-1.4: 2015].
When the area of the openings at the dominant face is twice the area of the openings in the
Remaining faces,
Cpi = 0.7×Cpe
A B
Cpe -1.2 -0.8
Cpi -0.84 -0.56
The net wind pressure is the difference of the pressure on each surface taking into account
the signs. And there will be various net wind pressure combinations out of which the
severe cases are taken. The net wind forces are shown below:
The concrete cover is the distance between the surface of the reinforcement closest to the
nearest concrete surface (including links and stirrups and surface reinforcement where
relevant) and the nearest concrete surface from [ES EN1992:2015 Art 4.4.1]
Where:-
an adequate resistance
cmin,b
cmin max cmin,dur cdur , cdur , st cdur ,add Equation 2-9
10m
Where:
But the recommended value of ∆cdur,ɣ , ∆cdur,st and ∆cdur,add is zero. [ES EN 1992:2015 Art
4.4.1.2(6,7,and 8)].
In order to transmit bond forces safely and to ensure adequate compaction of the concrete,
the minimum cover should not be less than Cmin,b.
Assume use Φ10 longitudinal bar and 20mm nominal maximum aggregate size
The condition of exposure is given to be XC4 for cyclic and wet-dry in which the concrete
surface subjected to water contact, not within exposure class XC2 from [EN ES 1992 1.1
2015 table 4.1] then the indicated strength of concrete is C30/37.
The recommended structural class (design working life 50 years) is S4 for the indicative
concrete strengths given in Annex E and the recommended modification to structural class
is given in Table 4.3N. And based on the above table the exposure class is reduced by 1 so
the structural class would be class S(4 – 1) = S3.
Therefore, the value of minimum cover required for the durability of reinforcement steel
Cmin,dur=25mm using [ES EN 1992:2015 table 4.4N]. Then;
Cmin=max{cmin,b=10mm,cmin,du=25mm,10mm}
The value of ∆𝑐𝑑𝑒𝑣 for use in a Country may be found in National Annex. The
recommended value is 10 mm.
l o o
3/2
l o 1 '
k 11 1.5 f ck f ck if > o Equation 2-11
d 12
'
o
l o o
3/2
3
l 5.48 103 2
=k(11+1.5 30 ×5.48×10-3/5×10-3+ 3.2 30 3
1 )
d 5 10
l
=20.52k
d
The above two expressions have been derived on the assumption that the steel stress, under
the appropriate design load at SLS at a cracked section at the mid-span of a beam or slab
or at the support of a cantilever, is 310Mpa, (corresponding roughly to fyk= 500Mpa).
Where other stress levels are used, the values obtained using these expressions should be
multiplied by 310/σs. It will normally be conservative to assume that
l
=20.52k×1.25=25.65k
d
Table 2-5 Depth determination for roof slab
Panel Ly Lx Ly/Lx Type of L(mm) Boundary K 25.65k d(mm)
(mm) (mm) slab
P1 5.5 5 1.1 two way 5000 Interior 1.5 38.47 129.95
P2 5.5 5 1.1 two way 5000 End 1.3 33.34 149.97
P3 5 3 1.67 two way 3000 Interior 1.5 38.47 77.98
P4 5 3 1.67 two way 3000 Interior 1.5 38.47 77.98
P5 5.5 5 1.1 two way 5000 End 1.3 33.34 149.97
P6 5.5 5 1.1 two way 5000 End 1.3 33.34 149.97
From the above depth determination, we select the governing one d=149.97mm
∅
D=d+cover+2=149.97+35+5=189.97mm 190mm
D=190mm
d=190-35-5=150mm
Dead load
Table 2-6 Dead load of the roof slab
Material Dimension(m)*unit weight(kN/m3) Dead load (kN/m2)
Floor finish 0.02×27 0.54
Sement screed 0.02×23 0.46
RC slab 0.19×25 5.25
Plastering 0.02×25 0.5
Total dead load 6.75
Live load
Since the roof is inaccessible except for normal maintenance or other similar things, it falls
under category H. And accordingly to the nature of the roof which is a flat roof. From [ES
EN 1991 1.1: 2015 table 6.10]
Therefor from the above loading combinations we select the governing combination and
the governing combination is combination 2.
Depending on the type of panel support and field moment of the individual panel can be
determined by using the coefficient method.
M sy sy Pd lx 2 Equation 2-13
Pd=9.71 kN/m2
Table 2-7 Moment distribution
P Type ly lx ly/lx ꞵsx,sup ꞵsx,span ꞵsy,sup ꞵsy,span Msx,sup Msx,span Msy,sup Msy,span
1 *** 5.5 5 1.1 0.047 0.036 0.037 0.034 11.409 8.739 8.982 6.797
2 **** 5.5 5 1.1 0.055 0.0412 0.045 0.034 13.351 9.953 10.924 8.254
3 ** 5 3 1.67 0.061 0.046 0.037 0.028 5.365 4.02 3.233 2.447
4 ** 5 3 1.67 0.0614 0.046 0.037 0.028 5.365 4.02 3.233 2.447
5 **** 5.5 5 1.1 0.055 0.0412 0.045 0.034 13.351 9.953 10.924 8.254
6 **** 5.5 5 1.1 0.055 0.0412 0.045 0.034 13.351 9.953 10.924 8.254
8.982−5.365
Change= × 100 = 67.4% > 10% use moment distribution
5.395
Member Stiffness DF
Joint B BA 𝐼 0.182I 0.35
5.5
BC 𝐼 0.333I 0.65
3
𝐼
Stiffness=KBA=5.5=0.188I
0.182𝐼
DFBA=(0.182𝐼+0.33𝐼)=0.35
BA BC
DF 0.35 0.65
8.982 -5.365
3.617
1.266 -2.35
7.716 7.716
The adjusted moment is 7.716kNm
M1= (8.982+6.979)-7.716=8.245kNm/m
M3=95.365+4.02)-7.716=1.669kNm/m
13.351−11.409
Change= × 100 = 17.02% > 10%, use reinforcement distribution
11.409
BA BC
DF 0.5 0.5
-11.409 13.351
1.942
-0.971 -0.971
-12.38 12.38
The adjusted moment is 12.38kNm
10.924−5.363
Change = × 100 = 98.4% > 10% use moment distribution
5.395
Member Stiffness DF
Joint BA 𝐼 0.182I 0.35
5.5
BC 𝐼 0.333I 0.65
3
BA BC
DF 0.35 0.65
10.924 -5.365
5.559
1.946 -3.613
8.978 -8.978
f ck
f cd cc =
0.85×30
= 17𝑀𝑝𝑎
c 1.5
f yk 400
f yd =1.15 = 347.83Mpa
s
𝑓𝑐𝑡𝑚 =2.9Mpa
𝑓𝑐𝑡𝑚
𝐴𝑠𝑚𝑖𝑛 =0.26 × 𝑏𝑑 > 0.013𝑏𝑑
𝑓𝑦𝑘
2.9
𝐴𝑠𝑚𝑖𝑛 =0.26 × 400 × 1000 × 150=282.75mm2
𝑏∙𝑎𝑠 1000×78.5
𝑠𝑚𝑖𝑛 = 𝐴𝑠 = =277.6mm use 𝑠𝑚𝑖𝑛 =270mm
282.75
3ℎ = 3 × 190 570
𝑠𝑚𝑎𝑥 =min { =𝑚𝑖𝑛 { = 400𝑚𝑚
400 400
𝑀𝑠𝑑 12.38×106
𝜇 = 𝑘=𝑓𝑐𝑑∙𝑏𝑑2 =17×1000×1502 = 0.03236
𝐾𝑧 = 0.5(1 + √1 − 2𝑘)=0.9835
𝑍 = 𝐾𝑧 ∙ 𝑑
𝑀
As=𝑍∙𝑓
𝑦𝑑
For panel 1 with 𝑀𝑠𝑑=12.38 then As=0.2 ∗241.25 = 48.25𝑚𝑚2 with a minimum spacing
Detailing
6=∅10𝐶/𝐶400𝑚𝑚
A rib is a slab system that consists of series of parallel reinforced concrete T beams framing
into reinforced concrete girders. The slab is the flange of the beam and the extended part
is the web. The extended part is known as ribs.
Ribs are made up of wideband beam running between columns with narrow ribs spanning
the orthogonal direction.
In this type of slab, the tension stress is eliminated on the tension side of the slab.
The strength of concrete in tension is very small and so elimination of much of the
tension concrete is done by the use of pan forms.
Economical where the live loads are fairly small such as apartment houses, hotels.
Long slab spans can be constructed through ribbed Slabs. In many cases, long
spans are desirable in the building. Ribbed slabs are an easy solution for this
purpose.
The slab thickness of ribbed slabs is less than other slab systems. Therefore, the
weight of the slab is reduced. This saving of weight can change in structural
characteristic.
They provide a very good form where slab vibration is a viable issue
Verifying if the general requirements for rib slab are met using ES EN.
The rib spacing does not exceed 1500 mm this is satisfied in our case, as the center
to center spacing between the ribs is 400mm.
The depth of the rib below the flange does not exceed 4 times its width.
The depth of the flange is at least 1/10 of the clear distance between ribs or 50 mm,
whichever is the greater 𝑡𝑓 mm mm, therefore, 60 mm
satisfies this requirement.
Transverse ribs are provided at a clear spacing not exceeding 10 times the overall
depth of the slab.
3.1.1 Loading
Live load
Qk = 0.4m*4kN/m2=1.6kN/m
Design load
W=6.57 kN/m
In this ribbed slab design axis A, B, C, D, E, and F used in place of axis Y01, Y02, Y03,
Y04, Y0, Y06, and Y07 respectively.
27.63 15.71
Reaction from the rib divided by rib spacing will be =69.1 kN/m and
0.4 0.4
=39.3kN/m
M (kNm)
M (kNm)
Take cover 25 𝑚𝑚
12
𝑑=260−25−8− =221 𝑚𝑚
2
b1=b2=160mm
Therefore, beff=400mm
However, since it is a negative moment the width of the compression zone will be,
b=80mm
0.85∗𝑓𝑐𝑘
𝑓𝑐𝑑= =14.167𝑀𝑝𝑎
1.5
400
𝑓𝑦𝑑=1.15 =347.87𝑀𝑝𝑎
𝑓𝑦𝑑 347.87
ɛ𝑦𝑑= 𝐸𝑠 = =1.74%
200
0.26∗𝑓𝑐𝑡𝑚
𝐴𝑠𝑚𝑖𝑛 = 𝑏𝑡 𝑑 = 29.88mm2 where 𝑏𝑡 = 𝑏𝑤 =80mm
𝑓𝑦𝑘
𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑠 Ok
𝜋𝑑2 𝐴
Using ∅12 𝑎𝑠 = =113.04 𝑛 = 𝑎𝑠 =1.37
4 𝑠
𝑉𝑅𝑑, 𝑐= [𝐶𝑅𝑑, 𝑐.𝐾 (100𝜌1 . 𝑓𝑐𝑘 ) 1/3 +𝐾1 ∙ 𝜎𝑐𝑝 ] 𝑏𝑤.𝑑 > (𝑉𝑚𝑖𝑛 +𝐾1 ∙ 𝜎𝑐𝑝 ]) 𝑏𝑤.𝑑
Where
0.18
𝐶𝑅𝑑, 𝑐= = 0.12
𝛾𝑐
200
𝐾=1+ √ ≤ 2.0 d=221mm
𝑑
K=1.95
𝐴𝑠
𝜌1 =𝑏 < 0.02
𝑤∙ 𝑑
155.8
𝜌1 ={80∗221} =0.00881, for the section with 2∅12 bars
𝑓𝑐𝑘 =25Mpa
𝐾1 =0.15
𝑁𝐸𝐷
𝜎𝑐𝑝 = <0.2𝑓𝑐𝑑 =0 ………. (𝑁𝐸𝐷 =0)
𝐴𝑐
3 1
𝑉𝑚𝑖𝑛 =0.035∙ 𝐾 2 ∙ 𝑓𝑐𝑘 2 =0.476
𝜶𝒄𝒘∙𝒃𝒘∙𝒁∙𝒗∙𝒇
𝒄𝒅
𝑽𝑹𝑫𝒎𝒂𝒙= Equation 3-2
(𝒄𝒐𝒕𝜽+𝒕𝒂𝒏𝜽)
𝑨𝒔𝒘
𝑽𝑹𝑫,𝑺= 𝑺
∙ 𝒁 ∙ 𝒇𝒚𝒘𝒅∙ cot𝜽 Equation 3-3
𝑉𝑅𝐷𝑚𝑎𝑥
𝑉𝑅𝐷(min) ={ 𝑉
𝑅𝐷,𝑆
Where
𝑓𝑐𝑑 = 14.164Mpa
Z= 0.9∙d=198.9mm
𝑉𝑅𝐷𝑚𝑎𝑥 =46.62kN
𝑨𝒔𝒘 ∙𝒇𝒚𝒅 𝟏
𝒃𝒘 ∙𝒔
≤ 𝟐 ∙ 𝜶𝒄 ∙ 𝒗 ∙ 𝒇𝒄𝒅 Equation 3-4
0.08√𝑓𝑐𝑘
𝜌𝑚𝑖𝑛 = =0.001
𝑓𝑦𝑘
𝜋
𝐴𝑠𝑤 2x(∅62 )
4
S=𝑏 = =706.5mm > 𝑠𝑚𝑎𝑥
𝑤 ∙𝜌𝑤 ∙𝑠𝑖𝑛𝛼 80∗0.001∗1
Shear reinforcement
𝐴𝑠𝑤 𝑉
=0.78∙𝑑∙𝑓𝐸𝐷
𝑠 𝑦𝑘∙ 𝑐𝑜𝑡𝜃
𝑆𝑚𝑖𝑛 = 707mm
On-axis C and D
𝑀𝑠𝑑 = 12.28 kNm,𝑏𝑡= 𝑏𝑤 = 600 𝑚𝑚, D =300mm 𝑓𝑐𝑑 =14.167 Mpa,𝑓𝑦𝑑 = 347.87𝑀𝑝𝑎
𝑓𝑐𝑡𝑚 = 2.6𝑀𝑝𝑎, use concrete cover 25, ∅16 𝑏𝑎𝑟 and ∅8 stirrup
16
d=300-25-8- 2 =259mm
𝑀𝑠𝑑
𝜇𝑠𝑑 = =0.021
𝑓𝑐𝑑 𝑏𝑑 2
𝐾𝑧=0.974 𝑍=𝐾𝑧𝑑=252.266mm
𝑀𝑠𝑑
𝐴𝑠 = 𝑓 = 139.93mm2
𝑦𝑑 𝑧
0.26∗𝑓𝑐𝑡𝑚
𝐴𝑠𝑚𝑖𝑛 = 𝑏𝑡 𝑑 = 262.63mm2 𝐴𝑠𝑚𝑖𝑛 >𝐴𝑠 not Ok
𝑓𝑦𝑘
𝜋𝑑2 𝐴𝑠𝑚𝑖𝑛
Using ∅16 𝑎𝑠 = =200.96mm2 𝑛 = =1.3
4 𝑎𝑠
𝑀𝑠𝑑 = 21.13𝑘𝑁𝑚
𝑀𝑠𝑑
𝜇𝑠𝑑 = =0.037
𝑓𝑐𝑑 𝑏𝑑 2
𝑀𝑠𝑑
𝐴𝑠 = 𝑓 = 240.55mm2
𝑦𝑑 𝑧
0.26∗𝑓𝑐𝑡𝑚
𝐴𝑠𝑚𝑖𝑛 = 𝑏𝑡 𝑑 = 262.63mm2 𝐴𝑠𝑚𝑖𝑛 >𝐴𝑠 not Ok
𝑓𝑦𝑘
𝜋𝑑2 𝐴𝑠𝑚𝑖𝑛
Using ∅16 𝑎𝑠 = =200.96mm2 𝑛 = =1.3
4 𝑎𝑠
12
d = 300-25-8- 2 = 261 mm
𝑀𝑠𝑑
𝜇𝑠𝑑 = =0.032
𝑓𝑐𝑑 𝑏𝑑 2
𝑀𝑠𝑑
𝐴𝑠 = 𝑓 = 68.06mm2
𝑦𝑑 𝑧
0.26∗𝑓𝑐𝑡𝑚
𝐴𝑠𝑚𝑖𝑛 = 𝑏𝑡 𝑑 = 88.22mm2 𝐴𝑠𝑚𝑖𝑛 >𝐴𝑠 not Ok
𝑓𝑦𝑘
𝜋𝑑2 𝐴𝑠𝑚𝑖𝑛
Using ∅12 𝑎𝑠 = =113.04mm2 𝑛 = =0.78
4 𝑎𝑠
Use 2∅12 bottom and topping bar for the total length of a beam
𝐴𝑠2=20% 𝐴𝑠min
𝐴𝑠2=0.12% 𝐴𝑡𝑜𝑝𝑝𝑖𝑛𝑔
𝑏𝑎
𝑆𝑝𝑎𝑐𝑖𝑛𝑔 𝑆= 𝐴 𝑠
𝑠
3.5 Detailing
4.1 Staircase
A stair is a set of steps leading from one floor of a building to another providing
communication between floors. They should be provided with natural light and proper
ventilation. Usually, the location of the stair is at the center of the building, while in our
project since a dual stair system is provided therefore the stair is located at both end hand
direction because we design a mixed-used building to reduce fluctuation of the user.
Riser = 170mm
Tread = 300mm
l p 1 p'
k 11 1.5 f ck f ck Equation 4-1
d p p 12
'
p
According to EC-2 table, 7.4N take the value of K=1.0, concrete highly stressed ρ=1.5%
is for a simply supported slab of structural system
l 500
11.67 Because we used S400 multiply the value by =1.25
d f yk
l
d
=14.5 and the overall width of the stair is l =2.8
2.8
d =0.192 190mm
14.58
Loading
Dead load at stair by 1m strip width
Stair slab
2cm plastering on the tread 0.02m 25 cos 29.05 1m 0.437 kN/m
2cm cement screed on the tread 0.02 23 cos 29.05 1m 0.402 kN/m
2cm cement screed on the riser 0.02 23 cos 29.05 1m 0.402 kN/m
2cm floor finish on the tread 0.02m 27 cos 29.05 1m 0.47kN/m
2cm floor finish on the riser 0.02m 27 cos 29.05 1m 0.47kN/m
1 1
riser conc = 0.16m 25 1m =2kN/m
2 2
Total dead load DL=8.6kN/m
Loading on beam
Beam width= 0.3m
Beam depth= 0.2m
Self-weight of the beam= 0.3×0.2×25=1.5kN/m
2cm plastering 0.02×25×1=0.5kN/m
2cm cement screed 0.02×1×23=0.47kN\m
2cm floor finish 0.02×1×27=0.54kN/m
The total dead load of landing beam=3.01kN/m
M Ed z 60k
k 2
0.0057 0.167.........OK 0.5(1 (1 )) 0.99
fckbd d 17
M Ed
Z=267mm As 100mm 2
z fyd
M Ed z 60k
k 2
0.002 0.167.........OK 0.5(1 (1 )) 0.99
fckbd d 17
M Ed
Z=267mm As 111mm 2
z fyd
d 190mm b 1000mm
0.85 25
C 25 / 30 fcd 14.16Mpa
1.5
According to ES EN 1992:2015
2
f ctm 0.3 fck 3 C 50 / 60 hence we use C 25 / 30
2
400
fctm 0.3 (25) 3 2.56 Mpa fyd 347.8Mpa
1.15
f ctm
Asmin 0.26 bt d 316.16mm2
f yk
M Ed 18.5 106
k 0.02 0.167.........OK
fckbd 2 25 1000 1902
z 60k
0.5(1 (1 )) 0.977
d 17
Therefore, z 0.97 190 185mm
M Ed 18.5 106
As 286.2mm
z fyd 185 347.8
b as 1000 154
s= 560mm
As 274
3h
Smax min 𝑆𝑚𝑎𝑥=400mm
400
z 1 60k
k 0.086 (1 1 ) 0.92
d 2 17
b as 1000 154
Spacing= 265mm
As 580
Therefore provide 14 with c/c 265mm
Is provide the same with at support A because a negative moment of the two support is
the same.
Provide 14 with c/c 265mm
Detailing
Mostly earthquake is the governing lateral load for frame analysis. In the case of the frame
system, lateral forces are resisted by frame action of beams, columns, and rigid joints.
While in the shear walls the lateral force is resisted by the wall itself in its major axes.
As per [ES EN 1998 1:2015] Elastic spectrum analysis can be applied to buildings
satisfying the following two conditions
1. The fundamental period of vibration T1 in the two main directions which are smaller
than the following values
4 Tc
T1 Equation 5-1
2.0 s
2. They meet the criteria for regularity in elevation specified [ES EN 1998 1:2015 art
4-2-3-3]
For a building with heights of up to 40m, the value of T1 see may be approximated by
Where C1 0.075
H 19.20m
T1 0.075 19.20
3/4
0.687
Where
C1 is 0.085 for moment resistant space steel frames, 0.075 for moment resistant space
concrete frames, and for the eccentrically braced steel frame and 0.050 for all other
structures;
H is the height of the building. In m, from the foundation or from the top of a rigid
basement
1) T1 2sec 0.687 sec < 2sec ] & [T1 < 4 0.6 0.687 sec 2.4 sec ], OK !
2) Elevation regularity conditions are met, OK! Both requirements are satisfied so,
elastic spectrum analysis can be used.
Ground Conditions
An appropriate investigation shall be carried out to identify the ground condition [ES EN
table 3.1 1998-1-2015]
The construction site and the nature of the supporting ground should normally be
free from risks of ground rupture, slope instability, and permanent settlements
caused by liquefaction or densification in the event of an earthquake.
Depending on the importance class of the structure and particular condition of the
project, ground investigation and/or geological studies to be performed to
determine the seismic action
Ground types A, B, C, D, and E are used to account for the influence of local
ground conditions on the seismic action.
The site should be classified according to the value of the average shear wave
velocity, vs 30 if this is available. Otherwise, the value of standard penetration test
below-count (NSPT) should be used.
For sites with ground conditions matching either one of the two special ground
types S1or S2, special studies for the definition of the seismic action are required.
For S2 the possibility of soil failure under the seismic action shall be taken into
account.
Special attention should be paid if the deposit is of ground type S1. a special study
to define the seismic action should be carried out, in order to establish the
dependence of the response spectrum on the thickness and vs. value of the soft
clay/silt layer
Therefore, the period values of the parameters and the soil factor for spectra-1 are given
in the table below:
Peak ground acceleration ag: this value depends on the earthquake zone for a given
town, in our project the building will be constructed in Haramaya. Therefore, it is
categorized on the seismic zone of H
Behavior factor (q): our building is a medium ductile, multi-story, and multi-bay building.
𝒒 = 𝒒𝒐 ∙ 𝒌𝒘 ≥ 𝟏. 𝟓 Equation 5-3
Where:𝑞𝑜 = 3𝛼𝑜 /𝛼1 for MRF systems……...…... [ES EN 1998-1:2015 Table
5.1].
𝑘𝑤 = 1 [ES EN 1998-1:2015 P(11)]
𝛼𝑜
= 1.3 [ES EN 1998-1:2015 P(5)]
𝛼1
2.5 TC
TC T TD : Se (T ) ag s ag Equation 5-4
q T
2.5
Sd T 1.47 1.15 0.6 / 0.687 0.2 1.47
3.9
0.94 0.294........OK
Where
is the lower bound factor for the horizontal design spectrum =0.2
TB is the lower limit of the period of the constant spectral acceleration branch;
TC is the upper limit of the period of the constant spectral acceleration branch;
TD is the value defining the beginning of the constant displacement response range of
the
Fb Sd (T1 )m
T1 is the fundamental period of vibration of the building for lateral motion in the
direction considered;
𝑀 is the total mass of building above the foundation or above the top of ridge
basement computed in accordance with (3,2,4(2)).
is the correction factor the value of which is equal to 0.85ifT1 2TC and the
building has more than two stories or 1.0 otherwise
According to [ES EN 1998:2015] the seismic weight of a building taking into account the
presence of masses associated with gravity loads are given by the combination below:
𝜓𝐸𝑖 = 𝜑. 𝜓2, 𝑖
The seismic weight of the building can be determined from ETABS software after
assigning mass source as specified load pattern option.
6.1 Introduction
Beam is a horizontal structural member used to carry a vertical load, shear load, and
sometimes horizontal load. It is a major component of building structures.
Depth determination for both end span and interior span of continuous beam on axis XO2
l o o
3/2
l o 1 '
k 11 1.5 f ck f ck if > o Equation 6-2
d 12
'
o
Assume the concrete is highly stressed then 𝜌=1.5%
l o 1 '
𝜌 > 𝜌𝑜 So we use k 11 1.5 f ck f ck
d 12
'
o
𝑙 5 × 10−3 1 0
= 𝑘 [11 + 1.5√25 + √25√ = 13.5𝑘]
𝑑 0.015 − 0 12 5 × 10−3
𝑙
= 13.5𝑘 × 1.25 = 16.88𝑘
𝑑
Cover= 25mm
Use h=300mm
Partition load=8.12+2.025=10.145kN/m
From the beams on-axis Y04 the governing moment is found on the beam B32 (between
axis X01 and X02) as well as on beam B48 (between X06 and X07)
d=300-25-8-16/2=259mm
𝑀𝑠𝑑 22.64×106
𝜇𝑠𝑑 = 𝑓 = = 0.119 < 𝜇𝑠𝑑 𝑙𝑖𝑚= 0.295 singly reinforced
𝑐𝑑 𝑏𝑑2 14.17×200×2592
Z = K z ∙ d=0.936× 259=242.54mm
Msd 22.64×106
As= = = 268.37mm2
Z∙fyd 242.54×347.83
0.26×fctm 0.26×2.6
Asmin = bd = × 200 × 259 =87.54mm2
fyk 400
πD2 As
Use ∅16mm, as = =201.06 then number of bar = =1.33≈ 2 bars
4 as
Support moment
d=300-25-8-16/2=259mm
𝑀𝑠𝑑 30.73×106
𝜇𝑠𝑑 = 𝑓 = = 0.162 < 𝜇𝑠𝑑 𝑙𝑖𝑚= 0.295 singly reinforced
𝑐𝑑 𝑏𝑑2 14.17×200×2592
Z = K z ∙ d=0.911× 259=235.97mm
Msd 22.64×106
As=Z∙f =235.97×347.83 = 275.83mm2
yd
0.26×fctm 0.26×2.6
Asmin = bd = × 200 × 259 =87.54mm2
fyk 400
πD2 As
Use ∅16mm, as = =201.06 then the number of bar = =1.37≈ 2 bars
4 as
Loading on beam
The beam is designed from the maximum moment envelope for beams on axis Xo2
Span moment
The governing moment is found on beam B3 (between axis Yo4 and Yo5)
d=300-25-8-16/2=259mm
𝑀𝑠𝑑 15.38×106
𝜇𝑠𝑑 = 𝑓 = = 0.081 < 𝜇𝑠𝑑 𝑙𝑖𝑚= 0.295 singly reinforced
𝑐𝑑 𝑏𝑑2 14.17×200×2592
Z = K z ∙ d=0.958× 259=248.06mm
Msd 15.38×106
As=Z∙f =248.54×347.83 = 178mm2
yd
0.26×fctm 0.26×2.6
Asmin = bd = × 200 × 259 =87.54mm2
fyk 400
πD2 As
Use ∅16mm, as = =201.06 then number of bar = =0.885 bars
4 as
d=300-25-8-16/2=259mm
𝑀𝑠𝑑 39.54×106
𝜇𝑠𝑑 = 𝑓 = = 0.208 < 𝜇𝑠𝑑 𝑙𝑖𝑚= 0.295 singly reinforced
𝑐𝑑 𝑏𝑑2 14.17×200×2592
Z = K z ∙ d=0.882 × 259=228.44mm
Msd 39.54×106
As=Z∙f =228.44×347.83 = 497. 6mm2
yd
0.26×fctm 0.26×2.6
Asmin = bd = × 200 × 259 =87.542mm2
fyk 400
πD2 As
Use ∅16mm, as = =201.06 then number of bar = =2.47 ≈ 3𝑏𝑎𝑟𝑠
4 as
The main aim of this section is to determine the shear stress in beams at the critical sections
stated in ES EN 1992: 2015 and providing adequate shear reinforcement. As per ES EN
1992-1-1:2015 article 6.2.1(3) in regions of the member where 𝑣𝑒𝑑 ≤ 𝑣𝑟𝑑 no calculated
shear force is necessary. Where 𝑣𝑒𝑑 𝑖𝑠 the design shear force and 𝑣𝑟𝑑 is the design shear
resistance of concrete without shear reinforcement.
As a sample calculation beams on-axis Yo4 will be used to show the design procedure as
per ES-EN
𝑣𝑒𝑑 = 35.26kN
Check for diagonal compression failure with the max value of allowed by the
code). For members with vertical shear reinforcement the design resistance value
𝑉𝑟𝑑, 𝑚𝑎𝑥 is given by [ES EN 1992−1−1: 2015, Eqn 6.9]
𝜶𝒄𝒘∙𝒃𝒘∙𝒛∙𝒗𝟏∙𝒇𝒄𝒅
𝑽𝒓𝒅, 𝒎𝒂𝒙 = Equation 6-3
𝐜𝐨𝐭(𝜭)+𝐭𝐚𝐧(𝜭)
𝛼𝑐𝑤 = 1
𝑓𝑐𝑘 25
v1 = v =0.6∙ [1 − 250] =0.6∙ [1 − 250] = 0.54
1×200×242.54×0.54×14.17
𝑉𝑟𝑑, 𝑚𝑎𝑥 = × 10−3 = 127.82kN> 35.26kN
2.5 +0.404
Diagonal compression failure is not possible, i.e. the depth provided is OK!
For members without shear reinforcement, the design value of shear resistance is given by
[ES EN 1992 -1-1: 2015, Eqn. 6.2a]
𝑓𝑐𝑡𝑚 2.6
ρ1 = 0.26 = 0.26* = 0.0017
𝑓𝑦𝑘 400
But, the above value should be greater than the minimum resistance value
Since the value of 𝑣𝑅𝑑,𝑐 is less than the minimum the 𝑣𝑅𝑑,𝑐,𝑚𝑖𝑛 as the value of thus
calculated shear reinforcement is required.
For members requiring the design of shear reinforcement, the area of shear reinforcement
can be calculated from the spacing of the shear links and it is given by: [ES EN 1992-1-1:
2015, Eqn. 6.8]
Assume 8mm diameter of two vertical shear links, (=22o and = 89.999o) the longitudinal
spacing: The area of two leg links:
𝜋𝐷 2 𝜋×82
𝐴𝑠𝑤 = 2 × = 2×( ) = 100.48mm2
4 4
𝐴𝑠𝑤 100.48
𝑆𝑣 = 0.209 = = 480.78mm
0.209
Check for the maximum longitudinal spacing of shear reinforcement 𝑠𝑣,𝑚𝑎𝑥 [ES-EN 1992-
1-1: 2015, Eqn.9.6N]
Since the nominal longitudinal spacing is greater than the maximum spacing allowed the
maximum longitudinal spacing is provided as the nominal spacing.
Check for a minimum percentage of shear reinforcement 𝜌𝑤, 𝑚𝑖𝑛 [ES-EN 1992-1-1:
2015, Eqn.9.5N]
0.08√𝑓𝑐𝑘 0.08×√25
𝝆𝑤, 𝑚𝑖𝑛 = = = 0.001
𝑓𝑦𝑘 400
𝐴𝑠𝑤 100.48
𝜌𝑤 = 𝑆∗𝑏𝑤∗sin(𝛼) = 190×200×1 = 0.0026
The reinforcing bar shall be anchored so that the bond force is safely transmitted to the
concrete avoiding longitudinal cracking or transverse reinforcement shall be provided if
necessary. [ES EN 1992:2015 section 8.4.2]
lb,rqd = (∅𝟒)(𝒇𝒃𝒅
𝝈𝒔𝒅
) Equation 6-8
ղ1 is a coefficient related to the quality of the bond condition and the position of the bar
during concreting (ղ1 = 1 when good condition are obtained)
347.83
𝑙𝑏, 𝑟𝑞𝑑=(Ø/4) (𝛿𝑠𝑑/𝑓𝑏𝑑) =(16/4)× ( 2.295 ) =606.24mm
The design anchorage length, 𝑙𝑏𝑑 for tension reinforcement for Ø16
The design anchorage length, 𝑙𝑏𝑑 for compression reinforcement for Ø16
The clear distance between lapped bars should not be greater than 4 or 50mm
otherwise the length should be increased by a length equal to the clear space where
it exceeds 4∅ or 50mm.
The longitudinal distance of two adjacent laps should not be less than 0.3 times the
lap length, 𝑙𝑜.
𝟎. 𝟑𝜶𝟔 𝒍𝒃,𝒓𝒒𝒅
𝒍𝒐,𝒎𝒊𝒏 ≥ 𝒎𝒂𝒙 { 𝟏𝟓∅ Equation 6-11
𝟐𝟎𝟎𝒎𝒎
∅ 𝑙𝑜,𝑚𝑖𝑛 (mm)
8 130
10 160
14 230
16 260
20 320
24 390
Values of 𝛼1 𝛼2 𝛼3 𝑎𝑛𝑑 𝛼5 maybe taken from [ES EN 1992-1-1:2015 table 8.2] which is
described herein the appendix while the value of 6 = ( 1 )0.5 but 1 0.65lo .
25
Assume 50% of the bar lapped at appoint 6 1.4 [ES EN 1992-1-1:2015 table 8.3]
Detailing
7.1 Introduction
Column is a vertical or inclined structural member supporting the axial compressive load
with or without moment. The cross-sectional dimensions of the column are generally
considerably less than its height. It supports vertical loads from the floors and roof and
transmits this load to the foundation.
Spiral columns: where the main longitudinal bars are enclosed within closely
spaced and continuously wound spiral reinforcement.
Short columns:-are column with low slenderness ratios, i.e. it is relatively short and
stocky columns, invariably fail under ultimate loads with the material (concrete, steel;
reaching its ultimate strength, and not by buckling
Slender (long) columns:-are Columns with very high slenderness ratios in danger of
buckling accompanied with large lateral deflection under relatively low compressive
B.Sc. Final Year Project Page 75
Structural analysis and design of G+5 mixed used building
loads, and thereby failing suddenly. Here columns buckle and the additional moments
caused by deflection must be taken into account in the design.
The internal forces and moments may generally be determined by elastic global analysis
using either: -First-order theory, using the initial geometry of the structure, or Second-
order theory taking into account the influence of the deformation of the structure.
First-order theory may be used for the global analysis in the following cases:
(c) Design methods that make indirect allowances for second-order effects.
The sample column is column C-12 with cross-section 400 × 400𝑚𝑚 on 2nd floor
P = 1243.2𝑘N
Mo1 = 105.7083kN-m
Mo2 = −131.23kN-m
Mo1 = −71.9065kN-m
Mo2 =103.8292kN-m
Where: Mo1 and Mo2 are end moments and always Mo2 greater than Mo1.
Material property
𝐶25/30
𝐹𝑐𝑡𝑚 = 2.6𝑚𝑝𝑎
𝑆 = 400
𝐸𝑠 = 200𝐺𝑝𝑎
𝐸𝑐𝑚 = 31𝐺𝑝𝑎
Where: -
𝑓𝑦𝑑 347.826
𝐸𝑦𝑑 = = 2×105 = 1.739 × 10−03
𝐸𝑠
In the x direction
20𝐴𝐵𝐶
λlim = ……………………… [ES-EN 1992-1-1: 2015, Eqn.5.13N]
√𝑛
𝑀𝑜1 105.7083
𝒓𝑚 = = = −0.805
𝑀𝑜2 −131.23
𝒍𝒐
λ= ………………………………….…. [ES-EN 1992-1-1 : 2015, Eqn.5.14]
𝒊
k1 k2
o 0.5l
llo 1 * 1
0.5 k 1 0.5 k 2 [ES-EN 1992-1-1: 2015, Eqn.5.15]
..................
EI
(
)column
Ki l
2 EI
( l )beam
ℎ𝑏 3 400 × 4003
𝑰 − 𝑐𝑜𝑙𝑢𝑚𝑛 = = = 2.13 × 109 𝑚𝑚4
12 12
𝑏ℎ3 200×3003
𝑰 − 𝑏𝑒𝑎𝑚 − 𝑥 = = = 0.45 × 109 𝑚𝑚4 (for beams at top and bottom)
12 12
2.13×109
3.2
K1 = 2×0.45×109 2×0.45×109
= 1.85
( )+( )
5 5
2.13×109
3.2
K2 = 2×0.45×109 2×0.45×109
= 1.85
( )+( )
5 5
The dimension of the beams for K2 is the same as K1, thus K1 = K2 = 1.85
Effective length
𝑘1 𝑘2
𝑙𝑜 = 0.5𝑙√[1 + 0.5+𝑘1] × [1 + 0.5+𝑘2]
1.85 1.85
𝑙𝑜 = 0.5 × 3200√[1 + ] × [1 + ] = 2859.57𝑚𝑚
0.5 + 1.85 0.5 + 1.85
𝑙𝑜 𝐼 2.13×109 2859.57
𝜆= 𝑖 = √𝐴=𝑖 = √ 400×400 =115.379 𝜆 = 115.379=24.78 𝜆lim=52.09
𝑖
Therefore 𝜆<𝜆lim the column is short (Non-slender) thus, second-order effects can be
neglected.
In the y-direction
20𝐴𝐵𝐶
λlim = …………………………[ES-EN 1992-1-1: 2015, Eqn.5.13N]
√𝑛
𝑀𝑜1 −71.9065
𝒓𝑚 = = = − 0.692
𝑀𝑜2 103.8292
𝒍𝒐
λ= …………………………………..…. [ES-EN 1992-1-1: 2015, Eqn.5.14]
𝒊
k1 k2
o 0.5l
llo 1 * 1
0.5 k 1 0.5 k 2 [ES-EN 1992-1-1: 2015, Eqn.5.15]
..................
EI
(
)column
Ki l
2 EI
( l )beam
ℎ𝑏 3 400 × 4003
𝑰𝑐𝑜𝑙𝑢𝑚𝑛 = = = 2.13 × 109 𝑚𝑚4
12 12
𝑏ℎ3 200×3003
𝑰 − 𝑏𝑒𝑎𝑚 − 𝑥 = = = 0.45 × 109 𝑚𝑚4 (for beams at top and bottom)
12 12
2.13×109
3.2
K1 = 2×0.45×109 2×0.45×109
= 1.43
( )+( )
3 5.5
2.13×109
3.2
K2 = 2×0.45×109 2×0.45×109
= 1.43
( )+( )
3 5.5
The dimension of the beams for K2 is the same as K1, thus K1 = K2 = 1.43
Effective length
𝑘1 𝑘2
𝑙𝑜 = 0.5𝑙√[1 + 0.5+𝑘1] × [1 + 0.5+𝑘2]
1.43 1.43
𝑙𝑜 = 0.5 × 3200√[1 + 0.5+1.43] × [1 + 0.5+1.43]=2785.49mm
𝑙𝑜 𝐼 2.13×109 2785.49
𝜆= 𝑖 = √𝐴=𝑖 = √ 400×400 =115.37 𝜆 = =24.14 𝜆lim=49.75
𝑖 115.37
Therefore 𝜆<𝜆lim the column is short (Non-slender) thus, second-order effects can be
neglected.
Eccentricity calculation:
𝒍o
ea = 400 …………………….
2859.57
ea = = 7.14mm (in x-direction).
400
2785.49
ea = = 6.96mm (in y-direction).
400
In the X direction
𝑀𝑜1 105.70×106
eo1 = 𝑵ed = 1243.2×103 =82.02 𝑚𝑚
In x-direction
𝑀𝑜2 −131.23×106
eo2 = 𝑵ed = = −105.55𝑚𝑚
1243.2×103
𝑀𝑜1 −71.90×106
eo1 = 𝑵ed = 1243.2×103 = −57.83𝑚𝑚
In y-direction
𝑀𝑜2 103.82×106
eo2 = 𝑵ed = 1243.2×103 = 83.51𝑚𝑚
𝑒𝑡𝑜𝑡𝑎𝑙,𝑥 = 𝑒𝑎 + 𝑒𝑒 + 𝑒2
𝑒𝑡𝑜𝑡𝑎𝑙,𝑦 = 𝑒𝑎 + 𝑒𝑒 + 𝑒2
Since the column is non-slender in both directions the value of second-order moments (e2)
is very small and it is ignored.
Design loads: -
Msd,x 61.37×106
𝜇𝑠𝑑,𝑥 = fcd∗b∗h2 = 14.167×400×4002 = 0.067
Msd,y 50.18×106
𝜇𝑠𝑑,𝑦 = fcd∗b∗h2 = 14.167×400×4002 = 0.055
Ned 1243.2×103
𝑉𝑠𝑑 = fcd∗b∗h2 = 14.167×400×4002 = 0.0013 𝑠𝑎𝑦 0.0
𝑑′ 51
= = 0.127, 𝑠𝑎𝑦 0.1
ℎ 400
Using the above calculated parameters reading the mechanical steel ratio () from [Design
Aid ES EN 1992-1-2:2015] from biaxial interaction chart No.9
𝑑′
For = 0.1 𝑉𝑠𝑑 = 0.0 𝜇𝑠𝑑, 𝑥 = 0.067 𝜇𝑠𝑑, 𝑦 = 0.055
ℎ
=0.1
ω∗fcd∗b∗d 0.1×14.17×400×400
As, tot = = = 651.81𝑚𝑚2
fyd 347.83
0.1∗Ned
As, min = Maximum of { fyd
0.002 ∗ Ac
0.1×1243.2×103
= Maximum of. { 347.83 = 357.41𝑚𝑚2
2
0.002 × 400 × 400 = 320mm
The above is a sample calculation and the rest of the calculations are included in
the Appendix section.
8.1 Introduction
Foundation is one of the essential parts of the structure.it is defined as that part of the
structure that transfers the load from the structure constructed on it as well as its weight
over a large area of soil in such a way that the amount does not exceed the ultimate bearing
capacity of the soil and the settlement of the whole structures remains within a tolerable
limit. Foundation is the part of the structure on which the building stands.
Shallow foundation
Deep foundation
Shallow foundations: - are foundations situated beneath the lowest part of the structure
near to the ground level to distribute the structural load over a considerable base area at a
foundation bed. Since spread foundations (shallow foundations) are constructed in open
excavations they are termed an open foundation.
Combined footing
Strip footing
Individual or isolated footings: - they are used to support individual columns. Isolated
footings can be stepped type, simple type, or slope type, having projection in the base
concrete.to support a heavy load, reinforcement is also provided at the base. The
reinforcement is provided in the form of steel bars and is placed in both directions.
Subsurface condition
The pressure on the soil should not exceed the bearing capacity of the soil. The settlement
of the structure should be within the permissible limit.
Soil strength parameters (ϕ and C): ϕ is the angle of internal friction and C is cohesion.
Depth of footing the depth of embedment must be at least large enough to accommodate
the required footing thickness. The depth is measured from the lowest adjacent ground
surface to the bottom of the footing.
The required area of the footing subsequently the proportions will be determined using
presumptive allowable soil pressure and/or the soil strength parameters and C.
Structural consideration: the last stage in the design of the foundation is the structural
design. One should check the adequacy of the thickness of the footing and provide the
necessary reinforcement to withstand punching shear, diagonal tension (wide beam shear),
and bending moment.
The footing for a single column may be made square in the plan but where there is a large
moment acting about its axis it may be more economical to have a rectangular base.
The safe bearing pressure value is a serviceability value as it is used to control the
settlement of the foundation.
From frame analysis using ETABS, we have the following foundation column axial forces.
Area proportioning
The soil type is medium dense sand and gravel; the bearing capacity determined for the
soil is 300𝑘𝑝𝑎.
𝑀𝑋 147.602
𝑒𝑥 = = = 0.061
𝑃 2419.8784
𝑚𝑦 98.037
𝑒𝑦 = = = 0.041
𝑃 2419.8784
To calculate the stress at the four corners of the footing from the calculated dimensions
two conditions must be satisfied.
6𝑒𝑥 6𝑒𝑦
𝜎𝑚𝑎𝑥 = 𝑃⁄𝐴 × (1 + − ) ≤ 𝜎𝑎𝑙𝑙
𝐵 𝐵
𝑃 6 × 𝑒𝑥 6 × 𝑒𝑥
𝜎𝑚𝑖𝑛 = × (1 − − )>0
𝐴 𝐵 𝐵
Since both conditions are satisfied to take B=3.2 and the difference between the
eccentricity in both axes for both limit states are very small, therefore a square footing is
ideal i.e. B=L=3.2m is acceptable.
𝑀𝑥 141.4099
𝑒𝑥 = = = 0.046
𝑃 3128.8
𝑀𝑦 91.2153
𝑒𝑦 = = = 0.023
𝑃 3128.8
Now the stress at the four corners of the footing can be calculated from the ultimate loads
using the following equation.
𝑃 6 × 𝑒𝑥 6 × 𝑒𝑦
𝜎= × (1 ± ± )
𝐴 𝐵 𝐵
𝑃 6 × 𝑒𝑥 6 × 𝑒𝑥
𝜎𝑚𝑎𝑥 = × (1 + + )
𝐴 𝐵 𝐵
𝑃 6 × 𝑒𝑥 6 × 𝑒𝑥
𝜎𝑖𝑛𝑡1 = × (1 − + )
𝐴 𝐵 𝐵
𝑃 6 × 𝑒𝑥 6 × 𝑒𝑥
𝜎𝑚𝑖𝑛 = × (1 + − )
𝐴 𝐵 𝐵
𝑃 6 × 𝑒𝑥 6 × 𝑒𝑥
𝜎𝑚𝑖𝑛 = × (1 − − )
𝐴 𝐵 𝐵
𝑃
𝐴>
𝜎𝑎𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒
𝐴 = 2419.8784⁄300 = 8.066𝑚2
pu
Ultimate earth pressure, q where: Pu is the ultimate gravity load and A is the pad
u
A
area
𝑞𝑢 = 3128.8⁄10.24 = 305.55𝑘𝑝𝑎
Wide shear
The vertical shear force is the sum of the load acting outside the section considered.
Shear stress is checked at a distance d from the face of the column.
Shear stress is
𝑣 = 𝑉 ⁄(𝑙𝑑) ≤ 𝑉𝑅𝑑,𝑐
It is normal practice to make the base sufficiently deep so that shear reinforcement is not
required. The depth of the base is often controlled by the design for shear. If the shear
stress calculation indicates the need for shear reinforcement, the solution is to increase the
depth of footing until no shear reinforcement is required. The rule for members not
requiring shear reinforcement is covered in clause section 6.2.2 of the ES EN. From
equations (6.2a), (6.2b) and (6.3N) of ES EN 1992-1-1:2015].
200
𝑐𝑅𝑑,𝑐 = 0.18⁄𝛾𝑐 , 𝑘 = 1 + √ ≤2
𝑑
Axial load=3128.8kpa
Concrete cover=50mm
Pad dimension=2.5×2.5
Bar dimension=∅24mm
𝜙
𝐷 = 𝑑 − 𝑐𝑐 − ⁄2 𝐷 = 600 − 25 − 24⁄2 = 563
200
𝑐𝑅𝑑,𝑐 = 0.18⁄1.5 = 0.12 𝑘 = 1 + √563 = 1.596 < 2
𝐴𝑠𝑡
ρ= = 0.01
𝑏𝑤 ∙ 𝑑
1⁄
𝑉𝑅𝑑,𝑐 = [0.12 × 1.596(100 × 0.01 × 25) 3] ≥ (𝑉𝑚𝑖𝑛 =0.035× 1.5961.5 × √25)
= 0.56𝑀𝑝𝑎 ≥ 0.353𝑀𝑝𝑎
𝑉𝐸𝑑⁄
Vertical shear, 𝑣𝐸𝑑 = 𝑙𝑑 ≤ 𝑉𝑅𝑑,𝑐
= 3.2 × (1.6 − 0.2 − 0.563) × 305.55 − (0.563 × 3.2 × 0.4 × 25) = 800.37𝑘𝑁
Punching shear
𝑢𝑑 =Perimeter of the column= 2(𝑐1 + 𝑐2 ), 𝑐1 and 𝑐2 are side dimensions of the column.
𝑢𝑑 = 4 × 0.4 = 1.6
𝑢1 = 2 × (𝑏 + ℎ) + 4 × 𝜋 × 𝑑
Reinforcement
1 2
𝑀𝐸𝐷 = × (𝐵⁄2 − 𝐶 ⁄2) × 𝑞𝑢
2
𝑀𝐸𝐷 = 0.5 × (1.6 − 0.2)2 × 305.55 = 299.44𝑘𝑁. 𝑚
𝑀𝑠𝑑
𝜇𝑠𝑑 =
𝑓𝑐𝑑 × 𝑏 × 𝑑 2
299.44 × 106
= = 0.038
25 × 1000 × 5632
1 − 60 × 𝜇𝑠𝑑
𝑘𝑧 = 0.5(1 + √ )
17
1 − (60 × 0.038)
= 0.5 × (1 + √ ) = 0.637
17
𝑏. 𝑎𝑠 1000 × 452.38
𝑆= = = 188.8𝑚𝑚
𝐴𝑠 2399.8
Detailing
9.1 Conclusion
This project gives us to understand the theoretical concept that we learn in the class
towards practical with related to structural design and such project gives for us a great
appreciation for the future career after graduation in civil engineering especially, to
construct and design the different building.
To be safe and economical structural design, social and environmental factors as well as
the function of the building should be studied. For design and analysis of this G+5 mixed-
used building is based on the limits set by ES EN 1992: 2015 and engineering judgments.
On analysis of this project, many compliable calculation works were compiled with
ETABS 2019 software and the result was compared with hand calculation
For the design of the member, the initial assignment of the load is basic for the whole
design in the selection of design critical members and load combination.
Finally, this project leads us to read different reference books, ES EN manual, and ETABS
software to capture knowledge on design and analysis of the safe and economical structure.
That means it enables us to apply theoretical knowledge to practical one and also it makes
us develop engineering judgments and decision
9.2 Recommendation
Now, days it is well known that analysis and design of any engineering structure are
supported with design software, as we recommend that it would have been better if design
software course is given for civil engineering student as a subject in order to make the
students familiar with different software.
Since the condition is not suitable to meet each other because of pandemic disease (corona
virus) this affects our working environment.
REFERENCES
ES EN 1992:2015 Actions on structures-part 1-1: General Rules and Rules for Buildings
APPENDIX A
STOREY COLUM B(mm) H(mm) AREA( COMB P(kN) M2- M3- I(mm4) i(mm)
N ID mm2) 2(kNm) 3(kNm)
TOP BOT TOP BOT
ROOF c12 400 400 160000 ENVELOP - -33.9458 34.675 -36.112 25.773 213333 115.470
LEVEL Max 163.13 3333 0538
75
5TH c12 400 400 160000 ENVELOP - -36.3218 31.757 -46.744 40.904 213333 115.470
FLOOR Max 686.00 3333 0538
07
4TH c12 400 400 160000 ENVELOP - 64.018 53.913 -67.734 56.688 213333 115.470
FLOOR Max 1190.1 3333 0538
928
3RD c12 400 400 160000 ENVELOP - -83.15 67.283 -89.451 70.106 213333 115.470
FLOOR Max 1691.3 3333 0538
837
2ND c12 400 400 160000 ENVELOP - -131.23 105.7 -71.906 103.829 213333 115.470
FLOOR Max 1243.2 3333 0538
205
1ST c12 400 400 160000 ENVELOP - -152.62 137.01 -91.429 100.296 213333 115.470
FLOOR Max 1493.1 3333 0538
99
GROUND c12 400 400 160000 ENVELOP - -145.598 139.02 - 93.888 213333 115.470
FLOOR Max 2912.2 100.186 3333 0538
133
ROOF LEVEL c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
2 2 7
5TH FLOOR c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
2 2 7
4TH FLOOR c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
2 2 7
3RD FLOOR c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
2 2 7
2ND FLOOR c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
2 2 7
1ST FLOOR c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
2 2 7
GROUND c12 1.85185185 1.85185185 1.43790849 1.437908497 2859.84252 2787.183811 24.76696273 24.13771985
FLOOR 2 2 7
STORE COLU M01X M02X M01Y M02Y rmx rmy n λlimx λlimy slendernes
Y MN ID s
X-dir Y-
dir
ROOF c12 -33.9458 34.675 - 36.11 - - 0.0719707 153.78383 138.55601 short sho
LEVEL 25.77 2 0.9789704 0.7136962 33 23 32 rt
3 4 78
5TH c12 -31.757 36.321 - 46.74 - - 0.3026402 72.064351 72.085088 short sho
FLOOR 8 40.90 4 0.8743234 0.8750641 47 96 72 rt
4 09 79
4TH c12 53.913 64.018 - 67.73 0.8421537 - 0.5250727 18.231417 53.916032 short sho
FLOOR 56.68 4 69 0.8369208 04 95 38 rt
8 96
3RD c12 -7.6055 19.65 - 89.45 - - 0.7461811 37.207552 44.279640 short sho
FLOOR 70.10 1 0.3870483 0.7837363 34 07 02 rt
6 46 47
2ND c12 -105.7 131.23 - 103.8 - - 0.5484667 52.099357 49.751393 short sho
FLOOR 71.90 29 0.8054560 0.6925425 27 79 23 rt
6 69 46
1ST c12 -137.01 152.62 - 100.2 - - 0.6587487 49.289353 49.552559 short sho
FLOOR 91.42 96 0.8977198 0.9115916 65 64 5 rt
9 27 89
GROU c12 -139.02 145.59 - 100.1 - - 1.2847697 36.069762 35.829500 short sho
ND 8 93.88 86 0.9548208 0.9371369 55 4 07 rt
FLOOR 8 08 25
ROOF c12 -33.9458 34.675 - 36.11 7.1496062 85.020304 6.9679595 88.543713 92.169911 95.511672
LEVEL 25.77 2 99 96 28 13 26 65
3
5TH c12 -31.757 36.32 - 46.7 7.149606 21.17887 6.967959 27.25594 28.32847 34.22390
FLOO 18 40.9 44 299 052 528 886 682 839
R 04
4TH c12 53.913 64.018 - 67.73 7.1496062 50.391835 6.9679595 22.764042 57.541441 29.732002
FLOOR 56.68 4 99 68 28 93 97 46
8
3RD c12 -7.6055 19.65 - 89.45 7.1496062 5.1719784 6.9679595 21.154513 12.321584 28.122473
FLOOR 70.10 1 99 22 28 9 72 43
6
2ND c12 -105.7 131.23 - 103.8 7.1496062 42.222598 6.9679595 33.406463 49.372204 40.374422
FLOOR 71.90 29 99 49 28 29 78 82
6
1ST c12 -137.01 152.62 - 100.2 7.1496062 40.884034 6.9679595 26.867416 48.033641 33.835376
FLOOR 91.42 96 99 88 28 87 18 4
9
GROU c12 -139.02 145.59 - 100.1 7.1496062 19.998260 6.9679595 13.760805 27.147866 20.728764
ND 8 93.88 86 99 43 28 23 73 75
FLOOR 8
STOREY COLUMN msd,x msd,y vsd w d" As.t(mm^ As.min(m as(mm^2 As.provided(m no. of
ID 2) m^2) m^2) bar
ROOF c12 0.01658 0.01718 0.00017 0.1 0.1 651.5941 320 201 804.24 6
LEVEL 384 5113 9927
5TH c12 0.02143 0.02589 0.00075 0.1 0.1 651.5941 320 201 804.24 6
FLOOR 3343 383 6601
4TH c12 0.07553 0.03902 0.00131 0.1 0.1 651.5941 342.13428 201 804.24 6
FLOOR 3601 8657 2682 46
3RD c12 0.02298 0.05246 0.00186 0.1 0.1 651.5941 486.20723 201 804.24 6
FLOOR 5335 1148 5453 65
2ND c12 0.06769 0.05536 0.00137 0.1 0.1 651.5941 357.37769 201 804.24 6
FLOOR 7529 0069 1167 24
1ST c12 0.07910 0.05572 0.00164 0.1 0.1 651.5941 429.23681 201 804.24 6
FLOOR 5254 2531 6872 92
GROUND c12 0.08719 0.06657 0.00321 0.1 0.1 651.5941 837.14841 201 1206.36 6
FLOOR 6895 9225 1924 34