A Thesis submitted to the Faculty of the Graduate School of the University at Buffalo, State
University of New York in partial fulfillment of the requirements for the degree of
(Master of Science)
It is with immense gratitude that I acknowledge the support and help of my advisor, Dr.
HyungSeon Oh, who continually and convincingly conveyed a spirit of adventure in regard to this
research and his teaching. I would like to thank my committee members, Dr. Albert Titus and Dr.
Jonathan Bird for their guidance and persistent help without which this dissertation would not have been
possible.
I am grateful to the faculty of University at Buffalo, SUNY and my fellow Buffalo Energy
Science and Technology group members for the immense learning opportunities. I will remain deeply
indebted to my parents Dr. Swati Pachpinde and Dr. Eknath Pachpinde, my siblings and dear friends for
ii
Abstract
Measurement of synchrophasors can open up new avenues for improved control and
stability of the power system. Phasor Measurement Unit (PMU) can measure positive sequence
voltages and currents along with frequency and rate of change of frequency. They can directly
measure the state of the system thus eliminating the need for state estimation altogether, if the
system is completely observable. For this to become reality a large number of PMUs need to be
deployed that would call for large upfront investments. Another possibility to ensure large scale
Conventional PMUs which use global positioning system (GPS) for time synchronization
have some limitations. This thesis proposes a novel concept of PMU using network time protocol
(NTP) to synchronize the local oscillators of all the PMU. NTP is an attractive alternative as it
uses existing LAN lines for internet communication and the existing infrastructure and has time
accuracy in milli-seconds (lower than that of GPS). It does not require, however, any major
infrastructural changes. It is thus suitable for monitoring systems that do not require very precise
time stamping. We claim that a distribution network is an ideal candidate for such PMUs.
Currently distribution networks have sparse monitoring by supervisory control and data
acquisition (SCADA) system which has time synchronization window of 2-3 seconds.
This conceptual PMU is elaborated in the following text and its feasibility is evaluated.
Comparative measurement accuracy and cost of this PMU is discussed in detail in comparison
with the conventional PMUs. The new PMU offers significant benefits in terms of monitoring
and controlling the distribution network. One application considered in this study is fault-
location detection.
iii
List of Figures
Figure 1: Convention for synchrophasor representation. Taken and modified from Ref [17]. ........... 9
Figure 2: A sinusoid with a frequency is observed. The phase angle Φ increases uniformly in
relation to the frequency difference, (f – f0) ...................................................................................... 10
Figure 3: Generic block diagram of PMU ......................................................................................... 11
Figure 4: Typical synchrophasor installation at substation ............................................................... 12
Figure 5: Internet based PMU block diagram ................................................................................... 17
Figure 6. Diagrammatic depiction of NTP strata .............................................................................. 18
Figure 7: Example of Synchronization Topologies of NTP clocks ................................................... 19
Figure 8: Measuring Delay and Offset .............................................................................................. 19
Figure 9: Network Time Protocol ...................................................................................................... 20
Figure 10: Generic block diagram of Gadget Box ............................................................................ 22
Figure 11: Block diagram of the prototype design for the proposed PMU ....................................... 23
Figure 12: A distribution network substations with amount of monitoring present .......................... 27
Figure. 13. Format for files transmitted from and to PMUs. The numbers below the boxes indicate
length of the word in bytes. ............................................................................................................... 28
Figure 14. Offsets between the local clock and the PPS GPS ........................................................... 30
Figure 15: A single-line-to-ground fault on phase A ........................................................................ 39
Figure 16: Search for possible fault locations ................................................................................... 40
Figure 17: One-line diagram for a 14-Bus distribution feeder with two measurement points at
Bus-1 and Bus-5, respectively .......................................................................................................... 40
iv
List of Tables
v
Table of Contents
Acknowledgements _________________________________________________________________ ii
vi
5.2 Comparing conventional and proposed PMU performance _______________________ 27
5.2.1. Time synchronization accuracy ____________________________________________ 27
5.2.2. Measurement accuracy ___________________________________________________ 32
References _______________________________________________________________________ 43
vii
Chapter 1. Introduction
Power demand is increasing enormously and the power system is not equipped to
accommodate this change. The availability of reliable electric power supplies is an essential
precondition for the functioning of modern economies [1]. The U.S. Department of Energy plans
to address this challenge of growing energy demand by promoting distributed energy resources
and renewable energy integration. Its Renewable and Distributed Systems Integration (RDSI)
program recently selected nine projects to demonstrate 15% peak-load reduction on a distribution
policy and regulations on greenhouse gas emissions are developed and implemented by federal
authorities, individual states and provinces throughout North America [3]. Maintaining bulk
power system reliability in such a scenario will be challenging in the near future. Protection-
system misoperations, particularly incorrect settings and circuit breaker failure have been listed
amongst the most impactful causes for initiating system disturbances creating major stability
issues [3].
Real-time monitoring at all levels of the power grid will play a significant role in
addressing the situation. Phasor measurement unit (PMU) can provide voltages and currents
along with frequency and rate of change of frequency in real-time with high precision and
accuracy. It has the potential to improve system controls, event analysis, fault detection and
determining the location of fault through situation awareness tools and monitoring capability. It
can also provide tools for supervising the protection equipment to prevent false trips and its
1
consequences. With this information, control and protection of the power system can be
significantly improved.
The Department of Energy anticipates that once all of the Recovery Act (2009)
synchrophasor projects have been completed, there will be at least 1,043 networked PMUs in
place (compared to 166 in 2010) [4]. This number is insignificant compared to the extensive
transmission network in the US. To utilize all the benefits of this technology, it is necessary to
deploy PMUs at a large scale that would make the network completely observable. PMUs are
required at approximately one-third of the Buses to obtain complete observability [5]. However,
their integration costs are too high to deploy them on a large scale. This high cost is closely
The thesis proposes a novel idea for an alternative design of PMU by using existing
technologies such as the time distribution network of the internet and phase locked loops (PLLs).
It eliminates the need to have a dedicated communication network for time distribution but banks
on the existing network provided by the internet. The proposed PMU would be suitable for real-
time monitoring of distribution networks for its low costs and the non-necessity of a new
standard are discussed in Chapter 2 and 3 followed by the concept of the proposed internet based
PMU in Chapter 4. The evaluation of this proposed PMU in comparison with conventional PMU
and overview of its applications in distribution network are considered in Chapters 5 and 6.
2
Chapter 2. Background and Literature Survey
The concept of PMU originated from Symmetrical Component Distance Relay (SCDR)
as a part of dynamic relaying technology. PMUs were first realized in 1988 by Dr. Phadke and
Dr. Thorpe. Their paper outlined new measurement techniques for voltage phasors, frequency
and rate of change of frequency [7]. They investigated the possibility of commercially available
WWVB (Standard Time and Frequency Station, 60KHz, Fort Collins, Colorado) receiver
integrated as the source of time synchronization [7] but eventually finalized on using a GPS
receiver due to its accuracy and reliability. GPS adds a precise time stamp to the quantities and
sampled data for computer relaying applications. Thus PMUs equipped with GPS could measure
state of the power system with high speed, great accuracy and precession [5].
Energy Management System (EMS) based on state estimation came into being only after
the 1965 catastrophic failure of the North- Eastern power grid in North America [8].
Determining the state of the system thus became important for all applications of control. It was
not possible at that time to measure the state of the power system but only to estimate the state
from other measurements. It was recognized that the state obtained in this manner at best
described a quasi-steady state approximation to the actual state of the network [8].
When PMUs became commercially available for the first time in the early 1990s, its
applications were limited to being used as digital system disturbance recorders (DSDRs). At this
stage, even though their use in protection and control was theoretically established, PMUs were
continued to be used only as DSDRs. In July 1993 during the Comanche Peak load rejection test
3
in Texas, frequency measurements revealed the presence of an electromechanical wave
propagating through the system. Such data recordings led to the development of the Frequency
Monitoring Network (FNET) that shed light on many revelations about these electromechanical
waves [9].
After the blackouts of 1996 and 2003, PMU technology was highly encouraged for use
in all utilities. This led to the creation of the Eastern Interconnection Phasor Project (EIPP), now
known as North American Synchrophasor Project (NASPI). The EIPP performed the first real-
time wide-area monitoring in the United States. PMUs are expensive and their costs depend on
The need for real-time monitoring of power system has led to increased deployment of
PMUs increased in the United States. In China, about 400 PMUs were installed at the substations
and power plants of 500KV and 330KV voltage levels by 2007 [10]. According to the 11th five-
year plan for the Chinese power grid of China, all substations operating above 300kV will have
PMU monitoring. India and other European countries are also keenly pursuing PMU technology.
PMUs have been in use for a long time as DSDR in wide area monitoring. This section
provides a general overview of other applications of PMU technology mainly in state estimation,
4
State estimation of the system is performed today from the measurements of power
injection, voltage values from transformers, etc. This estimation algorithm is based on the
assumption that the state of the power system remains static when scanning takes place. The
system can look completely different by the time the state is estimated. This estimated state is
used as the input data for many other calculations and applications like economic dispatch,
PMU has the capability to directly measure the state of the system i.e. voltage at all the
Buses equipped with PMUs. If the entire system becomes observable by PMU measurements,
the need for state estimation would be eliminated altogether. However, the high costs of PMU
and large network of Buses makes it practically impossible to introduce PMU technology into
the power systems, at least in the near future. Therefore, the need arises for algorithms to
combine the measurements of PMU and existing monitoring systems such as SCADA systems
Every line has distance protection of different levels. Zone 1 relays are present at each
end of the line and protect 80% of the line. Zone 2 protects 100% of the line and about 20% of
the adjoining line. Zone 3 covers 100% of the line and more than 50% of the adjoining line. This
means these relays protect the connected line also to some extent and thus act as backup
protection for the lines. Backup relays used for providing Zone 2 and Zone 3 protection are
prone to false tripping. This can be catastrophic for a system operating on the edge of its stability
limits. PMUs at Buses where relays are connected can act as supervisory systems. If the relays
see a fault but none of the PMUs indicate it, then it can be ruled out as a false trigger.
5
Transients occurring in the system may cause the generator to loose synchronization, but
perform this detection and also to take appropriate tripping and blocking decisions. These relays
are set according to transient analysis. With new lines being added to the system, theses relays
keep readjusting the relay settings dynamically. A reliable prediction algorithm should be
[9, 14]. This is a developing field and much work needs to be done in this respect.
There are two ways in which the relay can fail to protect the system. It trips when it
should not (a false trip) or it does not trip when it should trip. Two types of reliability have been
designated as “security” and “dependability” respectively [9]. The system more secure if some or
the other relay always clears fault but leads to increased number of false trips. The system is
more dependable if relays operate conservatively and only clear faults that are seen with
certainty. The protection system of today is more secure than dependable. We can maintain the
balance between security and dependability with PMU data which allows the process to be
adaptive.
Loss of mains is a term describing a situation when one or more generator unit gets
separated from the system and is also called as islanding. Loss of mains can be detected more
accurately by using the phase angle difference method. Anti-islanding techniques based on the
rate of change of phase angle (ROCOPA) are being explored. PMUs can be implemented at
distributed generation (DG) terminals (or at a strategic location within a potentially islanded
6
2.2.3 Power system control
With real time data, power system control finds significant benefit. Control can now be
based on remote quantities. Wide-area measurements allow the system to control insecure
situations without employing continuous feedback [14]. In the case of such situations, control
actions like reconfiguring the network to ensure the demand is met or curtailed can be taken
remotely. Reference [16] describes the incorporation of synchrophasor measurements into new
system integrity protection schemes (SIPS). PMU measurements enhance robustness of the
system by retaining local control signals while additionally providing supervisory signals. Such a
redundancy in the system control would be indispensable for fine control of the system even
7
Chapter 3. Theory of conventional PMU
A thorough study of conventional PMU technology is essential to lay the foundation for
the proposed concept of PMU. Understanding the limitations and challenges of conventional
PMUs provide motivation and room for improvement. The chapter also discusses the
3.1 Synchrophasors
commonly used for AC power system analysis. If the sinusoidal Equation is represented in
Equation (3.1):
x (t ) = X m cos(ωt + φ ) (3.1)
Xm Xm
X = e jφ = (cosφ + jsin φ ) = X r + j X i (3.2)
2 2
Here, Xm /√2 is the root mean square value of the waveform and φ is the phase angle.
Phasors represent a sinusoidal waveform taking into consideration the phase difference of
the measured waveform with respect to a predefined reference so that two waveforms are
directly compared with respect to the same reference. Synchrophasors use coordinated universal
time (UTC) as an absolute time reference. If UTC is used as a reference for all phasor
measurements globally then these measurements can directly be compared irrespective of the
locations of sampling.
8
The synchrophasor representation of the signal x(t) in Equation (3.1) is the value X in
Equation (3.2) where φ is the instantaneous phase angle relative to a cosine function at the
nominal system frequency synchronized to UTC [17]. One pulse per second signal (PPS)
generated by some very precise clocks which trace UTC is used as reference for sampling the
waveform.
Figure 1: Convention for synchrophasor representation. Taken and modified from Ref [17].
Figure 1 illustrates how PPS signal is used as a reference to measure phasors. If the PPS
signal coincides with the peak of the measured waveform, the phase difference is zero hence the
Xm
X = (3.3)
2
For the second case, where the phase difference between the reference peak and the
Π
Xm −j 3
X= e (3.4)
2
9
A power system hardly operates at its fundamental or nominal frequency. If frequency f ≠
f0 and f < 2f0, where f0 is the fundamental frequency of a sinusoidal wave, the observed phasor
X2, X3, … Xn, …}} will change uniformly at a rate of 2π (f – f0) T0, where T0 = 1/ f0 and, as shown
Figure 2: A sinusoid with a frequency is observed. The phase angle Φ increases uniformly in
This section will talk about how a PMU measures synchrophasors and will describe a
generic form of a conventional PMU. Since different types of PMUs are manufactured,
manufactured it is
important to understand such a generic model. PMU can measure synchrophasor along with the
frequency and rate of change of frequency (ROCOF), and the measurements are also time
10
Figure 3: Generic block diagram of PMU [5]
As shown in Figure 3,
3 the measured analog inputs are stepped down for electronic
components using instrument transformers,, typically within the range of ±10 volts.
volts These are
hardwired to the Bus or the line from which waveform is collected for measurement (Figure 4).
All three phase measurements of current and voltages are used to derive positive, negative and
power of the signal without distorting the waveform. These signals are then conditioned
c by
sampling frequency in order to satisfy the Nyquist criterion [5]. Higher cut
ut-off frequency may be
used for a higher sampling rate, inn such case a digital decimation filter may be used to
downconvert
convert the higher sampling rate to lower, thus providing digital anti
anti-aliasing [5]. These
relative magnitudes of the different signals are practically unchanged at various weather
conditions [5].
11
Figure 4: Typical synchrophasor installation at substation [18]
GPS provides a 1 PPS waveform received anywhere on earth within 1µs of each other.
Time precision of nanoseconds may be achieved using GPS. These pulses are used to
synchronize the local oscillator to sample the analog input in the Analog-to-Digital (ADC)
converter. The sampling rate is determined by the local oscillator. Oversampling the data helps
determine the phasor with better precision as the estimation accuracy increases. GPS also
provides a time stamp to the measurements evaluated using the microprocessor. These time
stamps make it possible to index and align the data coming from various PMUs. The time-stamps
are created from two of the signals derived from the GPS receiver.
The phasor is evaluated and time-stamped in the microprocessor unit. This data is then
communicated to a common Phasor Data Concentrator (PDC) that is the next hierarchical unit of
PMU architecture. At the PDC level, the data is time aligned, and system state is determined and
12
The communication requirements of a network of PMUs depend on the rate of sampling
to determine the bandwidth of communication required. The data acquired from PMU may be
made compact instead of raw data being reported. At PDC level the snapshot of the system can
ROCOF measurements under all operating conditions [17]. It also provides format of time tag
and other synchronization requirements for implementing PMUs. According to this standard, the
performance of a PMU can be estimated by the reliability and accuracy of its time source capable
of tracing coordinated universal time (UTC). The time tag provided should clearly trace UTC
The standard requires value of total vector error (TVE), frequency error (FE), and
ROCOF error (RFE) to be within the required limits set by the standard. TVE is given by:
Here, X’r(n) and X’i(n) are the estimated value of real and imaginary component of the
phasor and Xr(n) and Xi(n) are the theoretical values of the input signal at the instants of time (n)
[17]. The allowable limit for TVE is 1% which translates to a phase error of 0.57 degrees (0.01
radian) by itself and a time error of ±26 µs for a 60Hz system and ±31 µs for a 50Hz system [17].
given by:
13
FE = = f true − f measured (3.6)
ROCOF is affected by the instability of the time source and can be given by:
df df
REF = = − (3.7)
dt true dt measured
The synchrophasor, frequency and rate of change of frequency are measured at the same
14
Chapter 4. New conceptual internet based PMU
GPS is integrated in conventional PMUs for providing precise time synchronization. This
requires all the remote units to be located in points from where at least four GPS satellites must
be seen at every moment [20, 21]. Additionally, in terms of capacity for communication, the
GPS system itself cannot provide communication capability for PMU. Therefore, additional
use a communication network to distribute time like the Precision Time Protocol (PTP) [20- 25].
This is achieved by using a network of dedicated time servers which communicate with each
other via messages to synchronize time. PTP was introduced in IEEE 1588- 2002, but requires
that the substation be upgraded in accordance with the IEC 61850 standards. It is not always
economically and physically viable to do so because of the dedicated hardware required solely
Both designs yield high precision and high resolution in time measurements that are
necessary for monitoring the status of transmission networks. A PMU with a lower precision in
time measurements might be acceptable for distribution networks. Our objective is to design a
PMU having lower cost but accurate enough to monitor distribution networks. We realize that it
is important to maintain high resolution rather than high precision in the time measurements. The
main blocks or components of the proposed internet based PMUs are discussed in the following
section along with the overview of the concept. The subsequent sections will talk about the
mechanism to synchronize time using NTP in detail and the requirements of the same in terms of
15
hardware and software. The time synchronization accuracies and the mathematical analysis
While the proposed PMU replaces GPS time with internet time, the working of the
system remains essentially identical to that of conventional PMUs. Measured analog inputs are
collected from the secondary of the instrument transformers. These signals are then conditioned
using anti-aliasing filters to satisfy the Nyquist criterion as in a conventional PMU. NTP over the
internet network will now provide one PPS. This signal will lock the local oscillator to UTC time
and improve synchronization of the master or reference clock with the local oscillator. A method
to obtain PPS signal is by the addition of a hardware component called a “gadget box” that can
be connected to the PLL. The gadget box is capable of receiving a PPS signal from GPS present
at the server level via the ethernet/internet network. The various methods to obtain the PPS
signal using NTP are described in detail in the subsequent sections. Time stamps are provided
by NTP network, and the time tagging of data takes place in the microprocessor after the data is
A local clock signal of high frequency acts as the reference for sampling the analog
signal in ADCs with high sampling rate. Oversampling leads to more accurate phasor estimation
[5]. Here oversampling is done mainly to compensate for the low (as compared to GPS)
16
Figure 5:: Internet based PMU block diagram
The phasor data obtained from ADC is processed in the microprocessor unit and
magnitude, phase, frequency and rate of change of frequency of the signal is gained and time
made by the precise clocks present on these satellites and PPS signal generate
generated by these clocks.
There are two types of clocks present in NTP, the master clock or reference clock and the
slave clock or end device clock. The reference clock is typically a very precise clock,
clock such as
17
which synchronize their time in accordance with this reference clock. These secondary servers
representing the active synchronization paths and direction of timing information flow
flow; and the
where the line marked ‘x’ denotes line which is “out of service” [27- 31].
18
Figure 7: Example of Synchronization Topologies of NTP clocks [27- 31]
the time-stamps are T1, T2, T3 and T4, then the offset ( σ ) and delay ( δ ) of time assuming T3 > T2
a+b
δ = a+b and σ= (4.1)
2
timestamp T4 is determined upon arrival of the message. Thus, both peers A and B can
independently calculate delay and offset. Numerous clocks are available to be synchronized to
the system clock but a clock-selection algorithm determines which clocks have the best accuracy.
These offsets from a system of peers are combined using weighted-average and act as input to
In the PLL the combined effects of the filtering, selection and combining operations are
to produce a phase-correction term, which is processed by the loop filter to control the voltage-
controlled oscillator (VCO) frequency. The VCO furnishes the phase (timing) reference to
produce the timestamps used in all timing calculations [27- 31]. The voltage controlled oscillator
is the system clock in the end device. Figure 9 shows a schematic overview of the system.
A PPS signal is essential to maintain the synchronization between our system and
absolute time. With the loss of PPS signal the system clock may drift away from UTC and error
in time will get accumulated. A PPS signal can be obtained by using only NTP software or a
combination of hardware and software. One method is to use the ASCII timecode which requires
20
only software and can provide PPS with accuracy of 1ms. ASCII timecode can be interfaced with
PLL and a local oscillator using RS-232 or RS-422 interface. For the PPS signal to be interfaced
with PLL some bridge will be required that converts data according to the RS232 protocol, to the
form required by PLL. The accuracy of ASCII timecode might not be acceptable for our PMU.
We propose to use a combination of hardware and software that can provide better accuracies.
The proposed PMU uses ‘gadget box’ to provide the PPS synchronization signal. It can
be used to synchronize the NTP time to one PPS signal generated by any master clock, either
GPS or the radio clock present at the sever level. This PPS signal helps to align the slave time
and maintain synchronization with the reference clock. The combination of PLL, NTP and
gadget box can provide precision control of the local oscillator within 1µs [27].
The NTP host can derive the time of the day, and day of the month from peers but the
PPS signal helps it remove jitter and is thus essential for better synchronization [27- 31]. In
version 4 of NTP, NTPD allows end users to specify up to 9 NTP servers to synchronize from
and it classifies the servers according to their stratum. This provides a way to maintain
synchronization with other PMUs in the network even of the absolute time synchronization is
lost [20]. So even without the time-stamps we can make synchronized measurements and use a
A PPS signal may also be derived from the IRIG- B signal produced by numerous radio
instrumentation recorders in the early days of the U.S. space program. The result can always be
21
4.2.2.1 Gadget Box
The gadget box includes a level converter and pulse generator that turns the PPS signal
on-time
time transition into a valid character. The character generated for each PPS pulse is
acts as the synchronization reference input for the system. This signal is then conditioned using
bandpass filters to avoid aliasing effects. A TTL (Transistor Transistor Logic) pulse of specific
width is generated (commonly the width is 26µs) from this signal. Using a TTL to EIA
(Electronic Industries Alliance) converter circuit i.e. EIA level converter, EIA output is obtained
which can then be directly used as the PPS signal [33].. EIA is a standard defining the electrical
local networks
etworks and communications channels.
channels
Dr. HyungSeon Oh, Dr. Albert Titus and their graduate students is presented here. The design is
in its initial stages and will help to give a rough idea of the system being proposed.
22
Figure 11:: Block diagram of the prototype design for the proposed PMU
A Linux or windows machine will be used to obtain NTP time using ntp daemon and
ASCII timecode software to obtain the PPS signal. Too use this data as the input for PLL, some
bridge will be required for interfacing. Here LPC1768 is used as it can interface data from
RS232 port and give out clock signal. PLL will lock this input clock signal (OCLK) and provide
a synchronized by higher frequency clock signal as output (NCLK). This output clock signal will
to synchronize the output clock and the time obtained from ntpd to generate time stamps at
microprocessor level. The cost breakdown of building this prototype is indicated in table 1:
1
23
Component Estimated Cost ($)
PLL 3 to 7
ADC 6 to 20
FPGA 20
Gadget Box
Memory (8GB) 70
The costs discussed above are the component costs only. Additional cost will be required
for fabrication and labor [33- 47]. Since the PLL that will be used to lock the PPS signal is not
commercially available, the costs quoted here are for a regular PLL.
The motivation of this thesis is to develop a new PMU that is substantially cheaper to
implement and does not require additional infrastructure. This PMU would still be accurate
24
enough to be used in distribution networks. Chapter 5 will establish clear goals and methods for
systematically evaluating the performance of the internet based PMU. The proposed PMU will
be compared with the conventional PMU based on the requirements of the synchrophasor
standard described in this chapter and monitoring requirements of the distribution networks.
25
Chapter 5. Evaluation of the proposed PMU versus conventional PMU
5.1 Introduction
A low cost PMU solution was proposed in the preceding chapter. This proposed PMU
banks on the existing network of NTP servers for time synchronization thus largely bringing
down the cost of the required communication infrastructure. NTP has been in use for a long time,
and the performance is nearly perfect for the PMU time synchronization. Using NTP, it is not
necessary to add or change any major construction and equipment. The common time
synchronization equipment can have the interface for NTP, and the cost is very low.
The precision provided by NTP synchronization however, might not be sufficient for
monitoring of transmission networks. Distribution network on the other hand has SCADA
monitoring only at HV/MV substations i.e. primary substation and only Boolean data from
sectionalizers etc. at secondary substations [32]. Figure 12 shows a typical distributions network.
In SCADA, data is not synchronized at all but rather sent over a window of a couple of
seconds and assumed to be synchronized. Therefore, NTP would be an attractive solution for
real-time monitoring as it is better than SCADA, and close to the performance in conventional
26
Figure 12:: A distribution network substations with amount of monitoring present
This section concentrates on comparing the performance of the proposed internet based
synchronization accuracy and accuracy of measurement of data. The objective is to justify the
use of such a system for monitoring distribution networks and to establish the adequacy of
5.2.1. Time
ime synchronization accuracy
synchronization is not required for real time monitoring of distribution networks. To date, too
27
much emphasis hass been put on the issue of synchronization accuracy
curacy with consideration of
varied needs.
GPS provides very precise timestamps that consist of data, configuration, and header
files. The Header file is a human readable file which carries information about who has produced
the data and he may wish to share it. The configuration and data
ata files are machine readable files
with fixed formats. The data files carry the actual phasor data.
As shown in Figure 133, the first word of 2 bytes is for synchronization of the data transfer
(SYNC).. The second word defines the size of the total record (FRAME SIZE),
SIZE) the third word
identifies the data originator uniquely (IDCODE),, and the next two words provide the “second of
century” (SOC) and the “fraction of a second” (FRACSEC) at which the data is being reported.
The length of the Data words which follow FRACSEC depends upon the specifications provided
Figure. 13.. Format for files transmitted from and to PMUs. The numbers below the boxes
GPS receives GPS time which is different from UTC in the respect that leap seconds are
not present. These are added at the GPS receiver level and the time output thus traces UTC. The
Another hindrance for using GPS on a large scale is the communication requirement of
GPS as it does not have communication capabilities. Instead, it has to be integrated with some
communication network and having a dedicated communication system ensures better accuracy
but introduces extensive monetary and time investments. The report on DOE experience with
Recovery Act Synchrophasor Projects confirms that, in terms of other equipment needed for
synchrophasor systems, other than the PMUs and PDCs, the greatest amounts spent by any one
NTP also provides time stamps in SOC and fraction of second information in the form of
a 64-bit unsigned fixed-point number, with the integer part in the first 32-bit and the fraction part
in the last 32 bits and interpreted in standard seconds relative to UTC [28]. When a message
arrives, the time from the local clock of the computer interface is transferred to the time-stamp
variable. The quality of the time signal generated on the computer interface thus depends on the
quality of internal computer clock [51]. It also depends on the type of internet connection, the
congestion present in network, but not necessarily the stratum that is used for synchronization.
Algorithms can help decrease the latency in picking up the time signal that is received via
NTP [51]. The maximum resolution of an NTP time stamp is about 200 ps (about the time it
takes an electrical pulse to travel through 2 cm of copper wire), so the ultimate accuracy of NTP
is likely to be limited by hardware and latency concerns, rather than by the NTP protocol [26].
The NTP system consists of a network of primary and secondary time servers, clients,
29
primary reference source which is very accurate. The secondary
secondary servers connect to other servers
and choose the most accurate and reliable system of servers to obtain time.
significantlyy better accuracy and stability. These improvements include novel interfacing
Figure 14.. Offsets between the local clock and the PPS GPS [27]
Synchronization
ynchronization accuracy of NTP has improved from tens of milliseconds to sub
sub-
milliseconds. This has been experimentally proven to be true for various configurations of NTP.
NTP
PPS received from ASCII timecode can provide synchronization accuracy or around 25ms
25 [27].
Figure 14 shows the time offset the offsets between the local clock and the PPS signal from a
NTP time precision has been proven to be adequate for many PMU applications.
applications NTP is
being in PMU for time synchronization for determining electromechanical oscillations and
30
frequency measurements [52- 53]. For observing frequency in wide area, six PMUs have been
setup and synchronized via NTP (software only version) and the measured frequency is also sent
Many experiments have been conducted to test and calibrate the expected accuracy of
NTP over normal local area network (LAN) and wide area network (WAN) connections [27-
31]. In these experiments the PPS obtained from GPS is compared to one which is obtained
using NTP. The results of few such experiments by David Mills are mentioned below [27]:
1. The offset i.e. time error between PPS generated by GPS and obtained via NTP was
measured for a particular primary server with over 400 clients being supported using
NTP version 3. Some of the clients had intense computational and cryptographic
requirements. The results showed that synchronization could be maintained within 400µs.
2. The offset between two primary servers was measured. These represent typical a system
which is generally used. One of the servers was a dedicated time server while other was
multi-functional. Occasional spikes of 1ms were seen, but these would be taken care of at
3. The results of an experiment in which the primary and secondary server offset was
This data, as well as from several other experiments shows that using only software NTP
can provide synchronization in tens of milliseconds. With the addition of hardware such as a
gadget box for the PPS much better accuracies can be achieved. However, NTP version 4
provides the option of choosing the servers for synchronization. 9 or less servers can be chosen.
This gives an opportunity to connect all the PMUs to the same set of servers for lower mutual
offset. Also, in case of loss of absolute time, the PMUs would still be synchronized.
31
Using the gadget box along with NTP software and PLL can provide accuracies in the µs
range. The accuracy of time-stamps obtained in such an arrangement is 20-30 µs [27]. However,
it was claimed that this configuration might yield 1 µs accuracy in time-stamps [27]. This
Transmission networks have a dense network of SCADA present for monitoring. The
data received from SCADA along with other information is run through a state estimation
algorithm and the quasi state of the system is determined. This information is now used as an
input for various other applications. On the other hand, SCADA is present very sparsely in
distribution networks. This minimal data along with Boolean data coming from fault indicators,
sectionalizers and remote switches is uploaded at the control center. The control operator now
takes actions manually against an information log. These actions are thus taken very
transmission network, the need of PMU arises mainly to measure the state of the system, or
improve state estimation and control. This would require PMUs with very high synchronization
precision like the one provided by conventional PMU. The purpose of PMU in distribution
networks however would be mainly for situational awareness, fault location detection and so on.
For these purposes, the PMU need not to be so precise in time synchronization. The proposed
The real and reactive power flow from Bus i to Bus k can be given by:
32
Qi = Vi Vk (Gik sin θ ik − Bik cos θ ik )
where θ ik = θ i − θ k (2)
Where Pik and Qik is the real and reactive power flow between ith Bus and kth Bus, Gik is
conductance and Bik susceptance between the ith and kth Bus, Vi and Vk respective voltage
Suppose that the error in estimates of the real and reactive power flow over a line
connecting Bus i and k are δPik and δQik respectively; the error in measurement of the power
angle difference θ ik = θi − θ k is δθik; and δt is the error in measurement of time. Then, simplifying
Bik Bik2
tan(θ ik − α ) = − tan α −
1 2B
θ ik + h.o.t ≅ + 2 + 1θ ik ≤ ik (5.4)
cos 2 (α − θ ik ) θ Gik Gik Gik
ik =0
Note that θik is very close to zero in the power system operation, and typical values for
33
δQik 1 − (Bik Gik ) tan θ ik δθik ∂θ 2G ∂θ ik
= δt ≤ cot(θ ik + α ) ik δt ≅ ik δt
tan θ ik + (Bik Gik ) δt
(5.5)
Qik ∂t Bik ∂t
And
Gik Gik2
cot (θ ik + α ) = cot α −
1 2Gik
θ ik + h.o.t ≅ − 2 + 1θ ik ≤
sin (θ ik + α ) θ =0
2 (5.6)
Bik Bik Bik
ik
Assuming an error of 10 µs in time measurement, then the relative errors in estimating Pik
and Qik are very small as the instantaneous changes in the voltage angles is very small with time.
Anti- islanding techniques based on rate of change of phase angle difference (ROCPAD)
differentiate islanding and non- islanding conditions by setting a threshold at 50 degree/s to 100
degree/s value of ROCPAD. Considering a maximum variation of would be 200 degree/s i.e. 3.5
and
Accordingly,
∑ (P P )
k k
w
k k
Pi ∑P (5.9)
k ik k ik ij Pij Pij
and
34
δQi ∑ δQ ∑ (δQ Q )(Q Q ) =
Q δQik
δQ
= = ∑ ≤ N i ij ≤ 0.07%
ik ik ij ik ij
∑ (Q Q )
k k
w (5.10)
Qi ∑Q k k Q Qij
k ik k ik ij ij
Also, Ni is the number of the lines connected to Bus i, for a distribution network Ni ≤ 10 unless
Bus i is a feeder.
Note that these upper bounds are significantly overestimated. The most significant
overestimate comes from the upper bound replacing the rate of voltage angle difference between
two Buses with the rate of voltage angle at a Bus. According to the current operation policy of
distribution network (radial topology and uni-directional power flow from a feeder to sinks), the
rate of voltage angle difference is much smaller than that of voltage angle. Therefore, these
values are extreme cases but remain so small as to be still acceptable in distribution monitoring.
35
Chapter 6. Applications and future prospects
Real time monitoring in distribution networks can help to significantly reduce congestion
by monitoring the line flows continuously and making it easier to use lines to their maximum
capacity [54]. With the increasing amount of solar photovoltaics (PV) and rooftop wind turbines
being integrated into the grid, the penetration level of distributed generation steadily increases.
Real time monitoring in such scenarios can go a long way to strengthen the stability of the
system by helping to observe and allocate real as well as reactive power in a better way.
Moreover, distribution network topology is not constant and keeps on getting reconfigured. This
reconfiguration occurs automatically in the case of faults or is assumed to carry out maintenance
or repair work. PMUs can help reconfigure the network efficiently by making the network
parameters visible.
One immediate application of this PMU is to detect faults and fault location. Currently,
fault detection relies heavily on a phone-call from end-consumers. Needless to say, this method
involves a lot of ambiguity and is highly inefficient and time consuming. While many techniques
exist for fault location detection for transmission lines, these cannot be applied to distribution
network due to the inherent difference in topologies between transmission and distribution
networks. Another reason is that most of fault location detection techniques are knowledge based
often rely on external information such as SCADA alarms, substation and feeder switch status,
feeder measurements, load voltage sensors, etc. In distribution systems, measurements are
36
usually only available at the substation and information about the operation of feeder protective
Having a PMU at every node would make the system completely observable and make
way for utilization of many of the fault detection techniques in the distribution network. The
method discussed in [55] provides an accurate means to determine fault location in distribution
networks. The diagnostic scheme involves three steps: signal processing, fault location and fault
diagnosis. Signal processing refers to the step of estimating the phasors. This step can now be
eliminated as phasors can be directly measured using PMU. Fault location refers to the step of
performing fault distance calculations, estimating the range of faults and fault diagnosis is the
Consider a single line-to-ground fault on phase A as shown in Figure 15. Allowing for
the mutual couplings among different phases, the following relationship exists for the faulty
phase,
Va = D ( Z aa I a+ Z ab I b + Z ac I c ) + I f R f (6.1)
where, D is the fault distance, If is the fault current, Rf is the fault resistance, Zaa is self-
impedance of phase a, Zab is mutual-impedance between phase a and b, and Zac is mutual-
I f = Ia − Ia ' (6.2)
Here, Ia’ is the remote infeed current and is a function of Va’, Vb’and Vc’.
37
From Equation (6.1) and (6.2);
Va = D ( Z aa I a + Z ab I b + Z ac I c ) + ( I a − I a ' ) R f (6.3)
Var = D ( Z aa
r r
I a − Z aa
i
I ai + Z ab
r r
I b − Z ab
i
I bi + Z acr I cr − Z aci I ci )
(6.4)
+ R f ( I ar − I ar' )
and
Vai = D ( Z aa
r
I ai + Z aa
i
I ar + Z abr I bi + Z ab
i
I br + Z acr I ci + Z aci I cr )
(6.5)
+ R f ( I ai − I ai ' )
Var ( Z aar I ar − Z aa
i
I ai + Z abr I br − Z ab
i
I bi + Z acr I cr − Z aci I ci ) ( I ar − I ar' ) D
i = r i (6.6)
Va ( Z aa I a + Z aa I a + Z ab I b + Z ab I b + Z ac I c + Z ac I c ) ( I ai − I ai ' ) R f
i r r i i r r i i r
Here the superscript ‘r’ denotes the real component and ‘i’ denotes the imaginary component.
Solving Equations (6.4) and (6.5) simultaneously, the value of D and Rf can be calculated.
38
Figure 15: A single-line
line-to-ground fault on phase A [55]
mentioned in [40], the complete process of detecting and locating fault (with the assumption that
1. From the measurement of currents Ia and Ia’ obtained from the PMU, If is calculated.
With the known fault current, the fault distance and the fault resistance can be
2. Once the fault distance is calculated, the search begins by assuming the line directly
connected to be faulty. However, iff the fault distance is greater than the length of this
line, the search moves on to the lines connected to the receiving end of the line and so
on. By traversing the network in a certain sequence, all possible fault locations can be
39
Figure 16:: Search for possible fault locations
l [55]
3. Consider the example of a 14 Bus system shown in Figure 16.. Two PMUs placed at
Bus 1 and Bus 5 make the system observable. In this case, three candidate locations,
40
4. To determine if the line is faulted or not, voltage at every Bus is calculated using both
the PMUs. For location F2, voltage phasors at Bus-2, denoted as V21 and V25 are
calculated from Bus-1 and Bus-5, respectively, as if there is not a fault at F2.
actual fault location. Otherwise, it is removed from the candidate list [40]. This
method requires voltage and current values at both ends of the line.
6. Other methods for fault location include the knowledge of status of protective devices
A major step in the fault location algorithm mentioned in [55] was to calculate the remote
end current infeed using the radial power-flow algorithm. Measurements obtained from a PMU
can eliminate this step completely by providing values of the required quantities. This fault
location detection algorithm when used in conjunction with PMU technology can provide fault
The thesis proposed a new concept of PMU that could be built in only a couple of
hundred dollars and minimum cost for communication infrastructure. Evaluation of this PMU
shows that it is adequate in terms of accuracy for distribution networks. Fault location detection
using these PMUs can help in efficient restoration of service, reduce loss, help in load balancing
and load shedding, topology analysis, event monitoring and many other applications can benefit
Further research includes fabricating such a system using printed circuit board and later
in the form of a chip. The testing of this system against various communication network
41
topologies, under faults etc. would provide clarity and better understanding of the system. The
dedicated communication need of PMU is mainly because of accuracy and cyber security
reasons.
needed for distribution networks. As the system becomes more dependent on the communication
identified some cyber-attacks which utilize malicious data injection to compromise the state
estimator data and the counter-measures taken [57]. Many research papers discuss various
methods of detecting and protecting the synchrophasor system from cyber-attacks [57- 59]. Due
to the specific nature of data provided by PMUs, it is crucial that strategies be developed for
preemptive, real-time detection and post- attack analysis. This could open new doors for the use
The future smart grids will require significantly large number of PMUs for the benefits
outlined above. For achieving the goal, customizing PMU according to the application and
42
References
Generation”,
http://energy.gov/sites/prod/files/oeprod/DocumentsandMedia/RDSI_fact_sheet-
http://www.nerc.com/news/Headlines%20DL/NERC%202013%20Annual%20Report
4. “Synchrophasor Technologies and their Deployment in the Recovery Act Smart Grid
5. Phadke, Arun G., and John Samuel Thorp. Synchronized phasor measurements and
7. Phadke, A.G.; Thorp, J.S.; Adamiak, M.G., "A New Measurement Technique for
43
8. Phadke, A.G.; Thorp, J.S., "HISTORY AND APPLICATIONS OF PHASOR
9. De La Ree, J.; Centeno, V.; Thorp, J.S.; Phadke, A.G., "Synchronized Phasor
September-October 2008.
11. De La Ree, J.; Centeno, V.; Thorp, J.S.; Phadke, A.G., "Synchronized Phasor
12. Fang Chen; Xueshan Han; Zhiyuan Pan; Li Han, "State estimation model and
13. Hui Xue; Qing-quan Jia; Ning Wang; Zhi-qian Bo; Hai-tang Wang; Hong-xia Ma, "A
Dynamic State Estimation method with PMU and SCADA measurement for power
systems," Power Engineering Conference, 2007. IPEC 2007. International, vol., no.,
14. Thorp, J.S.; Phadke, A.G.; Horowitz, S.H.; Begovic, M.M., "Some applications of
44
15. Ding, Feng; Booth, C.D., "Protection and stability assessment in future distribution
2012. 11th International Conference on , vol., no., pp.1,6, 23-26 April 2012.
16. V. Madani, E. Taylor, D. Erwin, A. Meklin, and M. Adamik, “High speed control
17. IEEE Standard for Synchrophasor Measurements for Power Systems, IEEE Standard
18. “Executive Report On the State of Synchrophasors in the USA”, ESTA International
19. Premerlani, W.; Kasztenny, B.; Adamiak, M., "Development and Implementation of a
2008 .
20. Qin Lijun; Zheng Shenrui; Guo Qing; Hao Cuijuan, "Feasibility study of PMU based
21. Pallarés-López, V.; Moreno-Muñoz, A.; Torrellas, M.P.; García, I.M.M.; de la Rosa,
(ICIEA), 2010 the 5th IEEE Conference on , vol., no., pp.942,947, 15-17 June 2010
45
22. Pallares-Lopez, V.; Moreno-Munoz, A.; Gonzalez-Redondo, M.; Real-Calvo, R.;
Garcia, I.M.; de Castro, A.G.; Perez, F.D.; de la Rosa, J.-J.G., "Deterministic Ethernet
23. Amelot, J.; Fletcher, J.; Anand, D.; Vasseur, C.; Li-Baboud, Y.; Moyne, J., "An IEEE
24. Amelot, J.; Stenbakken, G., "Testing phasor measurement units using IEEE 1588
25. Lixia, M.; Benigni, A.; Flammini, A.; Muscas, C.; Ponci, F.; Monti, A., "A software-
26. Deeths, David, Glenn Brunette, and Sun BluePrints. "Using NTP to Control and
2001.
27. Mills, D .L., “Modelling and analysis of computer network clocks”, Electrical
46
28. Mills, D .L., “Network Time Protocol (Version 3) specification, implementation and
30. Mills, David L. "Internet time synchronization: the network time protocol."
31. Mills, David, Jim Martin, Jack Burbank, and William Kasch. "Network time protocol
32. Lei Wang; Fernandez, J.; Burgett, J.; Conners, R.W.; Yilu Liu, "An evaluation of
network time protocol for clock synchronization in wide area measurements," Power
and Energy Society General Meeting - Conversion and Delivery of Electrical Energy
in the 21st Century, 2008 IEEE , vol., no., pp.1,5, 20-24 July 2008.
33. David L. Mills, “Gadget Box PPS Level Converter and CHU Modem”, [Online];
contracts/Other_OEM_Price_Sheets/Spectracom/SPECTRACOM%2520NetClock%2
520Price%2520List%25203-1-
09.xls&sa=U&ei=QDZHU9znKcbbyQHM5oGYDA&ved=0CAUQFjAA&client=inte
rnal-uds-cse&usg=AFQjCNEionfHVvQXOSbyvEU7bTkgBBXCHw, 2013.
35. “lpc1768 price and stock”, findchips website, [Online]; available at:
http://www.findchips.com/search/lpc1768.
47
36. “Micropower Phase Lock Loop DIP-16”, Jameco Electronics website, [Online];
dip-16-4000-series.html
37. “Products for MSP430 Ultra-Low Power 16-bit MCUs”, Texas Instruments website,
bit_msp430/products.page
circuits-ics/embedded-fpgas-field-programmable-gate-array/2556262?k=spartan
39. “Products for MSP430 Ultra-Low Power 16-bit MCUs”, Texas Instruments website,
bit_msp430/products.page.
40. “Mechanical Dynamics, the Swing Equation, Units”, Iowa State University website,
41. David L. Mills, “Gadget Box PPS Level Converter and CHU Modem”, [Online];
42. “74ls123 price and stock”, findchips website, [Online]; available at:
http://www.findchips.com/search/74ls123
43. “icl232 price and stock”, findchips website, [Online]; available at:
http://www.findchips.com/search/icl232
44. “Corsair 8GB (1x8GB) DDR3 1333MHz (PC3 10666) Laptop Memory
48
http://www.amazon.com/Corsair-1x8GB-Laptop-Memory-
CMSO8GX3M1A1333C9/dp/B005T63BEM
45. “Modem Protocols Bell 103”, idealo.co.uk website, [Online]; available at:
http://www.idealo.co.uk/cat/3253F461237/modems.html
http://www.amazon.com/gp/product/B004H9C4JK/ref=as_li_tf_tl?ie=UTF8&camp=
1789&creative=9325&creativeASIN=B004H9C4JK&linkCode=as2&tag=swlcom01
-20
47. “Texscan 5BC110/2.0KK Band Pass Filter(2KHz), SMA connectors”, Ebay website,
Filter-2KHz-SMA-connectors-/390403528377
48. Samui, Ankita, and S. R. Samantaray. "Assessment of ROCPAD relay for islanding
391-398.
49. Lu-zhao, Li, Zhang Dao-nong, and Dong Yan-tao. "Time synchronization technology
for the smart substations." In Advanced Power System Automation and Protection
(APAP), 2011 International Conference on, vol. 3, pp. 2283-2285. IEEE, 2011.
50. Sebastian, M., O. Devaux, and O. Huet. "Description and benefits of a situation
awareness tool based on a distribution state estimator and adapted to smart grids."
In SmartGrids for Distribution, 2008. IET-CIRED. CIRED Seminar, pp. 1-4. IET,
2008..
51. Dobrogowski, A.; Jessa, M.; Kasznia, M.; Lange, K., "Generation of 1-pps timing
signal controlled by NTP," Frequency Control and the European Frequency and
49
Time Forum (FCS), 2011 Joint Conference of the IEEE International , vol., no.,
52. Malpani, Rohit, Zaheer Abbas, and KShanti Swarup. "High precision frequency
53. Salunkhe, Kunal A., and A. M. Kulkarni. "A wide area synchronized frequency
measurement system using network time protocol." 16th National Power System
54. Sebastian, M., O. Devaux, and O. Huet. "Description and benefits of a situation
awareness tool based on a distribution state estimator and adapted to smart grids."
In SmartGrids for Distribution, 2008. IET-CIRED. CIRED Seminar, pp. 1-4. IET,
2008.
55. Zhu, Jun, David L. Lubkeman, and Adly A. Girgis. "Automated fault location and
56. Ren, J., S. S. Venkata, and E. Sortomme. "An Accurate Synchrophasor Based Fault
57. Y. Liu, P. Ning, and M. K. Reiter, "False data injection attacks against state
estimation in electric power grids," ACM Trans. Information and System Security,
58. Yang, Y.; McLaughlin, K.; Sezer, S.; Littler, T.; Pranggono, B.; Brogan, P.; Wang,
50
Information and Communications Technologies (IETICT 2013), IET International
“Securing wide area measurement systems,” Pacific Northwest Natl. Lab., Tech. Rep.
PNNL-17116, (2007).
51