Professional Documents
Culture Documents
IN COMMERCIAL BUILDINGS
APPLICATION GUIDE
SI UNIT VERSION
CONTENT
PREFACE
Throughout the history of mankind, fire has towards better energy efficiency and new solu- WHY DO WE HEAT? ......................................................................................... 4
played an essential role as provider of warmth tions. However, as the construction industry is
and comfort and thus it has secured the devel- often characterised by conservatism and short Thermal comfort......................................................................................................... 4
opment and evolution of the human being. term investments, the solutions that provide
Performance of work................................................................................................. 8
Today – hundreds of years later – the ability to the best comfort and productivity may some-
find shelter and stay warm is still one of the times be neglected and disregarded with argu- EFFICIENT HEATING........................................................................................ 10
most fundamental needs of human beings and ments like “don’t change what already works”
the main purpose of modern buildings around and “it’s too expensive and unnecessary”. But Air-based vs. hydronic systems.......................................................................... 10
the world. However, much has changed since the solution may not be that difficult after all, Low temperature heating.................................................................................... 15
the early attempts with fire and we now know often an improved indoor environment will pay
the importance of, not only keeping warm and off in the long run as productivity and employee HEATING SYSTEMS......................................................................................... 18
dry, but also to facilitate the optimum indoor satisfaction increases.
climate in order to attain maximum productiv- The scope of this application guide is to define
Heat production................................................................................................... 18
ity and minimize energy consumption. and clarify the purpose of the heating applica- Heat distribution and control.......................................................................... 27
Due to recent year’s continuous focus on cli- tion and the reason why it should be taken
mate change and scarcity of energy resources, seriously as well as outline the necessity of Pipe configurations............................................................................................. 36
continuously tightened restrictions on energy energy efficient systems. It is not a complete
System balancing ................................................................................................ 39
consumption have been agreed in most parts guideline and it will not substitute the numer-
of the world. However, energy consumption in ous standards in this area, but we hope that it Heating consumers............................................................................................. 46
buildings still represents around 40 % of the will serve as a source of inspiration and maybe
total consumption in society, leaving a huge challenge the way the heating application is
potential for improvements. Rising energy normally dealt with.
prices and the constant concern of environ-
mental impact keep pushing the development
2 3
WHY DO WE HEAT?
PPD
WHY DO WE HEAT? 80
60
which is a measure of the wellbeing of the
humans in a given thermal environment. It is
The main reason for heating buildings is to 40 a prediction of the mean value of the votes of
shelter against the colder environment and to a large group of people on the 7-point thermal
ensure an adequate level of thermal comfort sensation scale. The optimal thermal environ-
20
in a building. But how do we define thermal ment corresponds to PMV = 0 (neutral percep-
comfort and why should we care about it? tion).
10 Based on the PMV index it is possible to predict
These issues are defined and discussed in the
following chapter. the general level of dissatisfaction amongst
5 people by calculating the Predicted Percentage
4 of Dissatisfied (PPD) index. The relationship
Thermal comfort -2.0 -1.5 -1.0 -0.5 0 0.5 1.0 1.5 2.0 between PMV and PPD appears on the graph.
4 5
WHY DO WE HEAT?
A good indoor climate improves working efficiency, satisfaction level and health
6 7
WHY DO WE HEAT?
Performance of work Relative costs in its lifetime and therefore enormous savings
performance may be achieved by creating the optimum indoor
The performance is - as mentioned above –
1.00 environment as it will increase the performance and
highly affected by the thermal environment. It
efficiency of work. Investments in HVAC installa-
has been proven by Wyon and Wargocki (2006) 0.95 tions represent around 0.4 % of the total LCC-budget
and published in REHVA Guidebook 6 that
whereas salaries make up around 80 % (see figure
0.90 below). In this case even the slightest add-on invest-
• Thermal discomfort distracts attention
ment in IEQ (Indoor Environment Quality)-improving
and generates complaints that increase 0.85
technologies should be welcomed. Imagine if an extra
maintenance costs
10 % investment in HVAC systems would increase the
• Warmth reduce mental capabilities and 0.80
staff productivity of just 2 %.
exacerbates Sick Building Syndrome (SBS)
symptoms 0.75
15 20 25 30 35 From these conclusions it is evident that thermal com-
• Cold conditions lower finger temperatures
Temperature, °C fort plays a vital role in attaining a good work environ-
and have a negative effect on mental
ment and that employers and building owner should
dexterity Relative performance as a function of temperature
pay special attention when specifying the building’s
• Rapid temperature swings have the same (REHVA Guidebook 6).The curve is based on measured
HVAC systems, which have a great impact on the
effects on office work as slightly raised work performance from 24 studies. In these studies the
buildings IEQ. Even the slightest reduction in IEQ will
room temperatures, while slow tempera- optimal working temperature is 22 °C. It suggests a
result in comprehensive productivity loss because
ture swings just cause discomfort reduction of performance of approximately 1% for every
the investments in the building, building services and
• Thermal discomfort can reduce perfor- 1% decrease or increase of temperature
equipment are relatively small in relation to the huge
mance by 5-15 %
Relative costs for salaries.
performance
From the figures to the right it is seen how the Total LCC cost Building related costs Construction
performance of work is affected by the room 1.05 100 %
temperature. Electricity
1.04 90 %
However, performance is also highly affected by Construction
Heating +
air quality and ventilation rates. This relation-
1.03 80 % Structural work
ship is illustrated by the figure below.
The figures clearly shows how an increment in 70 %
1.02 Space cleaning
ventilation rate may increase the performance
60 % Wages
but also that this gain flattens out at some
1.01 Interior
point. Thermal comfort and indoor air quality is
50 %
closely related and it is difficult to separate the 1.00 Heating + piping
two of them. 0 10 20 30 40 50 40 % Vent. + A/C
Ventilation rate, L/s per person Electrical works
“But what about the economy? Isn’t it expensive Construction Security + TC-syst.
30 %
Relative performance as a function of ventilation rate cost Design
to ensure a good indoor environment?”
(REHVA Guidebook 6). Effect of increasing ventila- 20 %
Building related
No quick answers may be given and the ques- tion rate in relation to a reference ventilation rate of cost VAT
10 l/s per person. In this case it is possible to raise the 10 %
tion should instead be answered by looking at
the problem from another point of view. Salaries performance by approximately 3 % by increasing the Misc. Misc.
0% Property
continue to constitute the bulk of total building ventilation rate.
Relative significance of salary cost for a typical office building (REHVA Guidebook 6).
8 9
EFFICIENT HEATING
EFFICIENT HEATING
Forced air systems are all-air systems where large
amounts of air are used in order to condition the space.
The air volume clearly exceeds the need for ventilation in
With the rapidly increasing demand for energy efficient the room, because the air is not only used for ventilation
heating solutions in combination with a high degree of but as a primary heat medium as well. In order to reduce
comfort and outstanding indoor environment, it is needed to the amount of cold outdoor air to be heated, an air
take a broad view on the building and the way it is heated. A recirculation duct is introduced. This means that a large
very important issue that has to be dealt with is whether an amount of polluted air is re-injected to the space.
air-based or a hydronic system should be used. This choice will If the air volume was based on the need for ventilation
have a long term effect on the operation cost of the building. alone, the air volume would be reduced significantly.
Exhaust air
Exhaust air
Forced air system used for space heating and ventilation. Here large amounts of air are needed. In order to save Dedicated Outdoor Air System (DOAS) used for space ventilation. Here the air volume is adapted to what is needed for IAQ
energy for heating of large air amounts a recirculation damper is introduced. It allows stale air from the space to be alone. Here a rotary heat exchanger is introduced. This exchanger may recover up to approximately 90% of the heat energy
re-injected. in the stale air. The return of investment in a rotary heat exchanger may be counted in weeks or month. If further space heat-
ing is needed, the floor heating system is activated.
10 11
EFFICIENT HEATING
12 13
EFFICIENT HEATING
Indoor environmental quality Finally, high ventilation rates introduce the risk
“What about the indoor environment, surely a of noise from the duct network and air diffusers
water-based hydronic radiator system cannot in the ceiling. It is obvious that noise should be
give the same level of comfort and environmen- avoided as it may distract attention and thereby
tal quality as an air-based ventilation system?” reduce productivity.
Again, the answer is clear – yes it can! The As described earlier, thermal discomfort gener-
use of hydronic systems often enables both a ates complaints and may in some cases reduce
better thermal and acoustic comfort with the the working performance with up to 15 %. With
main reason being that they are not relying this conclusion in mind and the possibility of
on large supplies of air. The ventilation system noise, hydronic systems are most often superior
only has to provide enough air to ensure an compared to air-based systems when it comes
adequate indoor air quality (IAQ) meaning to IEQ. In addition to this, it is often much
that the supply air is not used for heating thus easier to design a well-functioning hydronic
lowering the air change rate. This has several heat emitting system than an air-based system
benefits. Air diffusors suppliying high air flow rates contribute to giving the same level of comfort and IEQ.
what is often regarded as a high noise office environ-
First and foremost, a reduced ventilation rate
results in lower air velocities in the room.
ment. Low temperature heating
This is one of the biggest advantages of Comfort Max. mean air The process of heat transfer may be expressed
using hydronic systems as thermal comfort is Activity Category velocity (heating as the flow of thermal energy from high to low
highly affected by air velocities as it may lead season) temperature regions. In every transfer process
to draught (unwanted local cooling of body in a heating system, energy is wasted and lost
Sedentary activity, A 0.10 m/s
parts as a result of air movement). From the to the surroundings resulting in continuously
table, an example of the maximum allowed 1.2 met. decreasing temperatures. That is why it is
air velocity in the occupied zone is given for (Office, dwelling, B 0.16 m/s needed to supply heating systems with higher
the different comfort categories at sedentary school etc.) temperatures than needed at the end-user, e.g.
activity. C 0.21 m/s room air. It has for many years been common
to construct systems with supply temperatures
Example of the maximum allowed mean air velocity
Reduced ventilation rates and thus reduced air between 70-90 °C, even though the aim only
for sedentary activity. The values are based on a turbu-
velocities result in a better thermal environ- is to have room air temperatures at around 22
lence intensity of 40 % and air inlet temperature equal
ment. As the example shows, by halving the °C. However, it is relatively expensive to achieve
to the operative temperature of 22 °C.
maximum mean air velocity from 0.21 to 0.10 such relatively high temperatures.
m/s, it is possible to increase the local thermal
comfort in relation to draught from category The heat transferring process from a surface –
C to A. e.g. a heating coil or radiator – to the surround-
Besides the issue of air velocity, it is possible to ing air may be expressed as a function of a
supply a room with much more heat by using combined heat transfer coefficient, the surface
e.g. radiators than by ventilation as heat from area and mean temperature difference between
radiators is emitted by both convection and surface and air.
radiation resulting in a more even thermal
sensation.
14 15
EFFICIENT HEATING
Φ = α x A x ( ts – ta ) where 5 kW heat needs to be delivered to a 200 m2 room with air temperature 22 °C from an underfloor
heating system. This corresponds to 25 W m2 floor.
Φ = Heat flow [kW]
α = Surface heat transmission coefficient [W/m2K] Underfloor heating system (pipes cast into screed)
A = Surface area [m2] Pipe diameter and spacing = ø20 mm (pipe spacing = 150 mm)
ts = Surface temperature [°C] Screed thickness = 150 mm (concrete, λ = 1.9 W/mK)
ta = Air temperature [°C] Floor covering = light carpet (R = 0.1 m2K/W)
Maximum temperature difference of water in pipes, ΔTwater = 5 °C (limited due to thermal comfort)
When using air-based heating systems, air is sup-
plied to the space at a higher temperature than the Heat transfer coefficient (α) is determined in accordance with European Standard EN 1264-2:2008
room air temperature. The difference can be as high and REHVA Guidebook 7 to 2.57 W/m2K. This is based on geometry and materials used.
as 8 °C to 10 °C. The heating of the supply air takes
place in the heating coils which normally is located ΔTlog = Φ / (α x A) = 5,000 W/(2.57 W/m2K x 200 m2) = 9.7 °C (maximum allowed difference is 33 °C)
in the air handler (AHU). Due to cost reasons the Tsupply = ΔTlog + Tair + ΔTwater/2 = 9.7 °C + 22 °C + 2.5 °C = 34.2 °C
size of the air handler and coils are limited, thereby Treturn = Tsupply - ΔTwater = 34.2 °C - 5 °C = 29.2 °C
limiting the heating coil surface area. This means Circulated water = Φ / (cp x ΔTwater) = 5,000 W/ (4,200 J/kgK x 5 K) = 0.24 kg/s
that the temperature difference between coil surface
and air has to be proportionally bigger, requiring As shown it is possible to supply heat at a much lower water supply temperature (34.2 °C) in an
a higher water supply temperature for the coil. underfloor heating system than is the case with a traditional air-based system (approx. 70 °C). The
By utilizing a much bigger surface area as in e.g. capacity of the underfloor heating system is much higher than what is shown in this example poten-
underfloor heating, it is possible to reduce the water tially delivering up to maximum 100 W/ m2 floor and still ensuring thermal comfort resulting in a
supply temperature drastically. However, heating supply water temperature of only 55 °C.
Schematic illustration of the heat transfer from a
coils in AHU´s are still needed but only for condition- heating surface to surrounding air
ing of cool outdoor air in order to achieve isothermal
conditions of the supply air.
16 17
HEATING SYSTEMS
Heat production sate, high efficiency boilers must use stainless steel
or other corrosion-resistant heat exchangers.
In commercial building’s heating is typically
produced, centrally within the building (or on the
buildings premises) or the building is connected to a
district heating network. Production of on-site cen- Average dew point °C
tral heating takes place with different technologies 70 Natural gas
– below the most common and often used solutions
are described. 60 Oil
50
Gas and oil boilers
Boilers or furnaces are the traditional closed vessel 40
used to heat water or other fluids to be used in 30
central heating applications. A boiler installation has
20
the following components: burner, nozzles, boiler
casing, hot-water tank (integrated or separate) and a 10
chimney. The boiler generates heat from combustion 10 20 30 40 50 60 70 80 90 100 Excess Air (%)
of domestic fuel oil (smaller systems), heavy fuel oil Average dew point for typical fuels. Excess air - the ratio of the quantity of supplied air to the
(larger systems), and natural gas. Solid fuel boilers consumption process above that theoretically necessary for perfect combustion.
are not discussed in this publication.
18 19
HEATING SYSTEMS
20 21
HEATING SYSTEMS
Heat pumps
By means of a circulating refrigerant, heat
pumps are devices that transfer energy from Energy direction Energy direction Energy direction
one temperature level to another in order to
utilize low temperature heat sources. However, Brine Coolant Water
based based based
heat pumps are found in many different HVAC Ground Evaporator Condenser Floor heating ect.
circuit circuit circuit
applications and if used in air-conditioning
or refrigeration, the process is turned around, Schematic showing the circuits in a Ground Source Heat Pump system (GSHP).
transferring heat from a high temperature level
to a low level.
22 23
HEATING SYSTEMS
24 25
HEATING SYSTEMS
26 27
HEATING SYSTEMS
28 29
HEATING SYSTEMS
Outdoor
temperature
sensor
when having two different fluids as e.g. in heat Climate Mixing loop controls
Control
pumps or hot water production or simply if the As the purpose of the mixing loops is to regu-
owner of a district heating network requires late the water temperature, it needs a control
a separation for leakage considerations or to system with set-point and a water temperature
divide the multi tenanted usage. Moreover, it feedback signal. Such control systems may be
secures a better hydraulic decoupling and also configured in many different ways depend-
makes it possible to address pressure precau- ing on the nature of the application, however,
tions locally in big systems. it always consists of a controller (P, PI or PID),
which based on input signals regulates the
water temperature by either throttling valves
and/or adjusting pumps.
In radiator systems both temperature and
Flow temp. °C flow control is normally utilized. The supply
Ex. Outdoor t -20 °C = 75 °C temperature is centrally regulated in a mixing
80 Outdoor t 10 °C = 61 °C loop as a function of outdoor temperature thus
75 minimizing the energy consumption. This regu-
70 lation is often referred to as “climate control”
65 and relies on a pre-programmed relationship
60 between outdoor air temperature and supply
Flow temperature demand water temperature.
55
80 °C Outdoor
20 10 0 -10 -20 Moreover, the delivered heat on room level
temp. °C
is regulated by varying the flow through the
Example of a special mixing loop application – the so-
called climate control with the purpose being to centrally radiator by the use of thermostatic valves.
regulate the supply temperature as a function of outdoor Drawing on both temperature control and flow
temperature. control, these systems enable optimal control
and energy efficiency.
35 °C
Air
In heating coils, mixing loops are used to
control the inlet air temperature by mixing the
right supply water temperature for the heating
coil based on a feedback signal of the current
Controller inlet air temperature, which is continuously
evaluated up against a set-point, making it a
bit different from the weather compensation
Old cast iron radiators New light con- Heat coils Under floor heating control.
- High radiation vection radiators (AHU) (Fan coils) - Only radiant
- Low convection - Medium radiation - Only convection - Large surface
- Medium convection - Air driven Example of a mixing loop setup for a heating coil with feed-
back signal of the controlled air temperature after the coil.
In a heating system, different types of heating consumers are often installed with different flow tempera- By also measuring the inlet air temperature before the coil,
ture requirements. the controller may accurately adjust the inlet air set-point
based on a pre-programmed climate control.
30 31
HEATING SYSTEMS
32 33
HEATING SYSTEMS
34 35
HEATING SYSTEMS
36 37
HEATING SYSTEMS
Disadvantages:
• Longer and more complicated pipe runs
• Slightly higher pumping costs
38 39
HEATING SYSTEMS
Design flow should be available at all commercial ranges. These generally do not fit the
consumers at all times calculations made. In fact, the only component
The heat output by a consumer unit depends that can be adapted to the actual and correct
on the supply water temperature and the water water flow and pressure is a variable speed
flow. If the temperature is controlled at the heat pump.
production unit or by mixing loops the water Balancing a heating system means that all sur-
flow, at every consumer, is the determining plus pressure in the distribution section strings
factor for the heat output. In situations where are removed except pressure in the string with
the system is running at design load, a lack of the highest pressure loss (index string). This
flow will result in insufficient room tempera- secures an equal water distribution in the dif-
tures and poor indoor climate. In fact, control is ferent parts of the heating system but requires
only possible when the required water flows are balancing valves on all strings.
available. Balancing should be done under design condi-
In order to minimize the risk of too low flow, tions in order to safeguard that too low flow
both heat production units, the distribution never occurs at any consumer unit. When every
system and consumer units are often oversized consumer unit in the system is supplied with
by adding a security factor. However, even if the design flow, the pressure loss in the system
some problems are solved that way, others are is at its highest. When the load and hence the
created, particularly on the control side. Some flow are decreasing, the pressure loss in pipes
oversizing cannot be avoided, because pipes and components decreases exponentially and
and components must be selected from existing the differential pressure at the components will
increase. If the flow is sufficient at design condi-
Index string
tions, there will always be sufficient flow at all
other conditions too.
Balancing valves
Example of a well-balanced system. All radiators are supplied with sufficient and equal flow due to balancing
valves on all strings. Radiators should always be fitted with thermostatic valves with flow pre-setting.
40 41
HEATING SYSTEMS
70
authority, the higher the distortion. A balancing 60
valve installed in series with the chosen control 50
ΔH
valve does not change any of these two factors 40
and consequently does not affect the control 30
valve authority. 20
10
Differential
0 10 20 30 40 50 60 70 80 90 100 pressure valve
Valve lift [%]
A differential pressure valve increases the valve authority
Successful combination of non-linear control charac- of the control valve to 1.0.
teristics of a heating consumer and a control valve.
42 43
HEATING SYSTEMS
Tprimary Qsecondary
Water flows at system interfaces should
be compatible
In many heating systems the available heating
production exceeds the need with 25 % or more
even if a diversity factor has been taken into
account. Nonetheless, the heating consumer
Available heating
units do not always receive the desired heating.
output 70 %
If the maximum load cannot be reached, it is
often because the plant is hydraulically unbal- Heat
anced. When peak demands occur, control will source
open at 100 %. If they are oversized, a too high Distribution
flow in some parts of the heating system cre- 70 % Consumption
ates underflows in other parts. These unfa- 100 %,≤
Production
voured circuits are not able to provide their full 130 %
load when required. Furthermore, the produc-
If the capacity of production, distribution or consump-
tion flow will exceed the distribution system tion is undersized, the total performance of the system
flow. In this case the flows are incompatible will not meet its design heating output. Qprimary Tsecondary
and the desired flow temperature cannot be
reached. An example of a primary/secondary system where the secondary flow is higher than the pri-
mary flow.
The figure below represents a heating system Tprimary Qsecondary
with two boilers and a number of consumer
units. If the distribution circuit is not balanced,
the maximum flow, Qsecondary, may be higher
than the production flow, Qprimary. In this case
the flow in the bypass reverses. The flow water
temperature will decrease and the designed
heating output cannot be transmitted.
Heat
source
Qprimary Tsecondary
An example of a primary/secondary system where the primary flow is higher than the second-
ary flow. The primary flow should always be equal to the secondary flow..
44 45
HEATING SYSTEMS
46 47
HEATING SYSTEMS
Floor heating
Capacity of a floor heating system:
A viable alternative to conventional radiator style
heating systems is underfloor heating, which
Φ = α x A x ( ts – ta ) where
primarily utilizes heat emission by radiation. A
typical solution consists of small bore pipes, laid
in the concrete slab under the floor surface. The Φ = Heat flow [kW]
solution is typically fed by a condensing boiler, α = Floor surface heat transmission coef-
GSHP or district heating. ficient [W/m2K]
Heating buildings in this way provides a consist- A = Floor area [m2]
ent, even heat release from floor level. It provides ts = Floor surface temperature [°C]
comfort underfoot and pleasant temperatures. ta = Room air temperature [°C]
Compared to radiator systems it uses a lower
water temperature to maintain the same room The floor surface heat transmission coefficient is
temperature level. set between 9.5 and 10.2 depending on the floor-
For the sake of comfort, the floor surface temper- ing type.
ature should ideally be between 25-32 °C. This
results in a relatively low flow temperature. The The recommended maximum floor temperature
obtainable temperature difference will therefore depends on the usage
Installation of floor heating pipes. The mat keeps the
be between 10-15 °C, which is lower than with pipes in place before casting. Workshops, industrial kitchens 25 °C
radiator systems. Offices, lounges and residential areas 28 °C
Because condensing boilers work more
Lobbys, foyers 30 °C
efficiently at lower temperatures, pairing an Share of dissatisfied [%]
underfloor heating system can reduce heating 2.7 Swimming stadions, locker rooms 32 °C
80
costs. A condensing boiler run in the more cost-
efficient condensing mode at low temperatures. The graph shows the relation between the floor
40
Underfloor heating is also well-suited for usage temperature and the percentage of dissatisfied
with solar heating and heat pumps. because of thermal discomfort and thus why the
1.8 20 floor temperature is of vital importance. In envi-
Floor heating systems are characterized by a ronments where people are sitting or working,
(PPD)
resulting low vertical air temperature gradient. Room the floor surface temperature has to be kept very
From just above the floor the temperature stabi- 10
height [m] stable. Nevertheless it is never possible to obtain
lizes on a given temperature within the comfort 100 % satisfied people; a minimum of 5 % will feel
zone, which is defined from 0.2 m to 1.8 m above 5 in thermal discomfort due to floor temperature.
the floor. If the temperature around the person’s
head is high and the temperature around the However in locker rooms and similar rooms where
feet is low, this may result in discomfort and people are bare footed, high floor temperatures
dissatisfaction. 2 are accepted because people are staying there
5 10 15 20 25 30 35 40
The heat is emitted to the room as approxi- 0.2 only for a short while.
16 18 20 22 24 26 28
mately 60 % radiation, 20 % convection, and 20 % Floor temperature [°C]
Temperature [°C]
conduction. Each room has one or more circuits,
which are commonly controlled by a room Typical air temperature gradient in rooms with under- Predicted percentage dissatisfied as function of
floor heating. floor temperature
thermostat.
48 49
HEATING SYSTEMS
10
Water flow in a floor heating system: Capacity of a fan coil:
50 51
HEATING SYSTEMS
0.2
16 18 20 22 24 26 28
Temperature [°C]
52 53
Tel: +45 87 50 14 00
www.grundfos.com
DK-8850 Bjerringbro
Poul Due Jensens Vej 7
GRUNDFOS Holding A/S
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks
owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. 98936932 / 0715