I'm looking to carry out an upgrade of the panel firmware and the database.
Before I begin, is there anything I should be aware of or any errors that have a high frequency of
occurring?
I read in the release notes that the panel would restart and there might be a problem uploading
the bootloader code.
It doesn't specify why the error would occur but just that if it does I should restart the panel and
try again.
Top
gmcorreia
Posts: 24
Use the "Single Step" option and connect directly to the 3-CPU3.
Initially start with Bootstrap, notice that the percentage bar of the download stops in some
moments until reaching 100%. Wait for the various times to appear until the panel finishes
restarting. Then download the Code by following the same procedures as above. When you
complete you can proceed with the other cards or download the database.
If the communication is interrupted the panel can be in maintenance mode and must be turned
off. After reconnecting the panel, make sure it remains in maintenance mode or returns normally.
Try to download again.
Rarely the panel is locked in maintenance mode, but if this happens it should send the CPU to EST.
If you upgrade the SDDC or SSDC cards, always do this directly on the card with the "Single Step"
option checked.
Before you begin any upgrade, read the release instructions to find out if your hardware is
compatible with the latest version of the software.
Every update should be done carefully and without interruptions, do not divert your attention
during downloads.
PS: It happened only once during the download I did where the panel did not return after the
restart and did not show any information on the display and also did not communicate. I had to
send the 3-CPU3 to EST. It's rare, but it can happen.